C.P. Electronics DD-LCDHS User manual

1. Description and Operation
2. LCD Navigation
The DD-LCD-HS is the programming tool for all products in the –DD
(Direct Dim), -PRM (PRM) and MWS7 ranges.
On button
To turn the unit on press the „on‟ button. This button is also used for
selecting parameters and then sending to the device being
programmed.
Up, down. Left and right buttons
Use to navigate through the menus. The up and down buttons are
also used for selecting values or toggling between on / off, yes / no
etc.
To turn the unit off, either select the final main menu item or the unit
will turn off after 30 seconds.
Section Contents Page
1 Description and operation 1
2 LCD Navigation 1
3 Menu tree 2
4 Detector Parameter Menu 3
5 Modes menu 4
6 Ch1 (sw) set Menu 5
7 Ch2 (dim) set Menu 6
8 User menu 7
9 Ratings 8
Menu selection
Use the < > buttons to scroll through the menus. Press „on‟ to select.
Parameter selection
Use the < > buttons to scroll through the menus. Press „on‟ to select
menu. Use the up and down buttons to select values or toggle
between on / off, yes / no. Press „on‟ to send parameter to device.
Contents
Direct Dim, PRM and MWS7 Handset
Product Guide
DD-LCDHS

2
3. Menu Tree

3
IR cmd Description Default Products
Time Mins 10 seconds to 99 minutes time delay (select 0 for 10 second delay –use for commis-
sioning only).
All
Sens on Sensitivity level when the detector is already operational adjustable between 1 (min.)
and 9 (max.)
Product
dependant
All
Sens off Sensitivity level for switching the detector on –adjustable between 1 (min.) and 9
(max.).
Product
dependant
All
Range m Set the detectors‟ range in metres (0-999m) 8 MWS7 only
Power Up On Select No for a 30 second delay on start up. If Yes is selected, there will be no delay on
start up and the detector will always power up detecting.
Y All
Walk test If set, walk test mode will flash the internal LED when occupancy is detected N All
Disable Det Disables detection, leaving the relay output permanently off with the dimming output
operational. This mode is used when the unit is for maintained illuminance only.
N All
Factory default Restores factory default settings
Use with caution
All
Menus
The final column for each menu section shows which products can programmed with specific parameters.
4. Detector Parameter Menu

4
IR cmd Description Products
Channel modes Selects the channel modes menu All
Switch modes Selects the switch modes menu All
5. Modes Menu
IR cmd Description Default Products
Switch only Usually used for absence detection - in this mode the dimming channel is not used. -DD & MWS7
only
Sw&Dim
together
The detector will switch and dim the lighting together. Default -DD & MWS7
only
Sw&Dim
separate
Provides 2 channel operation –Channel 1 is switched via the relay output, and
Channel 2 is dimmed / switched via the dimming output.
-DD & MWS7
only
Channel Modes Menu
IR cmd Description Default Products
2pos sw
together
A single centre biased retractive switch will be used to control both channels to-
gether.
Default -DD & MWS7
only
2pos sw
separate
A single centre biased retractive switch will be used to control only the dimming
channel.
-DD & MWS7
only
1pos sw
together
A single position retractive switch controls both channels together. -DD & MWS7
only
1pos sw
separate
Two single position retractive switches, controlling the channels separately. -DD & MWS7
only
Switch Modes Menu

5
IR cmd Description Default Products
Presence Auto switch on with detection, auto off after movement ceases and time delay ends. Product
dependant
All
Absence Manual switch on, auto off after movement ceases and time delay ends. Product
dependant
All
Sw lev on Switch level on
Lux level setting to prevent the luminaires being switched on if the ambient light level
is sufficient (adjustable between 1 and 9). The luminaires will always be switched on at
level 9. For a higher resolution of „switch level on‟ a scale of 101-199 is available in the
„Special menu‟.
9 All
Sw lev off Switch level off
Lux level setting to switch the luminaires off during occupancy if the ambient light level
goes above the setting (adjustable between 1 and 9). Level 9 will always keep the lights
on. This setting can be used for “window row switching”.
9 All
Special Selects the special menu below All
6. Ch1 (sw) set Menu
Use this menu for programming Channel 1. This is the switched channel.
IR cmd Description Default Products
Sw lev on Switch level on
Lux level setting to prevent the luminaires being switched on if the ambient light
level is sufficient (adjustable between 101 and 199).
Use to provide finer adjustment than parameters above.
None All
Sw lev off Switch level off
Lux level setting to switch the luminaires off during occupancy if the ambient light
level goes above the setting (adjustable between 101 and 199).
Use to provide finer adjustment than parameters above.
None All
Special Menu

