Bin Master CNCR-220 User manual

CNCR-210/220 • Two-wire 4
-
20 1
Operating Instructions
Radar sensor for continuous level measurement
CNCR-210
Two-wire 4
-
20 mA
CNCR-220
Two-wire 4
-
20 mA/HART
Document ID: 925-0395 Rev C

CNCR-210/220 • Two-wire 4
-
20 2
Contents
1 About this document ............................................................................................................. 3
2 For your safety ....................................................................................................................... 3
2.1 Authorized personnel ....................................................................................................... 3
2.2 Appropriate use................................................................................................................ 3
2.3 Warning about incorrect use ............................................................................................ 4
3 Product description ............................................................................................................... 4
3.1Conguration.................................................................................................................... 4
3.2 Principle of operation ....................................................................................................... 5
3.3 Adjustment ....................................................................................................................... 5
4 Mounting................................................................................................................................. 6
4.1 General instructions ......................................................................................................... 6
4.2 Mounting versions............................................................................................................ 6
5 Connecting to power supply................................................................................................. 9
5.1 Preparing the connection ................................................................................................. 9
5.2 Connecting..................................................................................................................... 10
5.3 Wiring plan ..................................................................................................................... 11
6 Setup with smartphone/tablet (Bluetooth) ........................................................................ 11
6.1 Preparations................................................................................................................... 11
6.2 Connecting..................................................................................................................... 12
6.3 Parameter adjustment.................................................................................................... 13
7 Menu overview ..................................................................................................................... 14
8 Diagnostics and servicing .................................................................................................. 15
8.1 Maintenance .................................................................................................................. 15
8.2 Status messages ........................................................................................................... 15
9 Removal ................................................................................................................................ 17
10 Certicates and approvals .................................................................................................. 17
10.1 Radio licenses.............................................................................................................. 17
11 Supplement .......................................................................................................................... 18
11.1 Technical data .............................................................................................................. 18
11.2 Dimensions................................................................................................................... 20

CNCR-210/220 • Two-wire 4
-
20 3
Information, note, tip: This symbol indicates helpful additional
information and tips.
Note: This symbol indicates notes to prevent failures, malfunctions,
damage to devices or facility.
Caution: Non-observance may result in personal injury.
Warning: Non-observance may result in serious or fatal personal injury.
Danger: Non-observance of the information marked with this symbol
results in serious or fatal personal injury.
Ex applications
This symbol indicates special instructions for Ex applications.
List
The dot set in front indicates a list with no implied sequence.
Sequence of actions
Numbers set in front indicate successive steps in a procedure.
Battery disposal
This symbol indicates special information about the disposal of
batteries and accumulators.
1 About this document
2 For your safety
2.1 Authorized personnel
Alloperationsdescribedinthisdocumentationmustbecarriedoutonlybytrained,qualied
personnel authorized by the plant operator. Required personal protective equipment must always
be worn when working on or with the device.
2.2 Appropriate use
CNCR-210/220 is a sensor for continuous level measurement. Operational reliability is ensured
onlyiftheinstrumentisproperlyusedaccordingtothespecicationsintheoperatinginstructions.

CNCR-210/220 • Two-wire 4
-
20 4
Safety instructions for Ex areas
TakenoteoftheExspecicsafetyinstructionsforExapplications.Theseinstructions
are attached as documents to each instrument with Ex approval and are part of the
operating instructions.
2.3 Warning about incorrect use
Inappropriateorincorrectuseofthisproductcanresultinapplication-specichazards,e.g.vessel
overllbyincorrectmountingoradjustment.Damagetopropertyandpersonsorenvironmental
contamination can result.
3 Product Description
3.1 Conguration
Fig. 1: Components of CNCR-210/220
1 Radar antenna
2 Processtting
3 Process seal
4 Electronics housing
5 Ventilation/pressure compensation

