Basler BE1-50/51M-222 User manual

RELAY
OVERCURRENT
BE1-50/51M-222
S
T
U
I
N
+
T
E
N
S
S
T
I
N
U
+
E
N
T
T
H
S
S
H
T
T
N
E
+
U
N
I
T
S
(0.5 MIN. SET)
PICKUP
DIAL
PICKUP
MANUAL TRIP
TIME
MANUAL TRIP
PICKUP
0
0
0
0
0
Hi
g
hland, Illinois
Basler Electric
R
S
0
CURVE
INST
TIME
RESET
D2644-12
08-18-97
INSTRUCTION MANUAL
FOR
OVERCURRENT RELAY
BE1-50/51M-222
Publication Number: 9 2520 00 984
Revision: A 12/99

i
W A R N I N G !
To avoid personal injury or equipment damage, only
qualified personnel should perform the procedures
presented in this manual.
INTRODUCTION
This manual provides information concerning the operation and installation
of the BE1-50/51M-222 Overcurrent Relay. To accomplish this, the
following is provided.
Specifications
Functional description
Mounting information
Setting procedure/example.

ii
CONFIDENTIAL INFORMATION
OF BASLER ELECTRIC COMPANY, HIGHLAND, IL. IT IS LOANED FOR
CONFIDENTIAL USE, SUBJECT TO RETURN ON REQUEST, AND WITH THE
MUTUAL UNDERSTANDING THAT IT WILL NOT BE USED IN ANY MANNER
DETRIMENTAL TO THE INTEREST OF BASLER ELECTRIC COMPANY.
First Printing: August 1997
Printed in USA
© 1997, 1999 Basler Electric Co., Highland, IL 62249
December 1999
It is not the intention of this manual to cover all details and variations
in equipment, nor does this manual provide data for every possible
contingency regarding installation or operation. The availability and
design of all features and options are subject to modification without
notice. Shouldfurtherinformationberequired,contactBaslerElectric
Company, Highland, Illinois.
BASLER ELECTRIC, BOX 269, HIGHLAND, IL 62249 USA
PHONE 618-654-2341 FAX 618-654-2351

iii
CONTENTS
SECTION 1 GENERAL INFORMATION 1-1
Description ............................................. 1-1
Application ............................................. 1-1
General ............................................. 1-1
Load Demand Curve .................................. 1-2
Specifications ........................................... 1-3
Characteristic Curves ..................................... 1-8
SECTION 2 CONTROLS AND INDICATORS 2-1
SECTION 3 FUNCTIONAL DESCRIPTION 3-1
General ................................................ 3-1
Functional Description .................................... 3-1
Sensing Input ........................................ 3-1
Power Supply ........................................ 3-1
Instantaneous Signal .................................. 3-1
Time Signal ......................................... 3-1
Microprocessor ....................................... 3-1
Power-Off Sensing .................................... 3-2
Outputs ............................................. 3-2
SECTION 4 INSTALLATION 4-1
General ................................................ 4-1
Dielectric Test ........................................... 4-1
Mounting ............................................... 4-1
Outline Dimensions ....................................... 4-2
Panel Drilling Diagram, C1 Case ............................ 4-3
Connections ............................................ 4-4
AC Input Connections .................................. 4-4
DC Control Connections ................................ 4-5
BE1-50/51M-222 Overcurrent Relay, Rear View ................ 4-6
SECTION 5 TESTING 5-1
General ................................................ 5-1
Dielectric Test ........................................... 5-1
Operational Test Procedure ................................ 5-1
Test Equipment Required ............................... 5-1
Pickup and Timing Test Setup ........................... 5-2
Target Operational Test Setup ........................... 5-2
Test Procedure ....................................... 5-3
Setting the Relay ........................................ 5-6
Periodic Tests ........................................... 5-6
General ............................................. 5-6
Periodic Test ........................................ 5-6

iv
CONTENTS - Continued
SECTION 6 MAINTENANCE 6-1
General ................................................ 6-1
In-House Repair ......................................... 6-1
Storage ................................................ 6-1
Periodic Tests ........................................... 6-1
General ............................................. 6-1
Periodic Test ......................................... 6-2
SECTION 7 MANUAL CHANGE INFORMATION 7-1

