All HMI panels are developed to satisfy the demands of human-machine communication. Built-in
functions such as displaying and controlling text, dynamic indication, time channels, alarm and
recipe handling are included. The HMI panel works primarily in an object-oriented way, making it
easy to understand and use. Configuration is carried out on a PC using iX Developer software. The
project can then be transferred and stored in the HMI panel itself. Various types of automation
equipment such as PLCs, servos or drives can be connected to the HMI panels. In this manual, the
term “the controller” refers to the connected equipment. This manual explains how to install the
HMI panel. Please refer to the iX Developer reference manual for further information.
Copyright © 2023 Beijer Electronics AB. All rights reserved.
The information in this document is subject to change without notice and is provided as availa-
ble at the time of printing. Beijer Electronics AB, including all its group companies, reserves
the right to change any information without updating this publication. Beijer Electronics AB, in-
cluding all its group companies, assumes no responsibility for any errors that may appear in this
document. Read the entire installation manual prior to installing and using this equipment. Only
qualified personnel may install, operate or repair this equipment. Beijer Electronics AB, includ-
ing all its group companies, are not responsible for modified, altered or renovated equipment.
Because the equipment has a wide range of applications, users must acquire the appropriate
knowledge to use the equipment properly in their specific applications. Persons responsible
for the application and the equipment must themselves ensure that each application is in
compliance with all relevant requirements, standards and legislation in respect to configuration
and safety. Only parts and accessories manufactured according to specifications set by Beijer
Electronics AB, including all its group companies, may be used.
BEIJER ELECTRONICS AB, INCLUDING ALL ITS GROUP COMPANIES, SHALL NOT BE LIABLE TO
ANYONE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULT-
ING FROM THE INSTALLATION, USE OR REPAIR OF THIS EQUIPMENT, WHETHER ARISING IN TORT,
CONTRACT, OR OTHERWISE. BUYER'S SOLE REMEDY SHALL BE THE REPAIR, REPLACEMENT, OR
REFUND OF PURCHASE PRICE, AND THE CHOICE OF THE APPLICABLE REMEDY SHALL BE AT THE
SOLE DISCRETION OF BEIJER ELECTRONICS AB, INCLUDING ALL ITS GROUP COMPANIES.
Head Office
Beijer Electronics AB
Box 426
201 24 Malmö, Sweden
www.beijerelectronics.com / +46 40 358600

Table of Contents
1. Safety Precautions ........................................................................................ 5
1.1. General ............................................................................................ 5
1.2. Hazardous Materials ............................................................................. 5
1.3. Disposal Requirements Under WEEE Regulations ............................................ 6
1.4. UL and cUL Installation .......................................................................... 6
1.5. During Installation ................................................................................ 7
1.6. During Use ......................................................................................... 7
1.7. Service and Maintenance ........................................................................ 7
1.7.1. Cleaning the Display .................................................................... 8
1.8. Dismantling and Scrapping ...................................................................... 8
1.9. Appearance of Air in Touch Screen ............................................................ 8
2. Naming Convention ...................................................................................... 10
3. Installation ................................................................................................ 11
3.1. Space Requirements ............................................................................ 11
3.2. Installation Process ............................................................................. 11
3.2.1. Connections to the Controller ........................................................ 13
3.2.2. Other Connections and Peripherals .................................................. 13
4. Technical Data ............................................................................................ 14
4.1. Compass Safe Distance ......................................................................... 15
5. Chemical Resistance ..................................................................................... 16
5.1. Metal Casing ...................................................................................... 16
5.2. Touch Screen and Overlay Material ........................................................... 16
5.2.1. Protective Film ......................................................................... 16
5.2.2. Touch Screen Surface .................................................................. 17
5.2.3. Touch Screen Protector ................................................................ 17
6. HMI Panel Drawings ...................................................................................... 18
6.1. Connectors ....................................................................................... 18
6.1.1. Communication Ports .................................................................. 18
6.2. HMI Panel Outline ............................................................................... 19
7. Additional Installation Tips ............................................................................. 21
7.1. Grounding the HMI Panel ....................................................................... 21
7.2. Ethernet Connection in the HMI Panel ....................................................... 22
7.3. To Achieve Better EMC Protection ............................................................ 23
7.4. Ambient Temperature .......................................................................... 24
7.5. Safety ............................................................................................. 25
7.6. Galvanic Isolation ............................................................................... 26
7.7. Cable and Bus Termination RS-485 ........................................................... 27
7.8. CAN Interface .................................................................................... 27
7.8.1. Cable Recommendations .............................................................. 27
7.8.2. Termination ............................................................................. 27
7.8.3. Restrictions and Recommendations .................................................. 28
7.9. USB Flash Drive .................................................................................. 28
7.10. Image Sticking .................................................................................. 28
Beijer Electronics, MAEN265 3 2023-09