CNCR-210/220 • Two-wire 4
-
20 5
3.3 Adjustment
Devices with integrated Bluetooth module can be adjusted wirelessly via software adjustment tools:
• Smartphone/tablet (iOS or Android operating system)
• PC/notebook with Bluetooth USB adapter (Windows operating system)
Fig. 2: Wireless connection to standard operating devices with integrated Bluetooth LE
1 Sensor
2 Smartphone/Tablet
3 PC/Notebook
3.2 Principle of operation
CNCR-210/220 is a radar sensor for continuous level measurement. It is suitable for liquids and
solids in practically all industries.
The instrument emits a continuous, frequency-modulated radar signal from its antenna. The emit-
tedsignalisreectedbythematerialandreceivedbytheantennaasanechowithamodied
frequency. The frequency change is proportional to the distance to the material.

CNCR-210/220 • Two-wire 4
-
20 6
4.2 Mounting
The radar emits pulses of electromagmetic waves which are polarized. By adjusting the rotation of
the instrument the polarization can be changed to reduce false echoes.
The narrow portion of the radar signal is in the middle of the conduit entry on the instrument. This
should be pointed towards the center of the vessel or any obstacle that may cause any unwanted
reectionstominimizefalseechos,forexample,thesidewallorvesselstructure.
4 Mounting
4.1 General instructions
The instrument is suitable for standard and extended ambient conditions according to DIN/EN/IEC/
ANSI/ISA/UL/CSA 61010-1. It can be used indoors as well as outdoors.
Protect your instrument against moisture ingress through the following measures:
• Use a suitable connection cable
•Tightenthecableglandorplugconnectorrmly
• Face the cable connection or conduit entry downward, never upward
This applies mainly to outdoor installations, in areas where high humidity is expected (e.g. through
cleaning processes) or on cooled or heated vessels.
Fig. 3: Polarization position
Cable / conduit entry
Note:
Whenthehousingisrotated,thedirectionofpolarizationchangesandhencetheinuenceofthefalse
echo on the measured value. Please keep this in mind when mounting or making changes later.

CNCR-210/220 • Two-wire 4
-
20 7
In vessels with cone bottoms, the sensor can be mounted in the center of the vessel to mea-
sure material down to the outlet.
When mounting the sensor, distance it at least 200 mm (7.874 in) from the vessel wall. If the sensor
is installed in the center of dished or round vessel tops, multiple echoes can arise. However, these
can be suppressed by a false signal suppression (see chapter “Setup”).
If you cannot maintain this distance, you should carry out a false signal suppression during initial
setup. This applies particularly if buildup on the vessel wall is expected. If this is the case, we
recommend repeating the false signal suppression later with the additional buildup.
Fig. 5: Mounting the radar sensor with conical bottom
Fig. 4: Mounting the radar sensor on round vessel tops

CNCR-210/220 • Two-wire 4
-
20 8
Donotmounttheinstrumentinorabovethellstream.Makesurethatitispointedtowardsthe
materialsurface,notthellstream.
For socket or stand pipe mount, the pipe should be as short as possible and its bottom end
roundedtoreducefalsereectionsfromtheendofthepipe.
When using a threaded coupling, the antenna end should protrude at least 5 mm (0.2 in) out
of the coupling.
Fig. 6: Reference plane
1 Reference plane
Fig.7:Mountingtheradarsensorwithinowingmaterial
The lower side of the radar antenna is the reference plane for the min./max. adjustment, see
following diagram:

CNCR-210/220 • Two-wire 4
-
20 9
Socket diameter d Socket length h
40 mm 1½” ≤150mm ≤5.9in
50 mm 2” ≤200mm ≤7.9in
80 mm 3” ≤300mm ≤11.8in
100 mm 4” ≤400mm ≤15.8in
150 mm 6” ≤600mm ≤23.6in
Ifthereectivepropertiesofthematerialaregood,youcanmounttheCNCR-210onsockets
or stand pipes longer than the antenna. The pipe end should be smooth, burr-free and the end
rounded.
Note:
When mounting on longer sockets, we recommend carrying out a false signal suppression after
install (see chapter “Parameter adjustment”).
Recommended values for socket or stand pipe lengths and heights are in the following table. The
values come from typical applications.
Fig. 8: Mounting the radar sensor with stand pipes
5 Connecting to power supply
5.1 Preparing the connection
•Electricalconnectionshouldbecompletedbytrained,qualiedpersonnelauthorizedby
the plant operator.
• If overvoltage surges are expected, overvoltage arresters should be installed.

