CAMDEN CX-EMF-2 User manual

Page 1 of 16
Electrified Locks, Relays and Timers
CX-EMF-2 / EMF-2m
Multi-Function Timer
INSTALLATION INSTRUCTIONS
1. GENERAL DESCRIPTION
Camden's EMF-2 (EMF-2m or EMF-2ABM) is a microprocessor controlled multi-function relay. This all-in-one design replaces our
previous models EMF-1, EMF-1m or EMF-1ABM. The EMF-2 is designed for specialized applications such as ABM vestibules, one or two-
door restrooms in shared-use facilities, 2 – 5 door airlocks, and secure man-traps.
Dip switches let you choose the mode, and the unit automatically programs the inputs, outputs and potentiometers accordingly.
Removable terminal strips simplify wiring chores, and all adjustments are conveniently located on one end of the case.
IMPORTANT: Do not apply power to the unit until you have read the instructions fully and made the required adjustments.
2. INSTALLATION
Voltage 12/24V AC/DC
Current Draw 150mA @ nominal 500mA @ maximum
Response Time 0.3 seconds
Mode Selector via 3 dipswitches
Inputs 7 Dry Contacts, 1 Digital Input
Outputs 5 SPDT Relays, 1 Digital Output
Firmware Verion A1-001
Relay Contact
Rating 3 Amps @ 20 VDC
Time Delays 5 pots, adjustable from 1 to 30 seconds
(depending on mode selected)
Electrical Life 100,000 operations @ rated or
500,000 operations @ 1/2 rated capacity
Mounting
EMF-2: Double-sided foam tape or (2) #6 screws
EMF-2M & EMF-2ABM: 4 x Metal screws &
anchors (provided)
Enclosure EMF-2: Formed Plastic Housing
EMF-2M & EMF-2ABM: Beige Metal Cabinet
Dimensions EMF-2 7” H x 3” W x 7/8” D
(178mm x 76mm x 22mm)
EMF-2M &
EMF-1ABM
12” H x 7-1/2” W x 3-3/4” D
(305mm x 191mm x 95mm)
In addition to the above, Model EMF-2 ABM includes a lockable
metal cabinet to house the relay. The cabinet is equipped with two
lighted push-switches - on to turn the relay power on or off, and the
other to control the DAY/NITE function.
Mounting
The EMF-2 should be mounted in a clean dry location out of direct
contact with the elements. Suitable locations include inside a
metal box, operator header, or above a false ceiling.
If placed on top of a header, ensure that unauthorized personnel
cannot tamper with the unit.
If used in an Airlock or Mantrap application, the relay may be
located at either door location, or, centrally to all doors.
You must bring wiring from all door actuators to this unit
(as well as the lock, operator, and door contact outputs
as appropriate).
The EMF-2 is also available in an attractive lockable metal cabinet
version (EMF-2m or EMF-2ABM), suitable for wall mounting.
Wiring
Wiring of this unit is dependant on the mode desired. Select
your intended application, then proceed to the section indicated.
Note: Do not wire Safety devices to the EMF-2. If installed, wire
your safety device directly to the operator control box.
IMPORTANT: Changes to the Mode and Out2 do not take
effect until a power reset. It is therefore best to make these
adjustments with the power turned off!
NOTE: We highly recommend the use of a regulated power
supply when powering equipment for barrier-free washroom
applications where the strike power may be maintained from
a few minutes to many hours. We offer a low-cost board-only
regulated power supply - CX-PS13 V2, which in turn can be
powered from a small 24VAC transformer, (or the auxiliary power
on the door control) and will supply clean, ltered & regulated
24 VDC power for the strike and EMF-2.

Page 2 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
FILENAME: EMF-2 Diagram 1.ai
DRAWING No: DRG-EMF-2_01
EMF-2 Diagram 1. Electrical and Mechanical
SCALE: NONEDRAWN BY: DGW REVISED: 06/08/2010DATE: 03/24/10
5502 Timberlea Blvd.
Mississauga, Ontario
L4W 2T7
CAMDEN DOOR CONTROLS
RELAY 5 Chart
To have Relay 5
shadow another
relay,set dipswitch
as shown:
NOTE: Pin 2 Connector.