4

1. Safety Precautions
Both the installer and users of the HMI panel must read and understand this manual.
1.1. General
• Read the safety precautions carefully.
• Check the delivery for transportation damage. If damage is found, notify the supplier as soon as
possible.
• Do not use the HMI panel in an environment with high explosive hazards.
• The supplier is not responsible for modified, altered, or reconstructed equipment.
• Use only parts and accessories manufactured according to specifications of the supplier.
• Read the installation and operating instructions carefully before installing, using or repairing the
HMI panel.
• Never allow fluids, metal filings or wiring debris to enter any openings in the HMI panel. This may
cause fire or electrical shock.
• Only qualified personnel may operate the HMI panel.
• Storing the HMI panel where the temperature is lower or higher than recommended in this manual
can cause the LCD display liquid to congeal and become isotropic.
• The LCD display liquid contains a powerful irritant. In case of skin contact, wash immediately with
plenty of water. In case of eye contact, hold the eye open, flush with plenty of water and get
medical attention.
• The figures in this manual serve an illustrative purpose. Because of the many variables associated
with any particular installation, the supplier cannot assume responsibility for actual use based on
the figures.
• The supplier neither guarantees that the HMI panel is suitable for your particular application, nor
assumes responsibility for your product design, installation or operation.
• It is recommended to turn on and shut down the HMI panel at least once before installing any
components or cards, or before connecting the HMI panel to external devices, for example serial
devices.
• For Marine panels only:
• The HMI panel must be installed and operated as described in this document to meet this
certification.
• Observe precautions for handling electrostatic discharge sensitive devices.
1.2. Hazardous Materials
Part description
零件描述
Toxic and hazardous materials or elements
有毒和有害的材料或元素
PCB and electronic components
PCB 和电子元件
Pb Hg Cd Cr6+ PBB PBDE
X O O O O O
O: Indicates that the concentration of the hazardous substance in all homogeneous materials in the
parts is below the relevant threshold of the GB/T 26572-2011 standard.
O: 表示该有害物质在该部件所有均质材料中的含量均在 GB/T 26572-2011 规定的限 量要求以下。
Safety Precautions
Beijer Electronics, MAEN265 5 2023-09

X: Indicates that the concentration of the hazardous substance of at least one of all homogeneous
materials in the parts is above the relevant threshold of the GB/T 26572-2011 standard. But still
complies with the EU RoHS Directive 2011/65/EU.
X: 表明该有害物质至少在部件的某一均质材料中的含量超出 GB/T 26572-2011 规定 的限量要求。但仍然
符合 EU RoHS 指令 2011/65/EU。
1.3. Disposal Requirements Under WEEE Regulations
For professional users in the European Union: If you wish to discard electrical and electronic
equipment (EEE), please contact your dealer or supplier for further information.
For disposal in countries outside of the European Union: If you wish to discard this product please
contact your local authorities or dealer and ask for the correct method of disposal.
1.4. UL and cUL Installation
CAUTION
This section is only valid for UL labeled X2 panels.
• This equipment is suitable for use in Class 2 non-hazardous locations only.
[Combinations of equipment in your system are subject to investigation by the local authority
having jurisdiction at the time of installation].
• All devices have to be supplied by a Class 2 power supply.
WARNING
• Only UL and cUL approved expansion units are allowed to be connected to the
port designated “EXPANSION”. At the moment there are no such units evaluated or
allowed.
SEULES LES UNITÉS D'EXTENSION CERTIFIÉES UL ET cUL PEUVENT ÊTRE RACCORDÉES
AU PORT DÉSIGNÉ «EXPANSION». À L'HEURE ACTUELLE, AUCUNE UNITÉ DE CE TYPE
N'A ÉTÉ TESTÉE OU AUTORISÉE.
• Explosion hazard! Substitution of components may impair suitability for Class I,
Division 2.
RISQUE D’EXPLOSION! LA SUBSTITUTION DE COMPOSANTS PEUT NUIRE Á LA
CONFORMITÉ DE CLASSE I, DIVISION 2.
• Battery may explode if mistreated. Do not recharge, disassemble or dispose of in
fire.
LA BATTERIE PEUT EXPLOSER EN CAS DE MAUVAISE MANIPULATION. NE LA
RECHARGEZ PAS, NE LA DÉMONTEZ PAS ET NE LA JETEZ PAS DANS LE FEU.
• This product contains a battery; this must only be changed in an area known to be non-hazardous.
• Replace the battery with a BR2032 battery. Use of another type of battery may present a risk of
fire or explosion.
• For use on a flat surface of a type 4X enclosure indoor use only.
• Use minimum 75°C copper conductors only.
• To make wiring connections to the power supply connector, follow the table with cable and torque
specifications below:
Safety Precautions
2023-09 6 Beijer Electronics, MAEN265