CNCR-210/220 • Two-wire 4
-
20 10
Warning:
Only connect or disconnect in de-energized state.
Note:
Power the instrument via an energy-limited circuit (power max. 100 W) according to IEC 61010-1,
e.g.
• Class 2 power supply unit (acc. to UL1310)
• SELV power supply unit (safety extra-low voltage) with suitable internal or external limitation
of the output current
UseroundcabletoensureeectivesealingofthecableglandtotheappropriateIPratingand
checkthecablediameterversusthecableglandbeforewiringforpropert.
The instrument is connected with standard two-wire cable.
If electromagnetic interference is expected which is above the test values of EN 61326-1 for
industrial areas, shielded cable should be used.
Note:
If the temperatures are too high, the cable insulation can be damaged.
5.2 Connecting
Fig. 9: Connection

CNCR-210/220 • Two-wire 4
-
20 11
5.3 Wiring plan
Connect the instrument as described in the following wiring plan.
Fig. 10: Connection compartment CNCR-210/220
1 Voltage supply +24 VDC, signal output
6 Setup with smartphone/tablet (Bluetooth)
6.1 Preparations
Make sure that your smartphone/tablet meets the following system requirements:
• Operating system: iOS 8 or newer
• Operating system: Android 5.1 or newer
• Bluetooth 4.0 LE or newer
DownloadtheWirelessDeviceConguratorappfromthe“AppleAppStore”or“GooglePlay
Store” to your smartphone or tablet. To enable the Bluetooth software enter the BinMaster
company ID code BMYQXZ.

CNCR-210/220 • Two-wire 4
-
20 12
6.2 Connecting
Start the adjustment app and select the function “Setup”. The smartphone/tablet searches
automatically for Bluetooth-capable instruments in the area.
The message “Connecting …” is displayed.
The devices found are listed and the search is automatically continued.
Select the requested instrument in the device list.
Whenestablishingtheconnectionforthersttime,theoperatingtoolandthesensormust
authenticateeachother.Aftertherstcorrectauthentication,eachsubsequentconnectionis
made without a new authentication query.
Forauthentication,enterthe6-digitBluetoothaccesscodeinthenextmenuwindow.Youcannd
the code on the outside of the device housing and on the setup information sheet in the device
packaging.
Note:
If an incorrect code is entered, the code can only be entered again after a delay time and the delay
gets longer after each incorrect entry.
The message “Waiting for authentication” is displayed on the smartphone/tablet.
After connection, the sensor adjustment menu is displayed on the smartphone/tablet.
If the Bluetooth connection is interrupted, e.g. due to a too large distance between the two devices,
this is displayed on the smartphone/tablet. The message disappears when the connection is restored.
Parameter adjustment of the device is only possible if the parameter protection is deactivated, which
is default. Parameter protection can be activated later if desired.
Fig. 11: Enter Bluetooth access code

CNCR-210/220 • Two-wire 4
-
20 13
6.3 Parameter adjustment
The sensor adjustment menu is divided into two areas, which are arranged next to each other or
one below the other, depending on the smartphone/tablet.
• Navigation section
• Menu item display
The selected menu item can be recognized by the color change.
Entertherequestedparametersandconrmviathekeyboardortheeditingeld.Thesettingsare
then active in the sensor.
Close the app to terminate connection.
Note
IftheCNCRfailstoconnecttotheWirelessDeviceCongurationApp(WDCA)viaBluetooth,
close the (WDCA), power cycle the CNCR and attempt to reconnect.
If further action is required, power cycle the Bluetooth on your device, and repeat the steps above.
Fig. 12: Example of an app view - Setup sensor adjustment

