BRK electronic First Alert SC9120LBLA User manual

120V AC, 60Hz Wire-in
with 10-Year Locked Lithium Battery Backup
COMBO
ALARM
10-YEAR CO SENSOR
10-YEAR ALARM LIFE
10-YEAR LOCKED
LITHIUM BATTERY
SMOKE & CO COMBO
Electrochemical CO sensor;
Ionization smoke sensor.
LATCHING ALARM
INDICATOR
Remembers which unit initiated
an alarm.
SILENCE FEATURE
Silences nuisance alarms.
END-OF-LIFE SIGNAL
Provides audible notice when alarm
needs to be replaced after 10 years.
CAT. SC9120LBLA
Standard
Listed to
ULC S531
& CSA 6.19
S M O K E & C O
Description:
The BRK Brands, Inc. model SC9120LBLA is a wire-in, 120V 60Hz single and/or multiple
station smoke and carbon monoxide alarm specically designed for residential and
institutional applications including sleeping rooms of hospitals, hotels, motels, dormitories
and other multi-family dwellings. Model SC9120LBLA complies with ULC S531 and CSA
6.19. It meets building codes where AC/DC smoke and carbon monoxide alarms are required
either separately or in combination. The alarms are interconnectable up to 18 devices, of
which 12 can be smoke alarms.
The BRK®SC9120LBLA features a ionization smoke sensing chamber and a carbon
monoxide sensor, an 85dB horn, 10-Year Locked Lithium Battery Backup and a “silence”
feature. The “Intelligent Sensing Technology” system is designed to reduce nuisance
alarms. “Latching Alarm Indication” remembers which unit initiated an alarm. When
interconnected in a series, the unit that triggered the alarm rapidly ashes its red LED
indicator light. After the alarm condition subsides, the initiating unit will store in memory
or “latch” the information and begin to ash the Red LED indicator 2 seconds on,
2 seconds off. The “Perfect Mount” system features a gasketless base and a mounting bracket
that keeps the alarm secure over a wide rotation range to allow for true alignment. Other
Contractor Preferred features include a dust cover to keep alarm clean during construction and
keyhole slots in the mounting bracket eliminate the need to remove the electrical box screws
for installation. Two locking features are provided to prevent battery theft and/or theft of the
unit. Connection to AC power is made with a “Quick-Connect” wiring harness. Installation is
quick, easy and cost effective.
INSTALLATION OF ALARM
Installation of this smoke alarm must conform to all Canadian
electrical codes. It is recommended that all units be on the same
fuse or circuit breaker. If codes do not permit, be sure the neutral
wire is common to both phases.
©2019 BRK Brands, Inc. All rights reserved. Distributed
by BRK Brands, Inc. 3901 Liberty Street, Aurora, Illinois
60504. BRK Brands, Inc. is a subsidiary of Newell
Brands Inc. (NYSE: NWL). BRK is a registered trademark
of BRK Brands, Inc.
brkcanada.ca
1. Smoke /CO Alarm
2. Ceiling or Wall
3. Power Connector
4. Wire Nut
5. Junction Box
6. Neutral Wire (White)
7. Interconnect Wire (Orange)
8. Hot Wire (Black)
THE PARTS OF THIS ALARM
TECHNICAL SPECS
Alarm Dimensions: 5.6” dia x 2”H
Weight: 8.5 oz
Operating Voltage: 120V AC 60Hz w/ Locked Lithium Battery Backup
Operating Current: .09 amps (standby/alarm)
Temperature Range: 40° F (4° C) to 100° F (38° C)
Humidity Range: 10% to 95% relative humidity (RH)
Audio Alarm: 85dB at 10 feet
Test/Silence: Electronically simulates a smoke or carbon
monoxide condition, causing the unit to alarm.
Press and hold the test/silence button.
Alarm Reset: Automatic when Smoke and/or CO clears
Interconnections: Up to 18 Units of First Alert BRK Smoke, CO and
Heat Alarms. Maximum of 12 smoke alarms.
See user’s manual for details.
Smoke Sensor: Dual Ionization
CO Sensor: Electrochemical
Indicator Lights/Sounds:
AC Power: Constant Green LED
DC Power: Intermittent Green LED
Local Alarm: Red LED ashes rapidly Remote Alarm:
Red LED out
Latching Alarm: Red LED ashes 2 sec. on/2 sec. off after
local alarm
Low Battery Latch: Green LED ashes on for 2 seconds,
off for 2 seconds
End-of-Life Signal: Alarm “chirps” 3 times with 5 green LED ashes
once per minute
Listing: Listed to ULC S531 and CSA 6.19 Standards
SHIPPING SPECS
Individual Carton Dimensions: 5.69”L x 2.25”W x 5.59”H
Weight: .63 lbs.
Cube: .04 ft3
UPC: 0 29054 01758 1
Master Carton Dimensions: 14.43”L X 6.19”W X 12.63”H
Master Pack: 12
Weight: 8.1 lbs.
Cube: .65 ft3
I2of5: 100 29054 01758 8
Pallet Information:
Cases per Layer: 19
Number of Layers: 3
Cases per Pallet: 57
Units per Pallet: 684
Cube: 42.2 ft3
Weight: 527 lbs.
1. Mounting bracket
2. Mounting Slots
3. Locking Pins
4. Hot (Black) AC Wire
5. Neutral (White) AC Wire
6. Interconnect (Orange) Wire
7. Battery Drawer Latch
8. Battery Drawer - Install 9V
battery here
9. 9. Quick-Connect Plug
CAT. SC9120LBLA
A. Unswitched 120VAC 60 Hz source
B. To additional units; Maximum = 18 total
(Maximum 12 Smoke Alarms)
MOUNTING
BRACKET
TOP VIEW SIDE VIEW
5.6”
2.0”
ARCHITECTURAL AND ENGINEERING SPECS
The combination smoke and CO alarm shall be a BRK Model SC9120LBLA and shall provide
at a minimum the following features and functions:
1. An ionization smoke sensing chamber and an electrochemical CO sensor.
2. Powered by 120V AC, 60Hz and have a monitored 10-Year Locked Lithium Battery Backup and a solid
state piezo horn rated at 85dB at 10 ft. and be capable of self restoring.
3. The unit shall perform self diagnostic tests and issue a malfunction warning (three chirps) if the unit
malfunctions.
4. The unit shall have an “End of Life” signal. This signal should be capable of temporarily being silenced
for up to 2 days. After about 2 days, the signal will resume. After about 2-3 weeks the signal cannot
be silenced.
5. A visual power-on indicator to conrm unit is receiving AC power or has switched to battery backup
mode. Separate LED’s to indicate a smoke or CO alarm.
6. The CO sensor is adjusted not to detect CO levels below 30 PPM and will not alarm when exposed to
constant levels of 30 PPM for 30 days. It will alarm at the following levels: 400 PPM CO between 4 and
15 minutes, 150 PPM CO between 10 and 50 minutes and 70 PPM CO between 60 and 240 minutes.
7. Two Latching features: Alarm Latch to easily identify initiating alarm after alarm condition has subsided.
Low battery latch: to visually identify which unit is in low battery condition. Silence Feature: Alarm
Silence to temporarily silence nuisance alarms.
8. Two Locking features - tamper resistant locking pins that lock battery drawer and/or alarm to mounting
bracket. Battery drawer is shipped pre-locked so battery will not be discarded prematurely.
9. The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and relative humidity
between 10% and 95%.
10. The unit shall have a plug in connector and be capable of interconnection of up to 18 alarms, 12 of which
can be smoke alarms.
11. The unit shall at a minimum meet the requirements of ULC S531 and CSA 6.19.
1
2
3
5
6
4
2
3
9
7
8
678
43 1
5 2
A
B
}}
43 15
REV 11/19