When connecting to Camden Card Reader
in ABM Mode, it is possible to read all cards
by wiring the Blue wire to Pin2, or only
Cards beginning with a 4, 5 & 6 by wiring
the Brown wire (Data) to Pin 2 and the
yellow wire (Clock) to pin 3.
Dip 4
OFF OFF 1
2
3
4
OFF
ON
ON
ON
OFF
ON
Dip 5
=
1
1
5
2
3
4
6
7
8
9
10
11
12
13
14
15
1
5
2
3
4
6
7
1
5
2
3
4
6
7
8
9
10
11
12
13
14
Off / On
1
2
5
7
4
6
3
8
2 3 4 5
LED Output
12V 5V
Power
ON
1
2
EMF-2
1”
(25mm)
2-7/8” (72mm)
6-7/8”
(173mm)
6-13/16”
(160mm)
Side View
Top View
P2
P3
P1
P4
Inputs
Mode
Rel 5
Opt
Relay 1
Timer Settings
Relay ON Indicators
7
6
5
4
3
2
1
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
Relay 2
Relay 3
Relay 4
Relay 5
12/24V
Power
Trouble
Output
Input
Disables
Door #2
Digital
In/Out
Terminal
Strip
Connector
Terminal
Label
Function
1 Power Input
P1 2 Power Input
12/24 Volts AC/DC
Non-polarized
1 Ground
2 Blue (or Brown)
3 N/C (or Yellow)
4 CR Power +5V
5 Orange (output 1)
6 Output 2
P2
7 Ground 2
Card-Reader
Input
(aka - Digital
Connector)
1 Dry 1 Input
2 Dry 1 Input Non-powered Input 1
3 Dry 2 Input
4 Dry 2 Input Non-powered Input 2
5 Dry 3 Input
6 Dry 3 Input Non-powered Input 3
7 Dry 4 Input
8 Dry 4 Input Non-powered Input 4
9 Dry 5 Input
10 Dry 5 Input Non-powered Input 5
11 Dry 6 Input
12 Dry 6 Input Non-powered Input 6
13 Dry 7 Input
P3
14 Dry 7 Input Non-powered Input 7
1 Relay 1 – NC
2 Relay 1 – COM
3 Relay 1 – NO
Form C
4 Relay 2 – NC
5 Relay 2 – COM
6 Relay 2 – NO
Form C
7 Relay 3 – NC
8 Relay 3 – COM
9 Relay 3 – NO
Form C
10 Relay 4 – NC
11 Relay 4 – COM
12 Relay 4 – NO
Form C
13 Relay 5 – NC
14 Relay 5 – COM
P4
15 Relay 5 – NO
Form C

Page 3 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
SECTION 3A - SET-UP INSTRUCTIONS
ABM Vestibule Controller (Mode 1)
EMF-2 is a compact unit designed to interface an automatic
door operator with a card reader and lock system such as those
used on banks. When in “Day Mode” the strike is retracted
(manually/electrically) and the card reader is out of the circuit.
Pressing exterior/interior wall switch activates the door
operator. When EMF-2 is switched to “Night Mode” the electric
strike is energized (door is locked), and the exterior activator
(ie - wall switch) is removed from the circuit. When a valid card
is inserted, the strike unlocks immediately, and the exterior
switch is put back into the circuit for an adjustable period, so
that if pushed by the user, it will open the door automatically.
The inside switch will unlock and open the door at all times.
A new feature of the EMF-2 is the ability to add an “Emergency
- Push-to-Lock” switch near the ATM machine that when
activated “locks out” the card reader input in order to afford
the user extra security. Opening the door from the inside
resets the system (The system will reset automatically after
10 minutes). EMF-2 ABM provides a lockable cabinet to house
the relay, c/w two lighted push-button switches – one to turn
the relay power ON/OFF, the other to select DAY/ NITE modes.