6
IR cmd Description Default Products
Light lev Light level. Maintained illuminance level (adjustable between 1 and 999). At 999 the
output will be always be at maximum.
-DD & MWS7
only
Presence Auto switch on with detection, auto off after movement ceases and time delay ends. Product
dependant
-DD & MWS7
only
Absence Manual switch on, auto off after movement ceases and time delay ends. Product
dependant
-DD & MWS7
only
Sw lev on Lux level setting to prevent the luminaires being switched on if the ambient light level is
sufficient (adjustable between 1 and 9). The luminaires will always be switched on at
level 9. For a higher resolution of „switch level on‟ a scale of 101-199 is available in the
„Special menu‟.
9 -DD & MWS7
only
Sw lev off Lux level setting to switch the luminaires off during occupancy if the ambient light level
goes above the setting (adjustable between 1 and 9). Level 9 will always keep the lights
on. This setting can be used for “window row switching”. For a higher resolution of
„switch level on‟ a scale of 101-199 is available in the „Special menu‟.
9 -DD & MWS7
only
DSI Selects DSI dimming Default -DD & MWS7
only
DALI Selects DALI dimming -DD & MWS7
only
Memorise If this is set to Yes, the last manual lux level set will be memorised and used as the new
switch on level.
N -DD & MWS7
only
On value Dimming output level when switched on (0-99). 99 -DD & MWS7
only
Off value Dimming output level when switched off (0-99). If a non-zero off value is set, then the
output will toggle between this value and completely off depending on the switch level
on and off values. For example, if it is light outside, the fittings will be off if there is no
occupancy. If it is dark outside, they will adopt the preset off value. This feature is only
enabled if „Min value‟ is set to 99.
0 -DD & MWS7
only
Fade value After occupancy ceases, this dimming output level is loaded for the fade time
(adjustable between 0 and 99).
10 -DD & MWS7
only
Fade mins This is the time period (adjustable between 0 and 99 minutes) that the luminaire will be
held at the fade value before turning off. A value of 0 disables the fade function.
0 -DD & MWS7
only
Max value Maximum dimming output level (adjustable between 0 and 99). 99 -DD & MWS7
only
Min value Minimum dimming output level (adjustable between 0 and 99). 1 -DD & MWS7
only
Burn-n hrs Determines how long the output will be at 100% so that lamps „burn-in‟ (adjustable
between 1 and 999 hours). The ‟burn-in‟ time is not affected by power supply interrup-
tions. To disable burn-in set to 0 .
0 -DD & MWS7
only
Speed on Determines the dimming response speed after the setup time has finished. Measured in
0.1 sec intervals.
40 -DD & MWS7
only
Speed set Determines the dimming response speed during the set up time. Measured in 0.1 sec
intervals.
5 -DD & MWS7
only
Set secs Determines how long the dimming response set-up period lasts on power-up or on
setting change (adjustable between 1 and 999 seconds). This enables the desired lux
level to be achieved rapidly when the lights come on, or during setup.
120 -DD & MWS7
only
Special Selects the special menu below -DD & MWS7
only
7. Ch2 (dim) set Menu
Use this menu for programming Channel 2. This is the dimmed channel.

7
IR cmd Description Products
Lux up Increase light level. Reverts when occupancy cycle complete. All
Lux down Decrease light level. Reverts when occupancy cycle complete. All
Scene up Steps up between 6 pre-defined scenes. -DD & MWS7
only
Scene down Steps down between 6 pre-defined scenes. -DD & MWS7
only
Scene # Select the individual scene, between 0 and 6. (1 = min. output; 2 = 10%; 3 = 25%; 4 = 50%; 5 = 75%; 6 =
100%)
-DD & MWS7
only
Override on Permanently overrides the luminaire output on. All
Override off Permanently overrides the luminaire output off. All
Cancel Cancels the on or off override, returning the detector to normal operation. All
Set If sent before using lux up or lux down, it will set the light level as in „ Light lev‟ found „Ch2 (dim) set‟
menu
All
8. User Menu
IR cmd Description Default Products
Sw lev on Switch level on
Lux level setting to prevent the luminaires being switched on if the ambient light
level is sufficient (adjustable between 101 and 199).
Use to provide finer adjustment than parameters opposite.
None -DD & MWS7
only
Sw lev off Switch level off
Lux level setting to switch the luminaires off during occupancy if the ambient light
level goes above the setting (adjustable between 101 and 199).
Use to provide finer adjustment than parameters opposite.
None -DD & MWS7
only
DALI on Provides a permanent voltage to DALI ballasts when DALI has not been imple-
mented correctly in the ballast. Maximum number of ballasts is 10 unless the relay
is disabled then it is 20.
Off -DD & MWS7
only
Special Menu
7. Ch2 (dim) set Menu (con)

8
Ref #WD275 Issue 2
Battery 4 x 1.5Vdc AA
Temperature 0ºC to 35ºC
Compliance EMC-2004/108/EC
LVD-2006/95/EC
9. Ratings
C.P. Electronics Ltd
Brent Crescent
London
NW10 7XR
United Kingdom
Tel: + 44 (0) 333 900 0671
Fax: + 44 (0) 333 900 0674
www.cpelectronics.co.uk
enquiry@cpelectronics.co.uk
IMPORTANT NOTICE!
This device should be installed by a qualified electrician in
accordance with the latest edition of the IEE wiring regulations.
Due to our policy of continual product improvement CP Electronics reserves the right
to alter the specification of this product without prior notice.
FM 45789 EMS 534520
If any of these symbols are on the product or battery, the product or
battery must be disposed of in the correct manner and must not be
treated as household or general waste.
Table of contents
Other C.P. Electronics Control System manuals