Bryant CAPVP series User manual

CAPVP
Installation Instructions
Evaporator Coil
Upflow --- Downflow Cased
NOTE: Read the entire instruction manual before starting the
installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1.........................
INTRODUCTION 1...................................
INSTALLATION 2....................................
Inspect Equipment 2...............................
Select Installation 2................................
Installation of Evaporator Coils 2......................
Connect Refrigerant Piping 3.........................
Connect Lines 3...................................
Refrigerant Metering Device 4........................
Condensate Drain Line Connection 4...................
Waste Line Connection 4............................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock or other conditions
which may cause death, personal injury or property damage.
Consult a qualified installer, service agency, or your distributor or
branch for information or assistance. The qualified installer or
agency must use factory--authorized kits or accessories when
modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing
and work gloves. Use quenching cloths for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to the unit.
Consult local building codes and the current editions of the
National Electrical Codes (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical
Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol .
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER,WARNING and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing or servicing system, always turn off main
power to system. There may be more than one disconnect
switch. Turn off accessory heater power if applicable. Lock out
and tag disconnect switch with a suitable warning label.
!WARNING
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never use air or gases containing
oxygen for leak testing or operating
refrigerant compressors. Pressurized
mixtures of air or gases containing
oxygen can lead to an explosion.
!WARNING
PERSONAL INJURY HAZARD
Failure to follow this caution may result in personal injury.
This coil contains Nitrogen precharge of up to 15 PSI. Release
of this pressure through the center of the rubber plugs is
required before removing the plugs.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when
handling parts.
CAUTION
!
IMPORTANT: Nitrogen can leak out through the hole that the
needle pierced in the plugs. This does not indicate a leaking coil
nor warrant return of the coil.
2
Table 1 – CAPVP Cased Coil Information
MODEL SIZE (TON) FLUSH FIT TO
FURNACE WIDTH
COIL CONNECTION TUBE SIZE (IN.)
Liquid Suction
CAPVP1917ALA 1.5 17---1/2” / 445 mm 3/8 3/4
CAPVP2517ALA 2.0 17---1/2” / 445 mm 3/8 3/4
CAPVP3717ALA 3.0 17---1/2” / 445 mm 3/8 3/4
CAPVP3721ALA 3.0 21” / 533 mm 3/8 7/8
CAPVP4321ALA 3.5 21” / 533 mm 3/8 7/8
CAPVP6124ALA 5.0 24---1/2” / 622 mm 3/8 7/8
INTRODUCTION
Use this instruction manual to install CAPVP indoor coil on
multipoise furnaces. (See Fig. 1.) The CAPVP coil is enclosed in a
casing.
Downflow
Furnace
Installation
Upflow
Furnace
Installation
Return
Supply Return
Supply
Evaporator
Coil
A13060
Fig. 1 -- Typical Installation Upflow/Downflow Cased Coils
* CAUTION: DO NOT MOUNT COIL LOWER THAN
3˝ (76mm) MINIMUM OR FURNACE FAILURE MAY RESULT
Wide Coil Narrow Coil
Narrow Furnace
Wide Furnace
Field Fabricated
Adapter(s) 3˝ (76mm)
A13061
Fig. 2 -- Adapter(s) Installation When Coil Overhangs or Un-
derhangs Furnace
INSTALLATION
Inspect Equipment
File claim with shipper if equipment is damaged or incomplete.
Select Installation
Upflow CAPVP Coil Installation.
The cased coil is designed to fit furnaces of the same width.
1. Set coil in place on upflow furnace discharge air opening.
2. Ensure coil is level for proper condensate drainage. Do not
tip coil toward condensate drain. Coil casing need not be
fastened or screwed to furnace.
3. When installing wider coil on narrow furnace, create field
fabricated adapter. (See Fig. 2.)
4. When installing narrow coil on wide furnace, create field
fabricated adapter. (See Fig. 2.)
NOTE: On upflow installations where the indoor coil is placed in
an unconditioned space, a 6” (152 mm) wide piece of insulation