Terminal Block Connector Wire Size AWG Torque (Lb.In.)
X1/X100 Phoenix connectors AWG 30 – 12 5 – 7
X1/X100 Anytek connectors AWG 24 – 12 3.5
X1/X100 DECA connectors AWG 24 – 12 7
• These devices are Class 2 supplied programmable controllers (industrial PCs) for the use in
industrial control equipment and are intended to be (front) panel mounted (Type 12 and 4x for
indoor use only).
CAUTION
The enclosure provides a degree of protection of at least IP20, but when installed in
an apparatus, it should meet IP65.
LE BOÎTIER OFFRE UN DEGRÉ DE PROTECTION D'AU MOINS IP20, MAIS LORSQU'IL EST
INSTALLÉ DANS UN APPAREIL, IL DOIT ÊTRE DE CLASSE IP65.
1.5. During Installation
• The operator panel is designed for stationary installation on a planar surface, where the following
conditions are fulfilled:
• no high explosive risks
• no strong magnetic fields
• no direct sunlight
• no large, sudden temperature changes
• Install the HMI panel according to the accompanying installation instructions.
• Ground the HMI panel according to the accompanying installation instructions.
• Only qualified personnel may install the HMI panel.
• Separate the high voltage, signal, and supply cables.
• Make sure that the voltage and polarity of the power source is correct before connecting the HMI
panel to the power outlet.
• Peripheral equipment must be appropriate for the application and location.
1.6. During Use
• Keep the HMI panel clean.
• Emergency stop and other safety functions may not be controlled from the HMI panel.
• Do not use excessive force or sharp objects when operating the touch screen.
1.7. Service and Maintenance
• Only qualified personnel should carry out repairs.
• The agreed warranty applies.
• Before carrying out any cleaning or maintenance operations, disconnect the equipment from the
electrical supply.
• Clean the display and surrounding front cover with a soft cloth and mild detergent.
• The battery must be replaced by an authorized Beijer Electronics service center.
Safety Precautions
Beijer Electronics, MAEN265 7 2023-09

1.7.1. Cleaning the Display
We recommend using a dry, clean cloth to wipe off dust regularly. Use alcohol or ammonia-based
cleaning agent for cleaning only when necessary. When other solvents or cleaning agents are used,
be sure to follow manufacturers’ instructions. The agent should be applied to a clean cloth and
should not be sprayed directly onto the panel surface. After cleaning the agent should be removed.
Ammonia-based glass cleaners (typically 5-10% ammonia) or 75% alcohol can be used to clean the
surface of PCAP and resistive touch panels. When you clean the surface of your touch panel, please
follow these steps:
1. Apply cleaning agent (alcohol, bleach, or glass cleaner) to a clean cloth.
Make sure the cloth is well saturated.
2. Wipe the touch panel surface in a “Z” motion (see illustration below).
3. Dry the panel thoroughly with a dry cloth, removing as much of the cleaning solution as possible.
4. Do not mix bleach and ammonia because this will produce a dangerous chemical reaction.
5. Please do not spray cleaning solution directly onto the touch panel surface.
NOTE
• Cleaning solutions containing bleach, alcohol, and ammonia are corrosive to touch
panel surface coatings and ITO film. Do not leave the solution on the touch panel
surface for more than 2 minutes. Make sure to remove all residue when finished
cleaning.
• Do not use sharp tools to clean the surface of the touch screen.
• Do not use air guns, water jets, or steam, to clean the surface of the touch screen
as they may damage touch screen functionality.
• If condiments, food, or drinks are spilled on the surface of the touchscreen, please
remove it immediately.
• Ensure moisture does not seep through the cable connection area from the edges
during cleaning.
1.8. Dismantling and Scrapping
• Recycle the HMI panel and parts of it according to local regulations.
• The following components contain substances that might be hazardous to health and the
environment: lithium battery, electrolytic capacitor, and display.
1.9. Appearance of Air in Touch Screen
The layer structure of the touch screen contains air. In rare cases, the appearance of bubbles can
arise. This is purely cosmetic and does not affect the functionality of the HMI panel. The appearance
Safety Precautions
2023-09 8 Beijer Electronics, MAEN265