Step 1
Select MODE 1 via the rst 3 positions
of the dip switch as shown:
See Diagram 1 for location of dipswitch,
connectors, & potentiometers.
Step 2 - Dip Switch Options
Push dipswitch #6 ON, for a continuous duty strike, which is
to be energized during “Day Mode”. If using an intermittent
duty strike and/or the latch is to be mechanically retracted
during “Day Mode”, then leave switch #6 OFF.
IMPORTANT: Any changes to Mode selector or Out2 settings
must be made with power off!
Step 3 - Connections
Refer to Diagram 2 for the following connections. Wire all
input connections to the (removable) Input terminal strip
(numbered 1-14). Firmly re-insert connector if removed.
Next, make your wiring connections to the Relay Output
strip (numbered 1–15). Note: Relay 4 is not used in this
application. Re-insert connector.
If you are using this system with our Model #51T2B card reader,
refer to the 7-pin Digital I/O strip, making wiring connections
as per the respective card-reader wiring diagram. If using
model #ECI-210, or another card reader/dry contact - wire
to terminals 1 & 2 of the Digital I/O strip (Re-insert connector
rmly if removed). Connect 12 or 24V AC/DC supply to
terminals 1 & 2 of the 2-pin Power Connector (Terminals are
not polarity sensitive).
Step 4 - Adjustments
In this application, you will use pots #1–4 (Pot 5 has no effect).
Timer 1: Strike Delay-on-Release
Timer 2: Operator Delay-on-Activate
Timer 3: Operator Delay-on-Release
Timer 4: Exterior Switch Enable Time
Apply power to door operator, EMF-2, and any applicable
activating devices (ie – card-reader). Observe the RED
Power LED on the unit. It should be lit. If not, re-conrm
proper voltage connections. Turn key switch (Input #3) to
“Night Mode” (Night mode via an open contact, Day mode
via closed). Activate interior switch. Door should unlock and
open. Adjust potentiometers # 1, 2 & 3 for desired operating
times. Activate exterior switch. Door should remain closed
and locked. Activate the card reader input. The door should
unlock. Adjust Timer 1 for sucient time on the strike.
When card reader is activated, the exterior switch is “put into
the circuit” for a limited time. This time is adjustable from 1 –
30 seconds via pot # 4. Re-activate card reader, and within the
time frame, press the exterior switch. The door should open.
Turn the Key switch (or other switch) to “Day Mode”. If the
strike is to be dogged back mechanically, then do so. If it is to
be powered all day, conrm it is powered and released. Now
the interior and exterior switches will open the door when
activated. The card-reader has no effect on operation (it has
been electronically de-activated).
A new option on the EMF-2 is the provision for an emergency
“Lock Down” switch to be added. This momentary contact
switch only functions in night mode. This test takes two persons
– one to depress the switch inside, and another person outside
to conrm the card-reader input is disabled. Opening the
door from the inside (manually or automatically) resets the
system (N/C magnetic door contact switch required). Once
desired operation is achieved, proceed to Section 4, for
System Inspection Instructions.
3. APPLICATIONS & SET-UP INSTRUCTIONS
ABM Vestibule Control (Mode 1) Proceed to Section 3A - Page 3 2/3 Door Airlock w/ auto-crossing (Mode 5) Proceed to Section 3E - Page 13
1 Door Unsecured Restroom (Mode 2) Proceed to Section 3B - Page 5 2-5 Door Airlock (Mode 6) Proceed to Section 3F - Page 15
1 Door Secured Restroom (Mode 3) Proceed to Section 3C - Page 7 2 Door Man-trap (Mode 7) Proceed to Section 3G - Page 17
2 Door Unsecured Restroom (Mode 4) Proceed to Section 3D - Page 11 System Inspection Instructions - Page 18
Technical Specications and Warranty - Page 19
OFF / ON
1
2
3