1-1
SECTION 1
GENERAL INFORMATION
DESCRIPTION
BE1-50/51M-222OvercurrentRelaysaremicroprocessorbased,non-directionalphaseorgroundrelaysthat
monitor the magnitude of a single phase ac current to provide accurate instantaneous and time overcurrent
protection for 50 hertz or 60 hertz power systems. The BE1-50/51M-222 Overcurrent Relay is a special,
modified relay with software for a
Load Demand Characteristic Curve
in place of the short inverse standard
curve. To select the
Load Demand Characteristic Curve
, position the CURVE select switch to position S.
APPLICATION
General
The wide range of pickup settings and front panel selectable time characteristics permit applications
involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements.
Integratingresetfunctionsareavailabletosimulatethediskresetofelectromechanicalrelays. BE1-50/51M-
222 Overcurrent Relays have the following standard features.
&Independent time and instantaneous elements.
&A secure method to manually trip the breaker at the relay front panel.
&Direct reading front panel controls.
&Minimum pickup setting for safety during installation.
&Time characteristics extend to a pickup multiple of 40.
&Rugged draw-out construction with steel case.
&Magnetic latching targets retain indication without power.
&Built-in accuracy eliminates internal adjustments.
&Minimum transient overreach.
&Field selectable instantaneous or integrating reset.
&Field selectable 50 or 60 hertz operation.
&Field selectable fixed instantaneous delay (0.0, 0.1, 0.2, or 0.3 second).
Individual models are available for 1 ampere and 5 amperes sensing input currents. BE1-50/51M-222
Overcurrent Relays must be removed from the case and installed on a test bench for testing. Shorting
contacts are provided for all current inputs when the relay chassis is removed from the relay case. Figure
1-1 shows the front panel of the BE1-50/51M-222 Overcurrent Relay, in a C1, vertical mount case.
BE1-50/51M-222OvercurrentRelayshavemanyadvantagesoverotherovercurrentrelays. Thefiveprimary
advantages are:
&Time characteristics are defined by equations and graphs.
&Field selectable time characteristics.
&Very low burden.
&Self powered from the sensed current.
&Continuous automatic calibration.

BE1-50/51M-222 General Information
1-2
RELAY
OVERCURRENT
BE1-50/51M-222
S
T
U
I
N
+
T
E
N
S
S
T
I
N
U
+
E
N
T
T
H
S
S
H
T
T
N
E
+
U
N
I
T
S
(0.5 MIN. SET)
PICKUP
DIAL
PICKUP
MANUAL TRIP
TIME
MANUAL TRIP
PICKUP
0
0
0
0
0
Hi
g
hland, Illinois
Basler Electric
R
S
0
CURVE
INST
TIME
RESET
D2644-12
08-18-97
Figure 1-1. BE1-50/51M-222 Overcurrent Relay, C1 Case
Load Demand Curve
Scenario
Configure the relay such that when the sensed current is:
1.05 times pickup Time to trip 1.0 hour
1.2 times pickup Time to trip 1.0 hour
1.5 times pickup Time to trip 2.0 minutes
4.0 times pickup Time to trip 0.2 seconds
6.0 times pickup Time to trip 0.2 seconds
Settings
Position the following switches as designated. (Switch locations are shown in Section 2,
Controls And
Indicators
.) Figure 1-2 is a graph showing the timing for the application scenario.
SW8-1 Select nominal operating frequency
SW8-2 OFF (open) no instantaneous delay
SW8-3 OFF (open) no instantaneous delay
SW8-4 ON (closed) integrating reset selected
TIME DIAL 4.0
CURVE S
TIME PICKUP Select preferred time pickup level
INST PICKUP Select preferred instantaneous pickup level

BE1-50/51M-222 General Information
1-3
0.01
0.1
1
10
100
1000
10000
11040
Instantaneous
Tap = 5 amps.
Time Tap = 1amp.
Curve S
Time Dial 4.0
1
2
3
4
5
MULTIPLE OF PICKUP
TIME IN SECONDS
Figure 1-2. Load Demand Characteristic Curve
SPECIFICATIONS
BE1-50/51M-222 Overcurrent Relays have the following features and capabilities.
Current Sensing Input Continuous current: 14 amperes. One second current: 400 amperes.
TIME PICKUP Range 0.5 to 15.9 amperes in 0.1 ampere steps. Setting the TIME PICKUP to the
minimum pickup (0.5 ampere), places the relay in the most sensitive state
and may be used as a safety setting.
TIME Dropout Dropout occurs at 95% of pickup value.

