7
TBP101012 / 09.2010
A-ISOMETER® IR420-D4
Technische Daten IR420-D4..
Isolationskoordination nach IEC 60664-1/IEC 60664-3
Bemessungsspannung ........................................................................................................... 250 V
Bemessungs-Stoßspannung / Verschmutzungsgrad .................................................... 2,5 kV / III
Sichere Trennung (verstärkte Isolierung) zwischen:
............................................................... (A1, A2) - (L1, L2, E, KE, T/R) - (11-12-14) - (21-22-24)
Spannungsprüfung nach IEC 61010-1 ................................................................................. 2,21 kV
Versorgungsspannung
IR420-D4-1:
Versorgungsspannung Us.................................................................... AC 16...72 V / DC 9,6...94 V
Frequenzbereich Us................................................................................................ 42...460 Hz / DC
IR420-D4-2:
Versorgungsspannung Us..................................................................................... AC/DC 70...300 V
Frequenzbereich Us.................................................................................................. 42...460 Hz, DC
Eigenverbrauch ..................................................................................................................... ≤3 VA
Überwachtes IT-System
Netznennspannung Un................................................................................................ AC 0... 300 V
Nennfrequenz fn............................................................................................................. 42...460 Hz
Ansprechwerte
Ansprechwert Ran1 (ALARM 1) ...................................................................................... 1...200 k
Ω
Ansprechwert Ran2 (ALARM 2) ...................................................................................... 1...200 k
Ω
Preset-Funktion:
Un≤72 V: Ran1 (ALARM 1)/ Ran2 (ALARM 2) ........................................................ 20 k
Ω
/ 10 k
Ω
Un>72 V: Ran1 (ALARM 1)/ Ran2 (ALARM 2) ........................................................ 46 k
Ω
/ 23 k
Ω
Ansprechabweichung (1...5 k
Ω
) / (5...200 k
Ω
) ............................................. ±0,5 k
Ω /
±15 %
Hysterese (1...5 k
Ω
) / (5...200 k
Ω
) .................................................................. +1 k
Ω /
+25 %
Zeitverhalten
Ansprechzeit tan bei RF= 0,5 x Ran und Ce= 1 µF................................................................. ≤1 s
Anlaufverzögerung t ............................................................................................................. 0...10 s
Ansprechverzögerung ton ..................................................................................................... 0...99 s
Messkreis
Messspannung Um.................................................................................................................. ±12 V
Messstrom Im(bei RF= 0
Ω
).......................................................................................... ≤200 μA
Innenwiderstand DC Ri....................................................................................................... ≥62 k
Ω
Impedanz Zibei 50 Hz........................................................................................................ ≥60 k
Ω
Zulässige Fremdgleichspannung Ufg ............................................................................. ≤DC 300 V
Zulässige Netzableitkapazität Ce.......................................................................................... ≤20 µF
Anzeigen, Speicher
Anzeige ......................................................................... LC-Display, multifunktional, unbeleuchtet
Anzeigebereich Messwert.......................................................................................... 1 k
Ω
...1 M
Ω
Betriebsmessabweichung (1...5 k
Ω
) .............................................................................. ±0,5 k
Ω
Betriebsmessabweichung (5 k
Ω
...1 M
Ω
) .......................................................................... ±15 %
Passwort ......................................................................................................................... off / 0...999
Fehlerspeicher (Alarmrelais) ................................................................................................ on / off
Eingänge
Leitungslänge externe Test- / Reset-Taste ......................................................................... ≤ 10 m
Schaltglieder
Anzahl .............................................................................................................. 2 (Wechsler K1, K2)
Arbeitsweise ........................................................................................... Ruhestrom / Arbeitsstrom
Elektrische Lebensdauer bei Bemessungsbedingungen ................................... 10000 Schaltspiele
Kontaktdaten nach IEC 60947-5-1:
Bemessungsbetriebsspannung AC ....................................................................... 230 V....... 230 V
Gebrauchskategorie AC ........................................................................................ AC 13....... AC 14
Bemessungsbetriebsstrom AC ................................................................................. 5 A............ 3 A
Bemessungsbetriebsspannung DC ................................................... 220 V....... 110 V.......... 24 V
Gebrauchskategorie DC ..................................................................... DC 12....... DC 12....... DC 12
Bemessungsbetriebsstrom DC ........................................................... 0,1 A ........ 0,2 A............ 1 A
Mindeststrom ..............................................................................................1 mA bei AC/DC ≥10 V
Technical data IR420-D4..