should be applied and wrapped around the outside of coil casing
and supply duct contact point.
See Table 1 for dimensions. Note instructions for placement of coil
casing on furnace.
Downflow CAPVP Coil Installation.
IMPORTANT: Installing “A” coils rotated 90_from the front of
the furnace in downflow applications can cause water blow off or
coil freeze up. This is due to the concentration of air on one coil
slab or lack of air on the opposite coil slab. If the airflow is high
due to ductwork or other causes, and there is a chance for water
blow off, it is recommended that a 3” (76 mm) field--supplied
adapter be placed between the coil and the furnace to allow the air
to distribute evenly to both coil slabs. (See Fig. 3.)
3” (76mm)
A13062
Fig. 3 -- Downflow Installation With Coil Rotated 90_
1. Set cased coil on supply duct opening.
2. Place field fabricated 3” (76 mm) adapter on coil casing.
Adapter should be tapered to fit coil/furnace combination
when one of them is larger than the other.
3. Set furnace on adapter.
NOTE: In downflow installation with a 4--way multipoise
furnace, break off perforated duct flanges on furnace. See furnace
installation instructions.
CONNECT REFRIGERANT PIPING
Use accessory tubing package or field--supplied tubing of
refrigerant grade, see Product Data information for ordering.
Suction tube must be insulated. Do not use damaged, dirty, or
contaminated tubing because it may plug refrigerant flow--control
device. ALWAYS evacuate the coil and field--supplied tubing
before opening outdoor unit service valves.
CAPVP
3
CONNECT REFRIGERANT LIQUID AND
SUCTION LINES
For matched and mismatched systems, use line sizes recommended
in outdoor unit Installation Instructions.
UNIT OR PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Take precautions to ensure aluminum tubes do not come in
direct contact or allow for condensate run--off with a dissimilar
metal. Dissimilar metals can cause galvanic corrosion and
possible premature failure.
CAUTION
!
The coil can be connected to outdoor units using accessory tubing
packages or field--supplied tubing of refrigerant grade. Always
evacuate tubing and reclaim refrigerant when making connections
or flaring tubing. Leak check connections before insulating entire
suction line.
See Table 1 for coil connection tube size.
1. Remove cabinet access door.
2. Remove rubber plugs, suction plug then liquid plug, from
coil stubs using a pulling and twisting motion. Hold coil
stubs steady to avoid bending or distorting.
3. Remove tubing plate with rubber grommets and slide plate
with grommets onto the refrigerant lines (field line--set),
away from braze joints.
4. Fit refrigerant lines into coil stubs. Wrap a heat sinking
material such as a wet cloth behind braze joints.
5. Wrap TXV and nearby tubing with a heat--sinking material
such as a wet cloth.
6. Use 1/2 psig Nitrogen purge in the suction and out the
liquid line.
7. Braze using a Sil--Fos or Phos--copper alloy. Do not use soft
solder.
8. After brazing, allow joints to cool. Carefully remove TXV
bulb insulation and verify that the TXV bulb is securely
fastened with hose clamp. Tighten screw a half--turn past
hand tight with TXV bulb placed in the indentation with
full contact with the vapor line tube. Re--wrap TXV bulb
with insulation.
9. Leak check connections before insulating entire suction
line.
10. Slide tubing plate with rubber grommets over joints.
Position tubing at center of each grommet to ensure an air
seal around the tube. Reinstall cabinet door.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
To avoid valve damage to the refrigerant control device while
brazing, valves must be wrapped with a heat--sinking material
such as a wet cloth.
CAUTION
!
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal injury.
Wear eye protection.
Coil is factory charged with 15 psi nitrogen. The coil is under
pressure and TXV screen is in place behind liquid line plug.
DO NOT removed liquid line plug first; always remove the
suction line plug first to depressurize the coil.
!WARNING
REFRIGERANT METERING DEVICE
The CAPVP coil has a factory--installed hard shut--off TXV
designed only for use with R--410A refrigerant. Use only with