BE1-50/51M-222 General Information
1-4
TIME PICKUP
Accuracy ±2% ±25 milliamperes at or above 0.5 ampere settings.
Frequency Response A change of ±5 hertz from the nominal 50/60 hertz current causes less
than 0.5% change in the current required for pickup.
TIME DIAL Range 0.0 to 9.9, in 0.1 steps.
INST PICKUP Range 1 to 99 amperes in 1 ampere steps. Setting the INST PICKUP to the
minimum pickup (1.0), places the relay in the most sensitivestate and may
be used as a safety setting.
INST Dropout Dropout occurs at 95% of pickup value.
INST PICKUP
Accuracy ±2% ±25 milliamperes at or above 1.0 ampere settings.
Frequency Response A change of ±5 hertz from the nominal 50/60 hertz current causes less
than 0.5% change in the current required for pickup.
INST Transient Response Less than 10% overreach with system time constants up to 40
milliseconds.
Burden Burden is non-linear. At 0.5 amperes, Z = 4.8 ohms. At 5.0 amperes,
Z = 0.2 ohms. (Figure 1-3 illustrates the device burden.)
Figure 1-3. Device Burden Characteristics

BE1-50/51M-222 General Information
1-5
Harmonic Response BE1-50/51M-222 harmonic rejection is illustrated in Figure 1-4.
Figure 1-4 shows that a relay set for one ampere pickup would pickup at
0.96 ampere on a current containing 40% seventh harmonic. This
corresponds to a ten-to-one rejection ratio. Other conditions may be
evaluated in the same manner.
Figure 1-4. Harmonic Response
INST Characteristics BE1-50/51M-222 instantaneous characteristic curves are similar to
standard electromechanical instantaneous units. However, the time to trip
for ground applications is slightly longer than that for phase applications to
allow time to power-up the relay. Longer trip time for ground applications
is beneficial because it helps to avoid nuisance trips.
For phase applications, the maximum time to trip is 3.5 cycles at a pickup
multiple of 1.0, and 1.5 cycles at a pickup multiple of 3.0. The
corresponding times for ground applications are 4.5 and 1.75 cycles.
Figure 1-5 shows the instantaneous characteristic curves for maximum
time to trip.
Additional delays of 0.1, 0.2, or 0.3 seconds may be added with internal
switches SW8-2 and -3. These delays apply to both phase and ground
applications. Closing switch SW8-2 provides an additional delay of 0.1
second. Closingswitch SW8-3provides an additionaldelay of0.2 second.
Closing both switches SW8-2 and -3 provides an additional delay of 0.3
second. Section 2 illustrates the location of SW8.
Time Characteristics Nine inverse time functions and one fixed time function can be selected by
a front panel switch.

BE1-50/51M-222 General Information
1-6
Figure 1-5. Instantaneous Characteristic Curves
Time Reset Reset occurs when the current drops below pickup and the relay has not
timed out. Switch SW8-4 provides selection of either an instantaneous or
integrating reset characteristic. Opening SW8-4 forces the instantaneous
reset timer to zero when timed dropout occurs. This fast reset
characteristic prevents the ratcheting effect that may occur with repeating
system faults. Closing SW8-4 selects the integrating reset characteristic.
The integrating reset characteristic simulates the disk reset of
electromechanical relays. BE1-50/51M-222 relays provide the integrating
reset function even when input current falls to zero. Integrating reset
characteristics are shown in Figure 1-6.
Target Indicators Magnetically latched, manually reset targets indicate that current of 0.2
amperes or greater was present in the trip circuit. Target coil resistance is
less than 0.1 ohm and operate time is less than one millisecond. See
50/51 Output specifications for maximum current rating.

BE1-50/51M-222 General Information
1-7
0.1
1
10
100
1000
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Multi
p
le of Ta
p
xD (Seconds)
SL
I
C
E
V
B
M
F
D
This chart vertical axis x D (Seconds) is applicable for all curves and is derived from
multiplying the curve selected times D(the TIME DIAL setting).
Figure 1-6. Integrating Reset Characteristic Curve
50/51 Output Output contacts are surge protected and rated as follows:
Resistive:
120/240 Vac Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
minutes, 3 amperes continuously, and break 5 amperes.
125/250 Vdc Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
minutes, 3 amperes continuously, and break 0.3 ampere.
Inductive:
120/240 Vac, Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
125/250 Vdc minutes, 3 amperes continuously, and break 0.3 ampere. 0.3 amperes.
(L/R = 0.04).
AUX Output Output contacts can be configured in the field using jumpers to select
closing on either/or timed or instantaneous trip. Output contacts are surge
protected and rated as follows:
Resistive:
120/240 Vac Make 30 amperes for 0.2 seconds, carry 7 amperes continuously, and
break 5 amperes.
125/250 Vdc Make 30 amperes for 0.2 seconds, carry 7 amperes continuously, and
break 0.3 ampere.
Inductive:
120/240 Vac, Make and carry 30 amperes for 0.2 seconds, carry 7 amperes
125/250 Vdc continuously, and break 0.3 ampere. (L/R = 0.04).