can occur under certain environmental conditions such as changes in temperature, humidity, or
atmospheric pressure.
Safety Precautions
Beijer Electronics, MAEN265 9 2023-09

2. Naming Convention
The name of each panel is based on its properties according to the table below.
Naming Convention
X2 family Size (inches) Generation/Version Variant
base
pro
marine (= with BL)
control (= with SC)
motion (= with SM)
extreme
4
5
7
10
12
15
21
v2 SC
SM
HB
HP
BL
12V
SL
RO
CO
web
Soft Control
Soft Motion
High Brightness
High Performance
Black
12 Volt
Sealed
Rugged Only
Certification Only
Web
Examples:
• X2 base 5 v2
• X2 pro 7
• X2 control 10
• X2 marine 12 SC
• X2 marine 15 HB SC
• X2 extreme 7 12V*
• X2 extreme 12 HP SC*
• X2 extreme 7 SL HP*
• X2 extreme 12 SL HP SC*
• X2 extreme 7 CO*
• X2 extreme 12 SL HP RO
NOTE
Not all combinations are available.
NOTE
* indicates variants including IECEx\ATEX and C1D2 accreditation.
Naming Convention
2023-09 10 Beijer Electronics, MAEN265

3. Installation
3.1. Space Requirements
• Maximum installation plate thickness: 11 mm.
The following drawings show the space requirements in millimeters when installing the HMI panel.
The drawings are only illustrative and may be out of proportion.
50 mm
50 mm
100 mm
100 mm
100 mm
204 mm
143 mm
43 mm
3.2. Installation Process
The following is needed:
• A Phillips/slot screwdriver
Do the following:
1. Unpack and check the delivery. If damage is found, notify the supplier.
NOTE
Place the on a stable surface during installation. Dropping the HMI panel or
letting it fall may cause damage.
2. To cut a correct opening for the HMI panel, use the cut out dimensions in the outline drawing.
A separate cut out drawing is available for download from the Beijer Electronics web site. For
more information, see chapters HMI Panel Drawings and Technical Data.
3. Make sure that the mounting surface of the cutout is smooth and cleaned from any burrs or
debris.
4. Install the HMI panel into the cutout.
Installation
Beijer Electronics, MAEN265 11 2023-09

5. Secure the HMI panel in position, using all the fastening holes and the provided brackets and
screws.
x 4 or 8
Tighten the screws to 0.5 - 1.0 Nm.
6. In cases where the front panel seal (IP54 or greater, NEMA-4X) is critical, use a torque wrench to
ensure all screws are torqued within the specification above.
7. Connect the cables in the specified order, according to the following drawing and steps.
24V DC
RS232/
RS422/
RS485
24V DC
A
D
Controller
Power
B
Ethernet
C
The image is illustrative only and may differ slightly from the actual panel.
• Connect cable A.
• Connect cable B, using 14-20 AWG (2.08–0.52 mm2), 180–220 N-cm torque.
• Connect cable C.
• Connect cable D. The recommended cross-section of the cable is 1.5 mm2.
8. Carefully remove the protective film over the HMI panel display, taking care to avoid static
electricity that could damage the panel.
Installation
2023-09 12 Beijer Electronics, MAEN265

CAUTION
• The HMI panel must be brought to ambient temperature before it is started up. If
condensation forms, ensure that the HMI panel is dry before connecting it to the
power outlet.
• Ensure that the HMI panel and the controller system have the same electrical
grounding (reference voltage level), otherwise errors in communication may occur.
• Ensure that the voltage and polarity of the power source is correct.
• Separate high voltage cables from signal and supply cables.
• Shielded communication cables are recommended.
3.2.1. Connections to the Controller
For information about the cables to be used when connecting the HMI panel to the controller, please
refer to the help file for the driver in question.
3.2.2. Other Connections and Peripherals
Cables, peripheral equipment and accessories must be suitable for the application and its
environment. For further details or recommendations, please refer to the supplier.
Installation
Beijer Electronics, MAEN265 13 2023-09

