9
ENGLISH
To restore operation (deactivate alarms):
Faults A 01-02-03
Position the function selector to   (OFF), wait 5-6 seconds then set it to 
the required position   (summer mode) or   (winter mode).
If the reset attempts do not reactivate the boiler, contact the Technical As-
sistance Centre.
Fault A 04
In addition to the fault code, the digital display shows the symbol  .
Check the pressure value indicated by the water gauge: if it is less than 
0.3 bar, position the function selector to   (OFF) and adjust the fi lling tap 
until the pressure reaches a value between 1 and 1.5 bar. Then position 
the mode selector to the desired position  (summer) or  (winter). 
The boiler will perform one purge cycle lasting approximately 2 minutes. If 
pressure drops are frequent, request the intervention of the Technical As-
sistance Service.
Fault A 06
The boiler operates normally  but cannot reliably  maintain a  constant do-
mestic hot water temperature, which remains set at around 50°C. Contact 
the Technical Assistance Centre.
Fault A 07 - A 08
Contact the Technical Assistance Centre.
Fault A 09 with fi xed red LED lit
Position the function selector to   (OFF), wait 5-6 seconds then set it to 
the required position (summer mode) or (winter mode). If the reset attempts 
do not reactivate the boiler, request the intervention of the Technical As-
sistance Service.
Fault A 09 with fl ashing red and green LEDs
The boiler is equipped with an auto-diagnostic system which, based on the 
total number of hours in certain operating conditions, can signal the need 
to clean the primary exchanger (alarm code 09 with fl ashing red and green 
LEDs and fl ue gas meter >2,500). Once the cleaning operation has been 
completed, using the special kit supplied as an accessory, the total hour 
meter will need to be reset to zero as follows: 
-  switch off the power supply
-  remove the housing  
-  loosen the fi xing screw then turn the instrument panel
-  loosen the fi xing screws on the cover (F) to access the terminal board (fi g. 16)  
-  while the boiler is powered up, using a small screwdriver included, press 
the CO button (fi g. 26) for at least 4 seconds, to check the meter has 
been reset, power down then power up the boiler; the meter reading is 
shown on the monitor after the “-C-” sign.
  Live electrical parts (230 V AC).
Note: the  meter resetting procedure should  be carried out  after each in-
depth  cleaning  of  the  primary  exchanger  or  if  this  latter  is  replaced.  To 
check the status of the total hour meter, multiply the reading by 100 (e.g. 
reading of 18 = 1800 total hours; reading of 1 = 100 total hours).
The boiler continues to operate normally even when the alarm is activated.
Fault A 77
This is an automatic-reset fault, if the boiler does not restart, contact the 
Technical Assistance Centre.
Fixed yellow LED 
Pre-heating function activated 
Flashing yellow LED
Combustion analysis in progress. 
4.4 Alarm records
The “ALARM RECORDS” function starts automatically once the display has 
been on for 2 hours, or immediately by setting the P1 parameter to 1. 
The records include all the latest alarms, up to a maximum of 5 alarms, and 
they are displayed in sequence by pushing and releasing the P1 button on 
the display board.  If the records are empty (P0=0) or if tracking the same is 
disabled (P1=0), the display function is not available. Alarms are displayed 
in reverse order compared to the order in which they occurred:  this means 
that  the last  alarm generated  is  the fi rst to  be displayed.   To  delete the 
alarms records, simply set parameter P0 to 0. 
NOTE: To get to the P1 button the cover on the control panel must be remo-
ved and the display board must be identifi ed (fi g. 37a). 
PROGRAMMING PARAMETERS 
Functioning of the display can be personalised by programming three pa-
rameters: 
Param. Default Description
P0 0 Deletion of alarms records 
(0 = records empty / 1 = records not empty) 
P1 0 Immediate activation of alarm record management 
(0 = delayed records management activated / 1 = 
immediate records management activated
P2 0 Do not change 
envisaged delivery T. - Tshift
KT=  20- min. envisaged external T.
When button P1 on the display (fi g. 37a) is held down for at least 10 sec, 
the programming procedure is activated.  The three parameters, with their 
respective values, are shown in rotation on the display (fi g. 37b).  To edit a 
parameter value, simply push the P1 button again when the required para-
meter is displayed, and then hold it down until the value switches from 0 to 
1 or vice-versa (approx. 2 sec). 
The programming procedure is closed automatically after 5 minutes, or if 
there is an electrical power failure
4.5 Boiler confi guration 
There is a series of jumpers (JPX) available on the electronic board which 
enable the boiler to be confi gured.
To access the board, proceed as follows:
-  turn off the main switch on the system
-  loosen the fi xing screws on the housing, move the base of the housing 
forwards and then upwards to unhook it from the chassis
-  undo the fi xing screws (E) from the instrument panel (fi g. 14) 
-  loosen the screws (F - fi g. 16) to remove the cover of the terminal board 
(230V)
JUMPER JP7 - fi g. 38: 
preselection of the most suitable heating temperature adjustment fi eld ac-
cording to the installation type. 
Jumper not inserted - standard installation
Standard installation 40-80°C
Jumper inserted - fl oor installation
Floor installation 20-45°C.
In the manufacturing phase, the boiler is confi gured for standard installations.
JP1 
Calibration (Range Rated)
JP2  Reset heating timer
JP3  Calibration (see paragraph on “Adjustments”)
JP4  Absolute domestic hot water thermostat selector
JP5  Do not use  
JP6  Enable  night-time  compensation  function  and  continuous  pump  (only 
with external sensor connected)
JP7  Enable  management  of  low  temperature/standard  installations  (see 
above) 
JP8  Do not use 
4.6 Setting the thermoregulation (graphs 1-2-3)
The  thermoregulation  only  operates  with  the  external  sensor  connected; 
once installed, connect the external sensor (accessory available on request) 
to the special terminals provided on the boiler terminal board (fi g. 5).
This enables the THERMOREGULATION function.
Selecting the compensation curve
The compensation curve for heating maintains a theoretical temperature of 
20°C indoors, when the external temperature is between +20°C and -20°C. 
The  choice of  the  curve depends  on  the minimum  external  temperature 
envisaged (and therefore on the geographical location), and on the delivery 
temperature envisaged (and therefore on the type of system). It is carefully 
calculated by the installer on the basis of the following formula:
Tshift =  30°C standard installations 
  25°C fl oor installations 
If the calculation produces an intermediate value between two curves, you 
are advised to choose the compensation curve nearest the value obtained.
Example: if the value obtained from the calculation is 1,3 this is between 
curve 1 and curve 1,5. Choose the nearest curve, i.e. 1,5.
Select the KT using trimmer P3 on the board (see multiwire wiring diagram).
To access P3:
-  remove the housing, 
-  loosen the fi xing screw on the instrument panel
-  turn the instrument panel towards you
-  loosen the fi xing screws on the terminal board cover
-  unhook the board casing
   Live electrical parts (230 V AC). 
The KT values which can be set are as follows:
standard installation: 1,0-1,5-2,0-2,5-3,0
fl oor installation 0,2-0,4-0,6-0,8 
and these are displayed for approximately 3 seconds after rotation of the 
trimmer P3.
TYPE OF HEAT REQUEST
Boiler connected to room thermostat (JUMPER 6 not inserted)
The heat request is made by the closure of the room thermostat contact, 
while the opening of the contact produces a switch-off. The delivery tem-
perature is automatically calculated  by the boiler, although  the user  may 
modify the boiler settings. Using the interface to modify the HEATING, you