outdoor units designed for R--410A.
NOTE: All TXV’S have preset superheat settings and are field
non--adjustable.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
DO NOT BURY MORE THAN 36” (914 mm) OF
REFRIGERANT TUBING IN GROUND. If any section of
tubing is buried, there must be a 6” (152 mm) vertical rise to the
valve connections on the outdoor unit. If more than the
recommended length is buried, refrigerant may migrate to cooler
buried section during extended periods of unit shutdown,
causing refrigerant slugging and possible compressor damage at
start--up.
CAUTION
!
CONDENSATE LINE CONNECTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
When installing over a finished ceiling and/or living area,
install a field--fabricated secondary condensate pan under the
entire unit.
CAUTION
!
The coil is designed to dispose of accumulated water through
built--in condensate drain fittings. It is recommended that PVC
fittings be used on the condensate pan. Do not over--tighten. Finger
tighten plus 1--1/2 turns. Be sure to install plastic plug in unused
condensate drain fitting. Two 3/4”. female threaded pipe
connections are provided in each coil condensate pan.
A trap is not necessary on the condensate line. Consult local codes
for additional restrictions or precautions. If local codes require a
trap then the following guidelines are suggested to assure proper
drainage. Install a trap in condensate line of coil as close to the coil
as possible. Make trap at least 3“ (76 mm) deep and no higher than
the bottom of unit condensate drain opening (See Fig. 4). Pitch
condensate line 1” (25.4 mm) for every 10 ft. of length to an open
drain or sump. Make sure that the outlet of each trap is below its
connection to condensate pan to prevent condensate from
CAPVP
4
overflowing the drain pan. Prime all traps, test for leaks, and
insulate traps and lines if located above a living area.
3” (76mm)
A13067
Fig. 4 -- Condensate Trap
NOTE: The unit is shipped from the factory with the horizontal
drain connections capped as for vertical installations. For
horizontal installations, remove the caps and place them on the
vertical drain connections to keep an airtight installation.
NOTE: If unit is located in or above a living space, where damage
may result from condensate overflow, a field--supplied, external
condensate pan should be installed underneath the entire unit, and a
secondary condensate line (with appropriate trap) should be run
from the unit into the pan. Any condensate in this external
condensate pan should be drained to a noticeable place. As an
alternative to using an external condensate pan, some localities
may allow the running of a separate 3/4--in. (19 mm) condensate
line (with appropriate trap) per local code to a place where the
condensate will be noticeable. The owner of the structure must be
informed that when condensate flows from secondary drain or
external condensate pan, the unit requires servicing or water
damage will occur. To further protect against water damage, install
a float switch to shut the unit off if the water in the secondary pan
gets too high.
NOTE: To avoid drainage problems, test the primary drain line by
slowly pouring water into the pan. Check piping for leaks and
proper condensate drainage. Using the secondary drain as
explained in the previous note provides further protection against
overflow due to a clogged primary drain.
NOTE:In applications where return air humidity levels stay at
70% or above for a prolonged period of time, condensation can
form on the bottom of pan and drip.
Condensate
Line
Trap
Sewer Line
Air Gap Above
Liquid Level
A10216
Fig. 5 -- Condensate Drain to Waste Line
WASTE LINE CONNECTION
If the condensate line is to be connected to a waste (sewer) line, an
open trap must be installed ahead of the waste line to prevent
escape of sewer gases (See Fig. 5).
EXPLOSION HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Provide trap with air gap in drain line
when connecting to waste (sewer) line.
!WARNING
Copyright 2017 CAC / BDP D7310 W. Morris St. DIndianapolis, IN 46231 Edition Date: 07/17
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
C a t a l o g N o : I M --- C
A
P
V
P --- 0 2
R e p l a c e s: IM --- C AP V P --- 0 1
CAPVP