4. Technical Data
Parameter X2 pro 7 - B2
Front panel, W×H×D 204 × 143 × 7 mm
Cutout dimensions, W×H 189 × 128 mm
Mounting depth 43 mm (143 mm including clearance)
Standalone mounting VESA 75 × 75
Note: Maximum screw length for VESA mounting is 4 mm. Usage of
longer screws may lead to damage.
Front panel seal IP 65
Rear panel seal IP 20
Touch screen material Polyester on glass, ITO film, resistive
Frame overlay Autoflex EBA 180L
Touch screen operations 1 million finger touch operations
Reverse side material Powder-coated aluminum
Frame material Powder-coated aluminum
Weight 0.8 kg
CPU i.MX6 Solo
Single ARM Cortex-A9 Core
1.0GHz
512 kB L2 cache
Serial ports StandardD-sub (9 Pin, female)
COM1: RS-232 with RTS/CTS
COM2: RS-422/RS-485
COM3: RS-485
1×RS-232 Rx/Tx with RTS/CTS and 1×RS-422 or 2×RS-485.
Ethernet LAN A 10/100 Mbit Base-T (shielded RJ45 with LEDs)
Ethernet LAN B 10/100 Mbit Base-T (shielded RJ45 with LEDs)
USB 1 × USB Host 2.0, max output current 500 mA
Supports up to USB 2.0 High Speed
External storage media 1 × SD card
Flash memory
(application memory)
1.5 GB SSD (eMMC)
Memory RAM 512 MB (DDR3)
NVRAM N/A
LED 1 × Multi color
Real time clock Yes
Battery BR 2032 lithium battery
replaceable
Technical Data
2023-09 14 Beijer Electronics, MAEN265

Parameter X2 pro 7 - B2
Power consumption at
rated voltage
14.4 W
Fuse Internal DC fuse, 3.14 AT, 5 × 20 mm
Power supply +24 VDC (18–32 V DC)
CE: The power supply must conform with the requirements
according to EN/IEC 60950 and EN/IEC 61558-2-4.
UL and cUL: The power supply must conform with the
requirements for class 2 power supplies.
Display TFT-LCD with LED backlight
800 × 480 pixels, 64k colors
Active area of display 7” diagonal
Pixel errors Class I (ISO 9241-307)
Backlight brightness 350 Cd/m2
Backlight lifetime 20,000 hours
Operating temperature -10°C to +60°C
Storage temperature -20°C to +70°C
Relative humidity in
operation
5 - 85% non-condensation
Vibration 1g, according to IEC 60068-2-6, Test Fc
Mechanical shock 15g, half-sine, 11ms according to IEC60068-2-27
Approvals and
certifications
CE/FCC/KCC Information is available on
www.beijerelectronics.com
UL approval Information is available on www.beijerelectronics.com and
UL.com
Marine certificates Information is available on www.beijerelectronics.com
4.1. Compass Safe Distance
Variant Condition Standard Compass Steering Compass
X2 pro 7 Non-energized 95 cm 85 cm
Non-energized after magnetization 95 cm 85 cm
Energized and operating 95 cm 85 cm
Technical Data
Beijer Electronics, MAEN265 15 2023-09

5. Chemical Resistance
5.1. Metal Casing
The frame and casing material is powder-coated aluminum. This powder paint withstands exposure to
the following chemicals without visible change:
Acetic acid 10% Phosphoric acid 4%
Citric acid 10% Phosphoric acid 10%
Diesel Sea water
Distilled water Sodium chloride 2%
Edible oil Sodium chloride 20%
Fuel oil Sulphuric acid 20%
Hydrogen peroxide 3% Tap water
The powder paint shows limited resistance to the following chemicals at room temperature:
Butanol Nitric acid 3%
Hydrochloric acid 5% Nitric acid 10%
Isopropyl alcohol Phosphoric acid 43%
Sodiumhypochlorite 10% Turpentine
NOTE
If exposure to any of the above chemicals is demanded, it is recommended to first
test the chemical in a hidden spot of the metal casing.
The powder paint shows little or no resistance to the following chemicals at room temperature:
Acetic acid, conc. Methyl-ethyl ketone Toluene
Acetone Nitric acid 30% Trichlorethylene
Ammonia 5% Phenol Xylene
Ammonia, conc. Sodium hydroxide 5% 97 octane unleaded petrol
Ethyl acetate Sodium hydroxide 30% 98 octane leaded petrol
5.2. Touch Screen and Overlay Material
5.2.1. Protective Film
The Autoflex protective film covers the overlay surrounding the screen.
Solvent Resistance
The protective film withstands exposure of more than 24 hours duration under DIN 42115 Part 2 to
the following chemicals without visible change:
Acetonitrile Diesel Petroleum spirit1
Chemical Resistance
2023-09 16 Beijer Electronics, MAEN265

