Accessories (AF series accessories may be employed)
IND-AF2 Damper position indicator
K4-1 US Universal clamp for up to 1.05” dia. jackshafts
K4-H Universal clamp for hexshafts C\,” to B\,”
KH-AF Crankarm for up to C\v” round shaft (Series 2)
KH-AF-1 Crankarm for up to 1.05” jackshaft (Series 2)
KH-AFV V-bolt kit for KH-AF and KH-AF-1
Tool-01 10 mm wrench
SGA24 Min. and/or max. positioner in NEMA 4 housing
SGF24 Min. and/or max. positioner for flush panel mounting
ZG-R01 500 Ωresistor for 0 to 20 mA control signal
ZDB-AF2 Angle of rotation limiter
ZG-100 Universal mounting bracket
ZG-101 Universal mounting bracket
ZG-103 Universal mounting bracket
ZG-104 Universal mounting bracket
ZG-106 Mounting bracket for Honeywell® Mod IV replacement
or new crankarm type installations
ZG-107
Mounting bracket for Honeywell® Mod III or Johnson®
Series 100 replacement or new crankarm type installations
ZG-108 Mounting bracket for Barber Colman® MA 3../4..,
Honeywell® Mod III or IV or Johnson® Series 100
replacement or new crankarm type installations
ZG-AF Crankarm adaptor kit for AF/NF
ZG-AF108 Crankarm adaptor kit for AF/NF
Wiring Diagrams
FSAF24-SR (-S) US Typical Specification
Proportional smoke, and combination fire and smoke dampers, shall be
controlled by Belimo FSAF24-SR actuators. The control signal shall provide
proportional damper control in response to a 2 to 10 VDC or, with the
addition of a 500 Ωresistor, a 4 to 20 mA control input from an electronic
controller or positioner. The actuators must be designed so that they may be
used for either clockwise or counter-clockwise failsafe operation. Actuator
shall open damper in <75 seconds per UL555S and shall spring closed in
under 20 seconds. Actuators shall be UL listed, have a 5-year warranty, and
be manufactured under ISO 9001 International Quality Control Standards.
Actuators shall be as manufactured by Belimo. Actuators with auxiliary
switches must be constructed to meet the requirement for double insulation
so an electrical ground connection is not required to meet agency listings.
Safety Note
Screw a conduit fitting into the actuator’s metal bushing. Jacket the
actuator’s input and output wiring with suitable flexible conduit. Properly
terminate the conduit in a suitable junction box.
ZS-100 Weather shield (metal)
ZS-150 Weather shield (polycarbonate)
ZS-260 Explosion-proof housing
ZS-300 NEMA 4X housing
For an overview of how to apply the accessories, see Belimo Mechanical Accessories
and refer to the Belimo Mounting Methods Guide.
NOTE: When using FSAF24-SR (-S) US actuators, only use
accessories listed on this page.
(+)
(–)
(+)
(–)
(+)
(–)
W188
W572
S1
S2
S3
S4
S5
S6
NC
NO
NC
NO
124 VAC Transformer
Line
Volts
1 Blk Com
2 Red + Hot
3 Wht Y1Input, 2 to 10V
5 Gn U Output 2 to 10V
Control Signal
2 to 10 VDC
3
2
FSAF24-SR US
124 VAC Transformer
Line
Volts
4 to 20 mA
Control Signal
2 to 10 VDC
Feedback Signal
3
2
1 Blk Com
2 Red + Hot
3 Wht Y1Input, 2 to 10V
5 Gn U Output 2 to 10V
FSAF24-SR US
5
4
500 Ω
Ω
Replacement Applications The number one “equal or better” requirement for use as a replacement for obsolete defective motors is the UL555S listing of the Belimo actuator with
the damper for the application. The local authority having jurisdiction sets the requirements since UL has stated that they do not regulate replacements.
1
INSTALLATION NOTES
Actuators may also be powered by 24 VDC.
The ZG-R01 500 Ωresistor converts the 4 to 20 mA control
signal to 2 to 10 VDC.
Only connect common to neg. (—) leg of control circuits.
For end position indication, interlock control, fan startup, etc.,
FSAF24-SR-S US incorporates two built-in auxiliary switches: 2
x SPDT, 7A resistive, 2.5A inductive 120/250 VAC, UL listed, one
switch is fixed at 10°, one is adjustable 30° to 90°.
APPLICATION NOTES
Meets UL requirements without the need of an electrical ground
connection. Actuator may also be powered by 24 VDC.
Double insulated.
3
2
4
5
CAUTION
Provide overload protection
and disconnect as required.
Actuators may be connected
in parallel. Power consumption
must be observed.
6
(+)
(–)
(+)
(–)
(+)
(–)
W188
W572
S1
S2
S3
S4
S5
S6
NC
NO
NC
NO
6
4
FSAF24-SR-S US
10°
30° to 90°
WARNING:Live Electrical Components!
During installation, testing, servicing and troubleshooting of
this product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow
all electrical safety precautions when exposed to live electrical
components could result in death or serious injury.