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Rated insulation voltage........................................................................................................... 250 V
Rated impulse voltage / Pollution degree........................................................................ 2.5 kV / III
Protective separation (reinforced insulation) between:
..............................................................(A1, A2) - (L1, L2, E, KE, T/R) - (11, 12, 14) - (21, 22, 24)
Voltage test acc. IEC 61010-1 .............................................................................................. 2.21 kV
Supply voltage
IR420-D4-1:
Supply voltage Us................................................................................ AC 16...72 V / DC 9.6...94 V
Frequency range Us................................................................................................ 42...460 Hz / DC
IR420-D4-2:
Supply voltage Us................................................................................................. AC/DC 70...300 V
Frequency range Us................................................................................................. 42...460 Hz, DC
Power consumption.............................................................................................................. ≤3 VA
IT System being monitored
Nominal system voltage Un......................................................................................... AC 0... 300 V
Nominal frequency fn..................................................................................................... 42...460 Hz
Response values
Response value Ran1 (ALARM 1).............................................................................. 1 k
Ω
...200 k
Ω
Response value Ran1 (ALARM 2).............................................................................. 1 k
Ω
...200 k
Ω
Preset function:
Un≤72 V: Ran1 (ALARM 1)/ Ran2 (ALARM 2) ........................................................ 20 k
Ω
/ 10 k
Ω
Un>72 V: Ran1 (ALARM 1)/ Ran2 (ALARM 2) ........................................................ 46 k
Ω
/ 23 k
Ω
Operating error (1...5 k
Ω
) / (5...200 k
Ω
) ........................................... ±0.5 k
Ω /
±15 %
Hysteresis (1...5 k
Ω
) / (5...200 k
Ω
) ....................................................................+1 k
Ω /
+25 %
Time response
Response time tan at RF= 0,5 x Ran and Ce= 1 µF ................................................................ ≤1 s
Starting delay t ...................................................................................................................... 0...10 s
Response delay ton ................................................................................................................ 0...99 s
Measuring circuit
Measuring voltage Um............................................................................................................. ±12 V
Measuring current Im(RF= 0
Ω
) .................................................................................. ≤200 μA
Internal d.c. resistance Ri.................................................................................................... ≥62 k
Ω
Internal impedance Zi(50 Hz) ........................................................................................... ≥60 k
Ω
Admissible extraneous d.c. voltage Ufg ......................................................................... ≤DC 300 V
System leakage capacitance Ce............................................................................................ ≤20 µF
Displays, memory
Display...................................................................... LC display, multi-functional, non-illuminated
Display range, measuring value ................................................................................ 1 k
Ω
...1 M
Ω
Operating error (1...5 k
Ω
) ................................................................................................ ±0.5 k
Ω
Percentage operating error (5 k
Ω
...1 M
Ω
) ........................................................................ ±15 %
Password ........................................................................................................................ off / 0...999
Fault memory (alarm relay) ................................................................................................. on / off
Inputs
Cable length external test / reset button.............................................................................. ≤10 m
Switching elements
Number of....................................................................................... 2 (changeover contacts K1, K2)
Operating principle....................................................................... (N/O operation) (N/C operation)
Electrical endurance ............................................................................ 10000 switching operations
Contact data according IEC 60947-5-1
Rated operational voltage AC ............................................................................... 230 V ....... 230 V
Utilization category AC ........................................................................................ AC 13 ....... AC 14
Rated operational current AC .................................................................................. 5 A ........... 3 A
Rated operational voltage DC ............................................................ 220 V....... 110 V ......... 24 V
Utilization category DC ...................................................................... DC 12........DC 12 ....... DC 12
Rated operational current DC ............................................................ 0.1 A........ 0.2 A ........... 1 A
Minimum current ..........................................................................................1 mA at AC/DC ≥10 V