Page 4 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
FILENAME: EMF-2 Diagram 2.ai
DRAWING No: DRG-EMF-2_02
EMF-2 Diagram 2. Typical ABM Vestibule Application
SCALE: NONEDRAWN BY: DGW REVISED:DATE: 03/24/10
5502 Timberlea Blvd.
Mississauga, Ontario
L4W 2T7
CAMDEN DOOR CONTROLS
RELAY 5 Chart
To have Relay 5
shadow another
relay,set dipswitch
as shown:
Dip 4
OFF OFF 1
2
3
4
OFF
ON
ON
ON
OFF
ON
Dip 5
=
Relay ON Indicators
Inside
Wall Switch
Outside
Wall Switch
(optional)
Day / Night
Toggle or
Key switch
Emergency
Panic Switch
(optional)
Magnetic Contact Switch
(only required if Panic switch
is utilised)
Fail-Safe Electric Strike Shown
(if Fail-Secure lock is used,
wire to Terminals 1 & 2)
MOV
Wire MOV
(supplied)
directly to strike
or magnet
Power for Strike
N.C.
!
Simple Micro-switch type Card reader
1
Timer Settings
EMF-2
1
5
2
3
4
6
7
8
9
10
11
12
13
14
15
1
5
2
3
4
6
7
1
5
2
3
4
6
7
8
9
10
11
12
13
14
Off / On
1
2
5
7
4
6
3
8
Mode
Rel 5
Opt
2 3 4 5
LED Output
12V 5V
Power
ON
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
C
C
C
C
C
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
1
2
12/24V
Power
Inputs
1
2
3
4
5
6
7
Digital
In/Out
terminal
strip
Output 1
Power +5V
Ground 1
Brown / Blue
Yellow / N/C
Output 2
Ground 2
Mag-stripe style Card reader
or
TO OPEN
PUSH
TO OPEN
PUSH
LOCKED
OUT
12 - 24 V
AC/DC
Power
DAY
NITE
Optional and only if
Panic switch is utilized
Door Operator

Page 5 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
SECTION 3B - SET-UP INSTRUCTIONS
Unsecured Restroom (Mode 2)
This application is a shared-use single (normally unlocked)
restroom door in facilities such as nursing homes, hospitals,
shopping malls, etc. The relay provides control of the lock,
operator, and switches, to provide the utmost in exibility,
safety for the occupants, yet still be easy to install and program.
The door opens automatically by pressing the exterior wall
switch. Once the door has closed, pressing the “Push to Lock”
button inside locks the door – energizing the strike, and
the exterior switch is removed from the circuit. To exit the
restroom, push the interior wall switch. The door unlocks, opens
and resets the system. Should the door be opened manually, the
magnetic contact switch will reset the system.
Unique to the EMF-2 is the emergency input, which allows a
panic button to unlock, open the door (optional), and send an
emergency signal for assistance. The output can be maintained
or pulsed. As an added safety feature, the EMF-2 can be set to
automatically reset (and unlock) after 15 minutes time.
Step 1
Select MODE 2 via the rst 3 positions
of the dip switch as shown:
See Diagram 1 for location of dipswitch,
connectors, & potentiometers.
IMPORTANT: Any changes to Mode selector or Out2 settings
must be made with power off!
Step 2 - Dip Switch Options
Push dipswitch #6 ON for the panic button to unlock and
open the door. Leave switch #6 OFF to enable the panic button
to unlock the door only but not open it.
Push dipswitch #7 ON, to enable the 15 minute time-out
(reset) feature. Leave in OFF position if you do not want an
automatic reset.
Use of Relay 5 is optional, and set according to dipswitches #4
& 5 (See diagram 1 for location). A common use in this mode
would be to have Relay 5 follow the lock relay and light an
occupied sign. By default, Relay #5 follows Relay #1. Dipswitch
# 8 is not used in this mode.
Step 3 - Connections
Refer to Diagram 3 for the following connections.