Other BRK electronic Security System manuals

BRK electronic C0250B User manual

BRK electronic

BRK electronic C0250B User manual

BRK electronic D702MC User manual

BRK electronic

BRK electronic D702MC User manual

BRK electronic First Alert SC9120BA User manual

BRK electronic

BRK electronic First Alert SC9120BA User manual

BRK electronic CO910V User manual

BRK electronic

BRK electronic CO910V User manual

BRK electronic 7030BSL User manual

BRK electronic

BRK electronic 7030BSL User manual

BRK electronic PC910VB User manual

BRK electronic

BRK electronic PC910VB User manual

BRK electronic MPG120 User manual

BRK electronic

BRK electronic MPG120 User manual

Popular Security System manuals by other brands

Brooks Firetracker FT1-SB System manual

Brooks

Brooks Firetracker FT1-SB System manual

Teletek electronics CM 120 R Installation and programming manual

Teletek electronics

Teletek electronics CM 120 R Installation and programming manual

Geutebruck G-ST 500+ Series installation manual

Geutebruck

Geutebruck G-ST 500+ Series installation manual

Menvier Security SD1 installation instructions

Menvier Security

Menvier Security SD1 installation instructions

Swann SW351-MDA operating instructions

Swann

Swann SW351-MDA operating instructions

Logan Switch CVBS AHD CVI TVI user manual

Logan

Logan Switch CVBS AHD CVI TVI user manual

SECU4 SECU4Bags user manual

SECU4

SECU4 SECU4Bags user manual

NAPCO MAGNUM ALERT 900 SYSTEM manual

NAPCO

NAPCO MAGNUM ALERT 900 SYSTEM manual

Pentair Pentek Defender Installation and user guide

Pentair

Pentair Pentek Defender Installation and user guide

Hiltron XR400GSM INSTALLATION GUIDE AND USE

Hiltron

Hiltron XR400GSM INSTALLATION GUIDE AND USE

GeoVision GV-Control Center System user manual

GeoVision

GeoVision GV-Control Center System user manual

DSC Impassa PT4 instruction sheet

DSC

DSC Impassa PT4 instruction sheet

ERA WIRELESS HD CCTV SYSTEM user manual

ERA

ERA WIRELESS HD CCTV SYSTEM user manual

SkyLink Household Aler HA-100 user manual

SkyLink

SkyLink Household Aler HA-100 user manual

Neptune NECPLBGN installation manual

Neptune

Neptune NECPLBGN installation manual

Teletek electronics CA864 installation manual

Teletek electronics

Teletek electronics CA864 installation manual

Monacor Security AV-3031COL Mounting instructions

Monacor

Monacor Security AV-3031COL Mounting instructions

RadioLink EIB168RC instructions

RadioLink

RadioLink EIB168RC instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.