Ajax / Vim in solution Downy / Lenor1Phosphoric acid (<30%)
Alkalicarbonate solution1Ethanol Potassium ferricyanide
Ammonia (<40%)1Glycerine Potassium hydroxide (<30%)
Acetic acid (<50%) Glycol Pure Turpentine
Ariel powder in solution1Gumption1SBP 60/951
Bleach1Hydrochloric acid (<36%) Sulfuric acid (<10%)
Castor oil Linseed oil Tomato ketchup
Caustic soda (<40%)1Methanol Trichloroacetic acid (<50%)
Cutting oil Nitric acid (<10%) White Spirit
Cyclohexanol Paraffin oil Windex1
Diacetone alcohol Persil powder in solution1Wisk
1Extremely faint glossing of the texture was noted.
The Autoflex protective film withstands DIN 42 115 Part 2 exposure of up to 1 hour duration to glacial
acetic acid without visible change.
The Autoflex protective film is not resistant to high pressure steam at over 100°C or the following
chemicals:
Concentrated mineral acids Benzyl alcohol
Concentrated caustic solution Methylene chloride
5.2.2. Touch Screen Surface
The touch screen surface on the HMI panel withstands exposure to the following solvents without
visible change:
Solvents Time
Acetone 10 minutes
Isopropanol 10 minutes
Toluene 5 hours
The touch screen surface on the HMI panel is made of polyester with a hard coat to resist scratches
and withstand exposure to many solvents without visible change.
5.2.3. Touch Screen Protector
For harsh environments and exposure to outdoor conditions, it is recommended to use a protective
film to guard the touch screen from damage. This optional part can be ordered from Beijer
Electronics.
Chemical Resistance
Beijer Electronics, MAEN265 17 2023-09

6. HMI Panel Drawings
6.1. Connectors
123 4
Pos Connector Description
1 Power supply +24 V DC (18–32 V DC)
2 LAN A 1×10/100 Base-T (shielded RJ45)
3 LAN B 1×10/100 Base-T (shielded RJ45)
4 COM Serial communication port
6.1.1. Communication Ports
Pin D-sub-9, female
COM 1 COM 2 COM 3 CAN 1
1 RS-422 Tx+
RS-485 Tx+/Rx+
CAN 1-H
2 RS-232 RxD
3 RS-232 TxD
4 RS-422 Rx+ RS-485 Tx+/Rx+
5 GND GND GND GND
6 RS-422 Tx-
RS-485 Tx-/Rx-
CAN 1-L
7 RS-232 RTS
8 RS-232 CTS
9 RS-422 RX- RS-485 Tx-/Rx-
The connector supports up to three independent communication channels and can be configured for
RS-232 and RS-422 or 2x RS-485 or 1x CAN.
NOTE
In order to utilize two communication ports, the Y-split cable CAB109 can be used.
To use RS-232 and RS-422, use CAB 109.
HMI Panel Drawings
2023-09 18 Beijer Electronics, MAEN265

6.2. HMI Panel Outline
204
143
43
7
1879
9
126
9
9
HMI Panel Drawings
Beijer Electronics, MAEN265 19 2023-09
Table of contents
Other Beijer Electronics Touch Terminal manuals

Beijer Electronics
Beijer Electronics QTERM-G70 User manual

Beijer Electronics
Beijer Electronics X2 control 10 - B2 User manual

Beijer Electronics
Beijer Electronics X2 base 15 v2 HP User manual

Beijer Electronics
Beijer Electronics X2 extreme 7 12V CO User manual

Beijer Electronics
Beijer Electronics QTERM-A12 User manual

Beijer Electronics
Beijer Electronics X2 control User manual

Beijer Electronics
Beijer Electronics X2 base 10 v2 User manual

Beijer Electronics
Beijer Electronics CIMREX 5 User manual

Beijer Electronics
Beijer Electronics X2 pro 10 - B2 User manual

Beijer Electronics
Beijer Electronics X2 control User manual