BE1-50/51M-222 General Information
1-8
Isolation Meets IEC 255-5 and exceeds IEEE C37.90-1989, one-minute dielectric
(high potential) tests as follows:
All circuits to ground: 2828 Vdc
Input to Output Circuits 2000 Vac or 2828 Vdc
Surge Withstand Capability
Oscillatory
Qualified to IEEE C37.90.1-1989 5VCPFCTF 5WTIG9KVJUVCPF
%CRCDKNKV[59%6GUVUHQT2TQVGEVKXG4GNC[UCPF4GNC[5[UVGOU
Fast Transient
Qualified to IEEE C37.90.1-1989
Standard Surge Withstand
Capability (SWC) Tests for Protective Relays and Relay
Fast Transient Qualified to IEEE C37.90-1989.
Impulse Test Qualified to IEC 255-5.
Radio Frequency Field tested using a five watt, hand held transceiver operating at random
Interference (RFI) frequencies centered around 144 megahertz and 440 megahertz, with the
antenna located six inches from the relay in both horizontal and vertical
planes.
Temperature Operating Range
-40(C (-40(F) to 70(C (158(F)
Recommended Storage Range
-50(C (-58(F) to 50(C (122(F).
Shock 15 g in each of three mutually perpendicular planes.
Vibration 2 g in each of three mutually perpendicular planes swept over the range of
10 to 500 hertz for a total of six sweeps, 15 minutes each sweep.
Case C1.
Weight 8.6 pounds.
CHARACTERISTIC CURVES
Figures 1-7 through 1-15 illustrate the characteristic curves that are programmed into the nonvolatile
memory of this relay. To order full-size drawings of these characteristic curves, contact the Customer
Service Department of the Power Systems Group, Basler Electric, and request the 99-(4 digit) number
associated with each graph. These graphs are full size characteristic curves on transparent paper (vellum).

BE1-50/51M-222 General Information
1-9
MULTIPLES OF PICK-UP
Figure 1-7. Time Characteristic Curve 99-1610, Load Demand Curve

BE1-50/51M-222 General Information
1-10
MULTIPLES OF PICK-UP
Figure 1-8. Time Characteristic Curve, 99-1370, L-Long Inverse

BE1-50/51M-222 General Information
1-11
MULTIPLES OF PICK-UP
Figure 1-9. Time Characteristic Curve, 99-1371, D-Definite Time

BE1-50/51M-222 General Information
1-12
MULTIPLES OF PICK-UP
Figure 1-10. Time Characteristic Curve, 99-1372, M-Moderately Inverse

BE1-50/51M-222 General Information
1-13
MULTIPLES OF PICK-UP
Figure 1-11. Time Characteristic Curve, I-Inverse

BE1-50/51M-222 General Information
1-14
MULTIPLES OF PICK-UP
Figure 1-12. Time Characteristic Curve, 99-1374, V-Very Inverse

BE1-50/51M-222 General Information
1-15
MULTIPLES OF PICK-UP
Figure 1-13. Time Characteristic Curve, 99-1375, E-Extremely Inverse
Table of contents
Other Basler Relay manuals

Basler
Basler BE1-50/51M-100 Series User manual

Basler
Basler BE1-27 User manual

Basler
Basler BE1-51 User manual

Basler
Basler BE1-59N User manual

Basler
Basler BE1-87G User manual

Basler
Basler BE1-50/51B-225 User manual

Basler
Basler BE1-87B User manual

Basler
Basler BE1-59NC User manual

Basler
Basler BE1-50M User manual

Basler
Basler BE1-79 User manual

Basler
Basler BE1-79A User manual

Basler
Basler BE1-81O/U User manual

Basler
Basler V3E Z1P B2C1F User manual

Basler
Basler BE1-951 User manual

Basler
Basler BE1-51 User manual

Basler
Basler BE1-50BF User manual

Basler
Basler BE1-50/51B-217 User manual

Basler
Basler BE1-51M User manual

Basler
Basler BE1-59N User manual

Basler
Basler BE1-40Q User manual