8. CONNECTING THE CONTROLER
Please read the instructions enclosed with each controller for complete details on mounting / connecting you controller to the air curtain.
The network sockets (connection points) are found on the left hand end of the air curtains. Either socket (see diagram, section 5, page 5) may be
used for the controller. The other socket is used when connecting other air curtains to the system.
There are knockouts on the casing to allow the network cable connections to be made. Connect all network cables before replacing the covers on to
the air curtains.
If adding more than one air curtain to the controller you will require an additional network cable for each additional air curtain.
Up to 11 additional air curtains may be connected together, giving a maximum of 12 air curtains per controller.
9. MAINTENANCE
Note: Before examining or carrying out any maintenance, ensure the air curtain has cooled down and is disconnected from the mains supply.
The air curtains are intended to operate for many years, problem free. All moving parts are factory lubricated and therefore should require no service.
A visual inspection of the unit and its internal components should be carried out once every 6 months.
Electric elements –The elements do not require any maintenance other than a visual inspection, however when cool, they may be vacuumed clean
to remove dust using a soft bush attachment.
Fuse –The mains inlet connector incorporates a 5A fuse which does not require any maintenance other than a visual inspection. Replace with a fuse
of the same type and value.
Fan motor –The fan motor has a ‘seal for life’ bearing which does not require any maintenance other than a visual inspection however they may be
vacuumed clean to remove dust using a soft bush attachment. All accessible surfaces can be wiped with a dry cloth.
Controls –Check remote on/off and speed switches for satisfactory operation.
Check fan run on and safety cut-out for satisfactory operation (located top of casing). If the safety cut out trips regularly in normal operation; check
the operation of the fan and that the airflow through the unit is not restricted by dust and the inlet or outlet are not obstructed. If the problem persists,
please contact us for further help.
When the air curtain is first turned on after cleaning, an unusual odour may be noted. This is due to the dust particles which inevitably will be disturbed
and be burnt off from the heating element.
If in any doubt always consult a qualified electrician for advice.
10. OVER TEMPERATURE PROTECTION / FUSE REPLACMENT
Two thermal protection switches are fitted to the air curtain.
One thermal switch provides the fan over-run. The fan will either continue to run after the unit is switched off on the wall control switch, until the air
temperature in the casing drops below 50°C, or will switch the fan back on after the unit is turned off should the case temperature rise above 50°C for
a short period.
The second manual reset thermal switch provides the safety cut out. Should the air temperature in the casing rises above 60°C this will cause the
safety cut out to trip. The safety cut out can be reset by pressing the red button located on top of the unit. If the safety cut out trips regularly; check
the operation of the fan and that the airflow through the unit is not restricted by dust and the inlet or outlet are not obstructed. If the problem persists,
please contact us.
The air curtain control circuit is protected by an internal fuse. The fuse holder is located near the contactors on the electrical tray. Should the fuse fail,
replace with another 5A fuse. If this replacement fuse fails seek professional help.
NOTE: It is our policy to continually improve products and as such we reserve the right to alter data, specifications and component parts without prior
notice.
IMPORTANT: No liability is accepted for incorrect use of this product.
WARRANTY: Your BN Thermic product is guaranteed for one year from date of purchase. We will repair
or replace at our discretion any part found to be defective. Our warranty does not cover corrosion. We
cannot assume any consequential liability. This guarantee in no way prejudices your rights under
common law and is offered as an addition to consumer liability rights.