CNCR-210/220 • Two-wire 4
-
20 14
Menu item Selection Default settings
Measurement loop name Alphanumeric characters Sensor
Medium Liquid
Bulk solid
Liquid
Application liquid
Storage tank, agitator tank, dosing tank, pumping station/
pumpshaft,rainoverowbasin,tank/collectionbasin,
plastic tank (measurement through tank top), mobile
plastictank(IBC),levelmeasurementinwaters,ow
measurementume/over-ow,demonstration
Storage tank
Application bulk solid Silo (slim and high), bunker (large
volume), stockpile (point measurement/
proledetection),crusher,demonstration
Silo
(slender and high)
Units Distance unit of the device
Temperature unit of the instrument
Distance in ft.
Temperature in °F
Adjustment CNCR-210 Max. adjustment (distance A) - 20mA (100%)
Min. adjustment (distance B) - 4mA (0%)
Distance from sensor
Max. adjustment 0.0 m
Min. adjustment 8.0 m
Adjustment CNCR-220 Max. adjustment (distance A) - 20mA (100%)
Min. adjustment (distance B) - 4mA (0%)
Distance from sensor
Max. adjustment 0.0 m
Min. adjustment 15.0 m
Menu item Selection Default settings
Damping Integration time 0 s
Current output Output characteristics 4 to 20 mA = 0% to 100%
Current range Min. current 4 mA and
max. current 20.5 mA
Reaction when malfunctions occur Failure mode < 3.6 mA
Linearization Linearization type Linear
Scaling Scaling size
Scaling unit
Scaling format
0% correspond to 0 l
100% correspond
to 100 l
Display Menu language
Displayed value
Backlight
English
Distance
On
Access protection Bluetooth access code -
Parameter Protection Deactivated
False signal suppression False signal suppression 0 m
Sounded distance to the material 0 m
Reset Delivery status, basic settings -
Menu item Selection Default settings
Status Sensor status
Measured value status
Status output
Status additional measured values
-
Echo curve Indication of echo curve -
7 Menu overview

CNCR-210/220 • Two-wire 4
-
20 15
8 Diagnostics and servicing
8.1 Maintenance
If the device is used properly, no special maintenance is required in normal operation.
Insomeapplications,buildupontheantennasystemcaninuencethemeasurement.
Depending on the sensor and application, be careful to avoid heavy soiling of the antenna
system. If necessary, clean the antenna system periodically.
8.2 Status messages
The status messages are divided into the following categories:
• Failure
• Function check
•Outofspecication
• Maintenance required
Failure
Code
Text message Cause Rectication
DevSpec
State in CMD 48
F013
no measured value
available
Sensor does not detect
an echo during operation
Antenna system dirty or
defective
Check or correct installation and/or
parameter settings
Clean or exchange process compo-
nent or antenna
Byte 5, Bit 0 of
Byte 0-5
F017
Adjustment span
too small
Adjustment not within spec-
ication
Change adjustment according to the
limitvalues(dierencebetweenmin.
andmax.≥10mm)
Byte 5, Bit 1 of
Byte 0-5
F025
Error in the
linearization table
Index markers are not
continuously rising, for
example illogical value pairs
Check linearization table
Delete table/Create new
Byte 5, Bit 2 of
Byte 0-5
F036
No operable
software
Failed or interrupted soft-
ware update
Repeat software update
Check electronics version
Exchanging the electronics
Send instrument for repair
Byte 5, Bit 3 of
Byte 0-5
F040
Error in the
electronics
Hardware defect Exchanging the electronics
Send instrument for repair
Byte 5, Bit 4 of
Byte 0-5
F080
General software
error
General software error Disconnect operating voltage
briey
Byte 5, Bit 5 of
Byte 0-5
F105
Determine
measured value
The instrument is still
in the start phase, the mea-
sured value could
not yet be determined
Wait for the end of the switch-on
phase
Duration up to approx. 3 minutes
depending on the version and
parameter settings
Byte 5, Bit 6 of
Byte 0-5

