Zone Pressure Sensors (ZPS) - BACK MOUNT
Installation and Operation Instructions
4/6/07rev.
Specifications subjectto changewithout notice.
3 of 3
POSSIBLE SOLUTIONS:
- Check power connections for proper power
- The unit may be performing an auto-zero. Wait 10 seconds and check again.
- The dip switches are in an unsupported configuration, check the dip switch
settings, both pressure and output, and change them to ranges desired
-Remove pressurefromports andperformauto-zero procedure
-Check dipswitches forproperpressure rangeselection
-Check dip switchesfor properoutput rangeselection
Switch 8 is reserved for Factory use, leave in the off position.
To adjust the pressure range, set dip switches 1-4 to the desired pressure range using the the label found inside the
cover of the ZPS unit (or shown on this pg 2). Moving the Bi-Directional dip switch (#4) to the up position doubles
the pressure range. For example, the 0 to .25” W.C. range becomes -.25” to .25” W.C. if the Bi-Directional dip
switch is in the up position.
Note: If any of the switches are placed in an undefined combination the LED will fast blink and the output will be forced
to 4mA or zero volts.
Pressure Range Select
Auto-Zero Select
To auto zero the BAPI ZPS, remove the tubing
from the pressure ports (to remove the normal
pressure source). Make sure that the pres-
sure ports are sheltered from any drafts,
including the technician’s breath. Ideally the
two ports should be connected together with a
short piece of tubing. Turning on switch 7
starts the auto-zero process. Switches 1 through 6 may be in any allowed
configuration. The LED will blink at a fast rate and the output will be
forced to zero (4mA or 0V) while the auto-zero is being performed. When
the LED blinks at a slow rate, turn off switch 7 and reconnect the pressure
source.
Fig. 10 Auto-Zero
Diagnostics
Before
auto-zero During
auto-zero After
auto-
zero
Switch 8
PROBLEMS:
LED does not light
LED is blinking fast
(1/2 second on, 1/2 second off)
Output stuck (high or low)
Output not tracking pressure properly
To adjust the output range, set dip switches 5 & 6 to the desired output range using the the label found inside the
cover of the ZPS unit (or shown on pg 2).
Note: If any of the switches are placed in an undefined combination the LED will fast blink and the output will be forced
to 4mA or zero volts.
Output Range Select
LED off No Power
LED Blinking 1/2 sec on, 1/2 sec off Auto-zero or dip switch in undefined configuration
LED on Normal operation
LED Blinking 1/2 sec on, 4 sec off Auto-zero complete
LED Operation