This manual suits for next models

6

Other Bryant Fan manuals

Bryant PAYNE 619C Installation and maintenance instructions

Bryant

Bryant PAYNE 619C Installation and maintenance instructions

Bryant HRVBBLHA Operation manual

Bryant

Bryant HRVBBLHA Operation manual

Bryant ERVBBLHA Operation manual

Bryant

Bryant ERVBBLHA Operation manual

Bryant ERVBBSVA1100 User manual

Bryant

Bryant ERVBBSVA1100 User manual

Bryant FAN COIL UNITS FF1DNA User manual

Bryant

Bryant FAN COIL UNITS FF1DNA User manual

Bryant HRVBBLHU Guide

Bryant

Bryant HRVBBLHU Guide

Bryant HRVBBLHA User manual

Bryant

Bryant HRVBBLHA User manual

Bryant ERVBBLHA Guide

Bryant

Bryant ERVBBLHA Guide

Bryant FA4A User manual

Bryant

Bryant FA4A User manual

Bryant 542F User manual

Bryant

Bryant 542F User manual

Bryant HRVXX Operation manual

Bryant

Bryant HRVXX Operation manual

Bryant 517E User manual

Bryant

Bryant 517E User manual

Bryant ERVBBSVB Operation manual

Bryant

Bryant ERVBBSVB Operation manual

Bryant FX4D Operation manual

Bryant

Bryant FX4D Operation manual

Bryant 619E Series Dimensions and installation guide

Bryant

Bryant 619E Series Dimensions and installation guide

Bryant HEAT RECOVERY VENTILATOR ERVBBLHA Operation manual

Bryant

Bryant HEAT RECOVERY VENTILATOR ERVBBLHA Operation manual

Bryant ERVBBLHA Series User manual

Bryant

Bryant ERVBBLHA Series User manual

Bryant FNCCAB series User manual

Bryant

Bryant FNCCAB series User manual

Bryant FAN UNIT FH4B User manual

Bryant

Bryant FAN UNIT FH4B User manual

Bryant HRVBBLHA User manual

Bryant

Bryant HRVBBLHA User manual

Bryant PERFECT AIR 1620 User manual

Bryant

Bryant PERFECT AIR 1620 User manual

Popular Fan manuals by other brands

inVENTer iV-Light operating instructions

inVENTer

inVENTer iV-Light operating instructions

Vornado OSCR37 owner's guide

Vornado

Vornado OSCR37 owner's guide

MICO aeronom WR 600 Mounting and operating instructions

MICO

MICO aeronom WR 600 Mounting and operating instructions

Faro Barcelona Corso manual

Faro Barcelona

Faro Barcelona Corso manual

Vallox A3712-1 manual

Vallox

Vallox A3712-1 manual

Fantech DBF110 installation instructions

Fantech

Fantech DBF110 installation instructions

Iwata HVLS DRUM 44 instruction manual

Iwata

Iwata HVLS DRUM 44 instruction manual

QUORUM INTERNATIONAL The Angel installation instructions

QUORUM INTERNATIONAL

QUORUM INTERNATIONAL The Angel installation instructions

KORADO KORASMART TUBE 2400E Quick start instructions

KORADO

KORADO KORASMART TUBE 2400E Quick start instructions

Hunter Altitude Owner's guide and installation manual

Hunter

Hunter Altitude Owner's guide and installation manual

ELTA FANS TWINFLOW STDR Installation & maintenance

ELTA FANS

ELTA FANS TWINFLOW STDR Installation & maintenance

DAY 73443 instruction manual

DAY

DAY 73443 instruction manual

Makita BCF300 instruction manual

Makita

Makita BCF300 instruction manual

EKIZNSN F073 owner's manual

EKIZNSN

EKIZNSN F073 owner's manual

Airflow MaxAir 7105A installation instructions

Airflow

Airflow MaxAir 7105A installation instructions

Hunter Brayden 21325 Parts guide

Hunter

Hunter Brayden 21325 Parts guide

Siemens LR97CAQ50 User manual and installation instructions

Siemens

Siemens LR97CAQ50 User manual and installation instructions

Elba ETWF-A3540RC owner's manual

Elba

Elba ETWF-A3540RC owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.