Wire all input connections to the (removable) Input terminal
strip (numbered 1-14). Firmly re-insert connector if removed.
Next, make your connections to the Relay Output strip
(numbered 1–15) (Relay 3 is not used in this application).
Re-insert connector.
The 7-pin Digital I/O strip provides either 12 VDC or 5 VDC on
Terminals 6 & 7 for lighting an “Occupied” LED. This output is
present whenever the door is locked. Select output voltage
using jumper as shown:
Connect 12 or 24V AC/DC supply to terminals 1 & 2 of the
2-pin Power Connector (Terminals are not polarity sensitive).
SECTION 3C - SET-UP INSTRUCTIONS
Secured Restroom (Mode 3)
This application is a shared-use single (normally locked)
restroom door in facilities such as nursing homes, hospitals,
shopping malls, etc. The relay provides control of the lock,
operator and switches, to provide the utmost in facility security,
safety for the occupants, yet easy to install and program.
In this application the door is normally locked whether
occupied or not. It may be unlocked by Key-switch, keypad, or
another credential. The EMF-2 can be congured to activate
the door operator immediately, or after pressing the wall-
switch within the (adjustable) time period. Once the door
has closed, pressing the “Push to Lock” button removes the
exterior keypad / key-switch from the circuit. The electric lock
will pulse twice to let the user know that the door is secure,
and an output is available to light an Occupied LED(s).
To exit the restroom, push interior wall switch. The door unlocks,
opens and resets the system. Should the door be opened
manually, the magnetic contact switch resets the system.
Unique to the EMF-2 is the emergency input, allowing a
panic button to unlock, open the door (optional) and send
an emergency signal for assistance. The output can be
maintained or pulsed. As an added safety feature, the EMF-2
can be set to automatically reset (and unlock) after
15 minutes time.
Step 1
Select MODE 3 via the rst 3 positions
of the dip switch as shown:
See Diagram 1 for location of dipswitch,
connectors, & potentiometers.
IMPORTANT: Any changes to Mode selector or Out2 settings
must be made with power off!
OFF / ON
1
2
3
OFF / ON
1
2
3

Page 6 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
FILENAME: EMF-2 Diagram 3.ai
DRAWING No: DRG-EMF-2_03
EMF-2 Diagram 3. Single Door Restroom Application (unsecured)
SCALE: NONEDRAWN BY: DGW REVISED: 06/08/10DATE: 03/24/10
5502 Timberlea Blvd.
Mississauga, Ontario
L4W 2T7
CAMDEN DOOR CONTROLS
RELAY 5 Chart
To have Relay 5
shadow another
relay,set dipswitch
as shown:
Dip 4
OFF OFF 1
2
3
4
OFF
ON
ON
ON
OFF
ON
Dip 5
=
Fail-Safe Electric Strike Shown
(if Fail-Secure lock is used,
wire to Terminals 1 & 2)
Wire MOV
(supplied)
directly to strike
or magnet
Power for Strike
Door Operator
Inside
Wall Switch
Outside
Wall Switch
Occupied LED (optional)
Panic switch
(optional)
Inside
Push to Lock
Switch
12 - 24 V
AC/DC
Power
Magnetic
Contact
Switch
MOV
PUSH
TO
LOCK
Optional
Optional OCCUPIED
N.C.
Occupied
Signal
(LED only)
1
Timer Settings
Relay OnIndicators
EMF-2
1
5
2
3
4
6
7
8
9
10
11
12
13
14
15
1
5
2
3
4
6
7
1
5
2
3
4
6
7
8
9
10
11
12
13
14
Off / On
1
2
5
7
4
6
3
8
Mode
Rel 5
Opt
2 3 4 5
LED Output
12V 5V
Power
ON
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
C
C
C
C
C
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
1
2
12/24V
Power
Inputs
1
2
3
4
5
6
7
Digital I/O
terminal
strip
Assistance
Required !
!