CNCR-210/220 • Two-wire 4
-
20 16
Code
Text message Cause Rectication
DevSpec
State in CMD 48
S600
Impermissible
electronics temperature
Temperature of the electronics
inthenon-speciedrange
Check ambient temperature
Insulate electronics
Byte 23, Bit 4 of
Byte 14-24
S601
Overlling
Dangerofvesseloverlling Make sure that there
isnofurtherlling
Check level in the vessel
Byte 23, Bit 5 of
Byte 14-24
S603
Impermissible
operating voltage
Terminal voltage too small Check terminal voltage, increase
operating voltage
Byte 23, Bit 6 of
Byte 14-24
Code
Text message Cause Rectication
DevSpec
State in CMD 48
C700
Simulation active
A simulation is active Finish simulation
Wait for the automatic
end after 60 mins.
“Simulation Ac-
tive” in “Standard-
ized Status 0”
Code
Text message Cause Rectication
DevSpec
State in CMD 48
F113
Communication
error
EMC interference RemoveEMCinuences Byte 4, Bit 4 of
Byte 0-5
F125
Impermissible electronics
temperature
Temperature of the electronics
inthenon-speciedrange
Check ambient temperature
Insulate electronics
Use instrument with higher
temperature range
Byte 5, Bit 7 of
Byte 0-5
F260
Error in the calibration
Error in the calibration carried
out in the factory
Error in the EEPROM
Exchanging the electronics
Send instrument for repair
Byte 4, Bit 0 of
Byte 0-5
F261
Error in the instrument
settings
Error during setup
False signal suppression faulty
Error when carrying out a reset
Repeat setup
Carry out a reset
Byte 4, Bit 1 of
Byte 0-5
F264
Installation/Setup error
Adjustment not within the
vessel height/measuring range
Max. measuring range of the
instrumentnotsucient
Check or correct installation and/
or parameter settings
Use an instrument with bigger
measuring range
Byte 4, Bit 2 of
Byte 0-5
F265
Measurement function
disturbed
Sensor no longer carries out a
measurement
Operating voltage too low
Check operating voltage
Carry out a reset
Disconnect operating voltage
briey
Byte 4, Bit 3 of
Byte 0-5
Failure
Function check
Out of specication

CNCR-210/220 • Two-wire 4
-
20 17
9 Removal
The device is made of recyclable materials that can be disposed of by specialty recycling companies.
Observe the applicable local regulations for proper disposal.
10 Certicates and approvals
10.1 Radio licenses
Radar
The device has been tested and approved in accordance with the current edition of the applicable
country-specicnormsorstandards.
Bluetooth
The Bluetooth radio module in the device has been tested and approved according to the current edition
oftheapplicablecountry-specicnormsorstandards.
Maintenance
Code
Text message Cause Rectication
DevSpec State in
CMD 48
M500
Error during the
reset “delivery status”
The data could not be restored
during the reset to delivery
status
Repeat reset
LoadXMLlewithsensordata
into the sensor
Byte 24, Bit 0 of
Byte 14-24
M501
Error in the nonactive
linearization table
Hardware error EEPROM Exchanging the electronics
Send instrument for repair
Byte 24, Bit 1 of
Byte 14-24
M502 Error in
the event memory
Hardware error EEPROM Exchanging the electronics
Send instrument for repair
Byte 24, Bit 2
ofByte 14-24
M503
Measurement reliability
too low
The echo/noise ratio is too
small for reliable measurement
Antenna dirty or defective
Check installation and process
conditions
Change polarization direction
Use instrument with higher sensitivity
Clean the antenna
Byte 24, Bit 3 of
Byte 14-24
M504
Error at a device interface
Hardware defect Check connections
Exchanging the electronics
Send instrument for repair
Byte 24, Bit 4 of
Byte 14-24
M505
No echo available
Sensor does not detect
an echo during operation
Antenna dirty or defective
Clean the antenna
Use a more suitable antenna/ sensor
Remove possible false echoes
Optimize sensor position and
orientation
Byte 24, Bit 5 of
Byte 14-24
M506
Installation/Setup error
Error during setup Check or correct installation and/or
parameter settings
Byte 24, Bit 6
ofByte 14-24
M507
Error in the instrument
settings
Error during setup
Error when carrying out a reset
False signal suppression faulty
Carry out reset and repeat setup Byte 24, Bit 7 of
Byte 14-24

