Technical data sheet SRF24A-SR
Modulating rotary actuator with
emergency control function for ball
valves
• Nominaltorque20Nm
• NominalvoltageAC/DC24V
• ControlModulatingDC(0)2...10V
• PositionfeedbackDC2...10V
• Deenergisedclosed(NC)
Technical data
Electrical data Nominal voltage AC/DC 24 V
Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V
Power consumption in operation 5.5 W
Power consumption in rest position 3 W
Power consumption for wire sizing 8.5 VA
Connection supply / control Cable 1 m, 4 x 0.75 mm²
Parallel operation Yes (note the performance data)
Functional data Torque motor Min. 20 Nm
Torque spring return Min. 20 Nm
Positioning signal Y DC 0...10 V
Positioning signal Y note Input impedance 100 kΩ
Operating range Y DC 2...10 V
Position feedback U DC 2...10 V
Position feedback U note Max. 0.5 mA
Position accuracy ±5%
Direction of rotation motor Y=0 (0V = A-AB = 0%)
Direction of rotation spring-return Deenergised NC, valve closed (A - AB = 0%)
Manual override By means of hand crank and locking switch
Angle of rotation 90°
Running time motor 90 s / 90°
Running time emergency setting position <20 s / 90°
Sound power level motor max. 45 dB(A)
Position indication Mechanical
Service life Min. 60,000 emergency positions
Safety Protection class IEC/EN III Safety extra-low voltage
Protection class UL UL Class 2 Supply
Degree of protection IEC/EN IP54
Degree of protection NEMA/UL NEMA 2, UL Enclosure Type 2
EMC CE according to 2004/108/EC
Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14
Certification UL cULus according to UL 60730-1A, UL 60730-2-
14 and CAN/CSA E60730-1:02
Mode of operation Type 1.AA
Rated impulse voltage supply / control 0.8 kV
Control pollution degree 3
Ambient temperature -30...50°C
Non-operating temperature -40...80°C
Ambient humidity 95% r.h., non-condensing
Maintenance Maintenance-free
Weight Weight approx. 2.2 kg
Safety notes
!
• This device has been designed for use in stationary heating, ventilation and air
conditioning systems and is not allowed to be used outside the specified field of
application, especially in aircraft or in any other airborne means of transport.
www.belimo.eu SRF24A-SR • en-gb • 2014-10-15 • subject to changes 1