TO OPEN
PUSH
TO OPEN
PUSH

Page 7 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
Step 2 - Dip Switch Options
Use of Relay 5 is optional, and set according to dipswitches #4
& 5. Push dipswitch #6 ON when you want the panic button to
unlock and open the door. Leave switch #6 OFF to enable the
Panic button to unlock the door only but not open it.
Push dipswitch #7 ON, to enable the 15 minute time-out
(reset) feature. Leave in OFF position if you do not want an
automatic reset.
Dip switch # 8 can have the keypad unlock and open the door
(OFF) or just unlock the door (ON). If set to ON, an exterior
wall-switch is required to open the door automatically.
Step 3 - Connections
Refer to Diagram 4 for the following connections.
Wire all input connections to the (removable) Input terminal
strip (numbered 1-14). Firmly re-insert connector if removed.
Make your connections to the relay output strip
(numbered 1–15) (Relay 3 is not used in this application).
Re-insert connector.
The 7-pin Digital I/O strip provides either 12 VDC or 5 VDC on
Terminals 6 & 7 for lighting an “Occupied” LED. This output
is present whenever the “Push-to-Lock” switch has been
pressed. Select output voltage using jumper as shown:
Wire the keypad, key-switch or other secure device to
terminals 1 & 2 of this terminal strip. Connect 12 or 24V AC/DC
supply to terminals 1 & 2 of the 2-pin Power Connector
(Terminals are not polarity sensitive).
Step 4 - Adjustments
In this application, you will use pots 1–5.
Timer 1: Strike Delay-on-Release
Timer 2: Operator Delay-on-Activate
Timer 3: Operator Delay-on-Release
Timer 4: Panic Relay (#4) ON time
Timer 5: Panic Relay (#4) OFF time
Note: If pot 5 is turned to zero, relay will be on steady.
Apply power to door operator (EMF-2) and all connected
equipment (strike, lights, etc). Observe the red Power LED on
the unit, which should light. If not, re-conrm proper voltage
and/or terminal strip connection.
Enter keypad, key-switch or other credential to activate EMF-2.
Depending on dipswitch #8, the door will unlock and open
or just unlock. If required, press exterior wall switch. Pot #1
adjusts the lock hold time. Pot #2 adjusts the door hold-open
time (up to 30 seconds). If restroom is occupied and the Lock
button is pressed, the door will not unlock or open.
After entering the restroom, push the Lock button. EMF-2 will
(de)energize the electric lock momentarily to let the occupant
know the door is secure, and remove the exterior inputs from
the circuit.
To exit the Restroom, two options are available:
1. To unlock and open the door automatically, push the
interior wall switch. This also resets EMF-2 for the next
person to use.
2. The door may also be used manually. To exit restroom,
turn the (lever) handle and pull (push) the door open.
The magnet switch resets the unit into standby mode.
Emergency Panic Switch (optional)
Should an emergency occur, and assistance from the outside
is required, the occupant can push a button or ribbon switch
to signal the EMF-2. When activated, the EMF-2 will unlock the
door (and optionally open the door). A maintaining type input
is required to keep the door held open.
Further, Relay #4 is now activated, which can be used to
signal for assistance, sound an alarm – whatever you choose.
The installer can choose a continuous or pulsing output,
depending on the settings of potentiometers #4 & 5.
Emergency Time-out Feature
An added safety feature in the EMF-2 is to automatically reset
to standby mode after a xed lock time of 15 minutes. The
door unlocks, allowing personnel to enter the restroom. This
feature is engaged by turning dipswitch #7 to ON position.
If not desired, simply leave dipswitch 7 OFF.

