
 
 
 
 
 
3 INSTALLATION 
3.1 Installation regulations 
Installation must be carried out by qualified persons, in compliance 
with the following reference standards: 
- UNI 7129-7131 
- CEI 64-8. 
- NZ building and plumbing codes with reference to NZ standards 
POSITION 
EXCLUSIVE - a wall-hung boiler for heating and for the production of DHW. 
with f lue gas discharge pipe and pick-up of combustion air from 
outside. It does not require an air intake point in the installation area. 
It must be installed using concentric pipes, or other types of 
discharge designed for condensing boilers with an airtight chamber. 
MINIMUM CLEARANCES 
( Ref fig. 6-6a Page 44) 
To ensure access to the boiler for normal maintenance operations, respect 
the minimum installation clearances envisaged. 
 
For correct appliance positioning, bear in mind that: 
- It must not be placed above a cooker or other cooking device 
- Heat-sensitive walls (e.g. wooden walls) must be protected by use of a 
cement fiber board 
It is ESSENTIAL to provide the necessary space for the introduction of an 
analyser for the combustion analysis check. In fig. 6a P44 a 
sample drawing where distances between boiler and cabinet/niche 
were obtained using a 300mm length analyser probe. 
3.2 Removing the casing 
To access the components inside, remove the casing as indicated below: 
- 
Locate and unscrew the 2 screws (
A 
- f
ig. 
13) that f
ix 
the front 
casing.
 
- 
By leveraging the fixing clips (
C 
- fig. 13), unhook the lower part of 
the
 
casing now 
lift the casing upwards to release it from the top tabs 
 
(
B 
- fig. 13 P44), then 
remove the face panel. 
 
The noise absorbing panels inside the front and side walls ensure 
the airtight seal for the air supply duct in the installation 
environment. It is therefore ESSENTIAL after dismantling 
operations to correctly reposition the components so as not to 
compromise the boiler’s operation. 
 
WARNING If damaged the front panel must be replaced.
Under the safety valve, install a tundish with the corresponding 
discharge in the event of leaks due to the overpressure of the heating 
system. The domestic cold input must not exceed 6 Bar 
 Prior to ignition, make sure that the boiler is designed to operate 
with the gas available; this can be checked by the wording on the 
packaging and by the adhesive label indicating the gas type. 
 It is important to highlight that in some cases the flue is under 
pressure, so the joints of the various elements must be airtight. 
 
 
3.3 Positioning and hydraulic 
connections 
 
The boiler comes as standard with a boiler hanger jig. The position and 
dimensions of hydraulic fittings are shown in Fig 8/9 on page 44 
, proceed as follows: 
- Fasten the boiler Bkt (F) to the wall and use a spirit level to make sure it 
is perfectly horizontal 
- Use the jig to identify the required pipe centers 
- 
The pipe template and hanger can then be removed 
form the jig . 
 
Install pipework 
Using the valve kit supplied . include a magnetic filter (not supplied) in the 
return line . A magnetic filter is a requirement of warranty 
Note The 1st 1m (minimum) of pipe used for the flow and return line 
should be run in copper. 
The condensate and relief drain outlet must be run avoiding 
double trapping 
The system attached must include a low point drain for 
flushing the system 
 
3.4 Gas connection 
Connection of the gas supply must be carried out in 
compliance with current NZ installation standards. By a 
certifying Gas fitter 
Ensure the supply pipework supports the delivery of the relevant 
Gas being used and is correctly sized. 
If the appliance is to use LPG attach the Gas type label supplied 
 
 
 
3.5 Electrical connections
 (
Figure 10/11 Page 45)
 
 
Low voltage connections 
Carry out the low voltage connections as follows: 
- Use the external cable box supplied as standard 
- Unscrew the fixing screws of the cover (V)
- Carry out the connections as shown in fig. 11 
 It is recommended to use wires with section not exceeding 
0,5mm2.In case of TA or TBT connection, remove the respective 
shunts 
(fig. 12). 
- Close the box with the screws that were previously removed 
- Press the two tabs on the sides of the box to place it correctly in its 
housing in the boiler sliding upward within the guide rails and tighten the 
safety screw (V1)
 If the low voltage electrical connection box is not connected the boiler 
will not ignite. 
 
High voltage connections 
The connection to the mains supply must be made via a standard power 
point. The appliance works with alternating current at 230 Volt/50 Hz, and 
is in compliance with Standard EN 60335-1. (NZ Compliant) 
It is obligatory to make the connection with a safe ground/earth, 
 
 The manufacturer will not be liable for any damage resulting incorrect or 
absent earth connection.
.
3.6 Flue gas exhaust and combustion air suction 
To evacuate combustion products, refer to UNI 7129-7131. Always comply 
with local standards of the Fire Department, and with possible local 
municipal dispositions. 
 
The release of combustion products is assured by a centrifugal fan. The 
control board constantly checks that it is operating correctly. It is essential 
for evacuating fumes and induction of boiler combustion air that only 
original flue pipes are used and that the connection is made correctly as 
shown in the instructions provided with the flue gas accessories. 
 
A single flue can be connected to several appliances provided that every 
appliance is the condensing type. 
 
The boiler is a C-type appliance (with airtight chamber), and must therefore 
have a safe connection to the flue gas discharge pipe and to the 
combustion air suction pipe; these carry their contents too and from 
outside, and are essential for the operation of the appliance. 
Both concentric and twin terminals are available. 
 
3.7 Filling the heating system (fig. 16) 
Note: 
Even though the boiler is fitted with a semi-automatic filling 
device, the first filling operation must be carried out by using the filler tap 
(
B
) with the boiler in the off position. 
Filling
. must be carried out when the system is cold, as follows.
- Open the caps of the lower (A) automatic air vent valve by two or 
Three turns; to allow a continuous venting of the air, leave valve 
A open. 
- Open the filling tap (B) until the pressure indicated by the water pressure 
gauge is between 1 and 1.5 bar 
- 
Re-close the filling tap.
 
 On going venting of the boiler takes place automatically via the two 
automatic vent valves positioned on the circulator & top point 
 
 
3.8 Flush and Protect 
In the case of a new installation or replacement of the boiler, it is necessary 
to pre flush the heating system 
To ensure the device operates well and is protected from scale and 
corrosion add inhibitors, antifreeze etc as required and check the 
parameters in the table are within the values indicated. 
 
Failures as result of not flushing the system will not be covered.