CNCR-210/220 • Two-wire 4
-
20 18
Materials and weights
Materials, wetted parts
–Antenna,processtting PVDF
– Process seal FKM
Materials, non-wetted parts
– Housing Plastic PBT (Polyester)
– Housing seals O-rings (silicone)
– Cable gland PA
– Sealing, cable gland NBR
– Blind plug, cable gland PA
– Weight 0.7 kg (1.543 lbs)
Torques
Max. torque mounting boss 7 Nm (5.163 lbf ft)
Max. torque for NPT cable glands and conduit tubes 10 Nm (7.376 lbf ft)
Measurement Range
Measurement Range
The measurement range is the distance between the
antenna face of the sensor and the material surface.
The antenna face is also the reference plane for
the measurement.
CNCR-210
Max. measuring range 8 m (26.25 ft)
Recommended measuring range up to 5 m (16.4 ft)
CNCR-220
Max. measuring range 15 m (49.21 ft)
Recommended measuring range up to 10 m (32.81 ft)
11 Supplement
11.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions which are included are valid for approved
instruments(e.g.withExapproval).Thesedatacandierfromthedatalistedherein,forexample
regarding the process conditions or the voltage supply.

CNCR-210/220 • Two-wire 4
-
20 19
Output
Output signal 4 to 20 mA
Range of the output signal 3.8 to 20.5 mA (default setting)
Signalresolution 0.3μA
Resolution, digital 1 mm (0.039 in)
Faultsignal,currentoutput(adjustable) ≤3.6mA,>=21mA,lastvalidmeasuredvalue
Max. output current 22 mA
Load See load resistance under Power supply
Startingcurrent ≤3.6mA;≤10mAfor5msafterswitchingon
Damping (63 % of the input variable), adjustable 0 to 999 s
Ambient conditions
Ambient temperature -40 to +60 °C (-40 to +140 °F)
Storage and transport temperature -40 to +80 °C (-40 to +176 °F)
Process conditions
Fortheprocessconditions,pleasealsonotethespecicationsontheprintedlabel.Thelowestvalue
(amount) always applies.
Process temperature -40 to +60 °C (-40 to +140 °F)
Process pressure -1 to 3 bar (-100 to 200 kPa/-14.5 to 43.51 psig)
Fig. 13: Measurement Range
1 Reference plane
2 Measured variable, max. measuring range

CNCR-210/220 • Two-wire 4
-
20 20
11.2 Dimensions
CNCR-210/220
Fig. 14: Dimensions CNCR-210/220
1 Thread G1½
2 Thread 1½ NPT
3 Thread R1½
Voltage supply
Operating voltage UB
– at 4 mA 12 to 35 V DC
– at 20 mA 9 to 35 V DC
Reverse voltage protection Integrated
Electrical protective measures
Altitude above sea level 5000 m (16404 ft)
Protection class III
Pollution degree 4
This manual suits for next models
1
Table of contents
Other Bin Master Accessories manuals

Bin Master
Bin Master FD-2000 User manual

Bin Master
Bin Master NCR-84 User manual

Bin Master
Bin Master NCR-80 User manual

Bin Master
Bin Master NCR-25 User manual

Bin Master
Bin Master CNCR-120 User manual

Bin Master
Bin Master CNCR-190 User manual

Bin Master
Bin Master CNCR-230 User manual

Bin Master
Bin Master NCR-80 User manual

Bin Master
Bin Master GWR-2000 User manual

Bin Master
Bin Master NCR-80 User manual