8
Installation
1. It is essential that the gas supply is correct for appliance to be installed and adequate supply
pressure and volume are available. The following checks should be made before installation:-
a. Gas Type appliance has been supplied for is shown on a
coloured sticker located above the gas entry point and next to
the rating plate. Check that this is correct for gas supply
appliance is being installed for. Gas conversion procedure is
shown in this manual.
b. Supply Pressure required for this appliance is shown in the
Specifications section of this manual. Check gas supply to
ensure that adequate supply pressure exists.
c. Input Rate of this appliance is shown on Rating Plate fitted to
inside of access door and in Specifications' section of this
manual. Input rate should be checked against available gas
supply line capacity. Particular note should be taken if
appliance is being added to an existing installation.
NOTE: It is important that adequately sized piping runs directly to the connection joint on the
appliance, with as few tees and elbows as possible to give maximum supply volume.
2. A suitable joining compound which resists the breakdown action of LPG must be used on every gas
line connection, unless compression fittings are used.
Connection to appliance is 3/4” BSP male.
NOTE: A Manual Isolation Valve must be fitted to the individual appliance supply line.
3. Correctly locate the appliance into its final operating position and using a spirit level, adjust legs so
that the unit is level and at the correct height.
4. Connect gas supply to the appliance.
5. Check all gas connections for leakages using soapy water or other gas detecting equipment.
6. Check gas supply pressure is as shown in ‘Specifications’ section, ‘Gas Supply Requirements’ table.
NOTE: Measure supply pressure at upper test point (Supply Pressure Test Point) on gas control
valve.
7. Light Pilot Burners. Refer to Operation section, Lighting Pilot Burners.
8. Check pilot flame size. Re-adjust if required, using pilot adjusting screw (See Fig 2 overleaf), and as
shown in Gas Conversion and Specifications section, Pilot Burner Flame Adjustment.
9. Light Main Burners. Refer to Operation section, Lighting Main Burners.
Rating Plate
Location
Fig 1
DONOT USE ANAKED FLAME TO CHECK FOR GAS LEAKAGES.
Warning
Ensure the tank(s) is / are filled with either water or oil prior to starting Main
Burners otherwise damage may be caused to fryer tank(s).
Caution