Page 8 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
FILENAME: EMF-2 Diagram 4.ai
DRAWING No: DRG-EMF-2_04
EMF-2 Diagram 4. Single Door Restroom Application (secured)
SCALE: NONEDRAWN BY: DGW REVISED: 06/08/10DATE: 03/24/10
5502 Timberlea Blvd.
Mississauga, Ontario
L4W 2T7
CAMDEN DOOR CONTROLS
RELAY 5 Chart
To have Relay 5
shadow another
relay,set dipswitch
as shown:
Dip 4
OFF OFF 1
2
3
4
OFF
ON
ON
ON
OFF
ON
Dip 5
=
Fail-Safe Electric Strike Shown
(if Fail-Secure lock is used,
wire to Terminals 1 & 2)
Wire MOV
(supplied)
directly to strike
or magnet
Power for Strike
Occupied LED
(optional)
Inside
Wall Switch
Outside
Wall Switch
(optional)
Panic switch
(optional)
Inside
Push to Lock
Switch
12 - 24 V
AC/DC
Power
Magnetic
Contact
Switch
MOV
PUSH
TO
LOCK
Optional
Optional OCCUPIED
N.C.
Assistance
Required !
!
C
1 2 3
4 5 6
7 8 9
Keypad, or
Card-reader
TO OPEN
PUSH
TO OPEN
PUSH
Occupied
Signal
(LED only)
1
Timer Settings
Relay OnIndicators
EMF-2
1
5
2
3
4
6
7
8
9
10
11
12
13
14
15
1
5
2
3
4
6
7
1
5
2
3
4
6
7
8
9
10
11
12
13
14
Off / On
1
2
5
7
4
6
3
8
Mode
Rel 5
Opt
2 3 4 5
LED Output
12V 5V
Power
ON
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
C
C
C
C
C
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
1
2
12/24V
Power
Inputs
1
2
3
4
5
6
7
Digital
In/Out
terminal
strip
Output
Power +5V
Ground
Input
N/C
Door Operator

Page 9 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
SECTION 3D - SET-UP INSTRUCTIONS
2-Door Restroom (Mode 4)
This application is a shared-use (normally unlocked) restroom
between two suites (utilizing two doors), in facilities such as
nursing homes & hospitals, etc. The relay provides control of
both locks, operators, and all switches, to provide the utmost
in exibility, safety for the occupants, and be easy to install
and program.
Either door is opened automatically by pressing the respective
exterior wall switch. Once the door has closed, pressing either
“Push to Lock” button inside locks both doors – the strike is
energized, and exterior switches are removed from the circuit.
To exit the restroom, push either interior wall switch. The
respective door unlocks, opens and resets the system. Should
either door be opened manually, the magnetic contact switch
will reset the system.
Unique to the EMF-2 is the emergency input, which allows a
panic button to unlock, open (one or both) door(s), (optional),
and send an emergency signal for assistance. The output can
be maintained or pulsed. As an added safety feature, the
EMF-2 can be set to automatically reset (and unlock) after
15 minutes time.
Utilizing the dry contact output (Relay #5) or the LED output is
strongly encouraged to indicate “Occupied” on the exterior of
both doors to let others know the restroom is in use.
Step 1
Select MODE 4 via the rst 3 positions
of the dip switch as shown:
See Diagram 1 for location of dipswitch,
connectors, & potentiometers.
IMPORTANT: Any changes to Mode selector or Out2 settings
must be made with power off!
Step 2 - Dip Switch Options
Leave switch #6 OFF to enable the panic button to unlock the
door only, but not open it. Put dipswitch #6 ON when you
want the panic button to unlock the door and also open it.
Furthermore, if dipswitch #6 is set to ON, and dipswitch #8
is set to OFF, then only the last door used will open. Setting
dipswitch #8 ON, will open both doors simultaneously.
Push dipswitch #7 ON, to enable the 15 minute Time-out
(reset) feature. Leave in OFF position if you do not want an
automatic reset.
Use of Relay 5 is optional, and set according to dipswitches
#4 & 5 (See diagram 1 for location). A common use in this
mode would be that Relay 5 follows the lock relay and lights
an occupied sign. It could also be utilized for the second door
lock, rather than connecting both door locks to Relay #1
output. By default, Relay #5 follows Relay #1.
Step 3 - Connections
Refer to Diagram 5 for the following connections. Wire all
input connections to the (removable) Input terminal strip
(numbered 1-14). Firmly re-insert connector if removed.
Make your connections to the relay output strip (numbered
1–15). Both door locks may be connected to Relay #1 or, wire
one lock to Relay #1 and the other to Relay #5.
Re-insert connector.
The 7-pin Digital I/O strip provides either 12 VDC or 5 VDC on
Terminals 6 & 7 for lighting “Occupied” LED’s. This output is
present whenever the door is locked. Select output voltage
using jumper as shown:
Connect 12 or 24V AC/DC supply to terminals 1 & 2 of the
2-pin Power Connector (Terminals are not polarity sensitive).
Step 4 - Adjustments
In this application, you will use pots 2–5. Pot #1 has no effect.
Timer 2: Operator Delay-on-Activate
Timer 3: Operator Delay-on-Release
Timer 4: Panic Relay (#4) ON time
Timer 5: Panic Relay (#4) OFF time
Note: If pot 5 is turned to zero, relay will be on steady.
Apply power to door operators (EMF-2) and all connected
equipment (strikes, lights, etc). Observe the red Power LED on
the unit, which should light. If not, re-conrm proper voltage
and/or terminal strip connection.
Press the exterior wall switch at door #1. If restroom is
unoccupied the door will open automatically. Pot #2 adjusts
the door hold-open time (up to 30 seconds). If restroom is
occupied and the Lock button has been pressed, the door will
not open (an Occupied light would be lit).
After entering the restroom, push the nearest Lock button.
The EMF-2 will energize both electric locks and remove both
exterior Push switches from the circuit.
To exit the Restroom, two options are available:
1. To have the door unlock and open automatically, push
the respective interior wall switch. This also resets the EMF-2
for the next person to use.
2. The door may also be used manually. To exit the
restroom, turn the (lever) handle and pull (push) the door
open. The magnet switch resets the unit into standby
mode. The Occupied lights / LED’s will extinguish.
Repeat the above procedure door #2.
It should function exactly as above.
OFF / ON
1
2
3

Page 10 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
FILENAME: EMF-2 Diagram 5.ai
DRAWING No: DRG-EMF-2_05
EMF-2 Diagram 5. 2 Door (shared) Restroom Application
SCALE: NONEDRAWN BY: DGW REVISED: 06/08/10DATE: 03/24/10
5502 Timberlea Blvd.
Mississauga, Ontario
L4W 2T7
CAMDEN DOOR CONTROLS
RELAY 5 Chart
To have Relay 5
shadow another
relay,set dipswitch
as shown:
Dip 4
OFF OFF 1
2
3
4
OFF
ON
ON
ON
OFF
ON
Dip 5
=
Fail-Safe Electric
Strike Shown
(if Fail-Secure lock
is used, wire to
Terminals 1 & 2)
Inside
Push to Lock
Switch
(If 2 are used,
wire in parallel)
Occupied LED
(optional)
Inside
Wall Switch
Door #1
Outside
Wall Switch
Door #1
Panic switch
(optional)
12 - 24 V
AC/DC
Power
Magnetic Contact Switch
on both doors. Wire in series.
PUSH
TO
LOCK
Door #1 Lock
Optional
N.C.
Assistance
Required !
!
TO OPEN
PUSH
TO OPEN
PUSH
Power for Locks
Door #2 Lock
TO OPEN
PUSH
TO OPEN
PUSH
Inside
Wall Switch
Door #2
Outside
Wall Switch
Door #2
Occupied
Signal
(LED only)
1
Timer Settings
Relay OnIndicators
EMF-2
1
5
2
3
4
6
7
8
9
10
11
12
13
14
15
1
5
2
3
4
6
7
1
5
2
3
4
6
7
8
9
10
11
12
13
14
Off / On
1
2
5
7
4
6
3
8
Mode
Rel 5
Opt
2 3 4 5
LED Output
12V 5V
Power
ON
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
C
C
C
C
C
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
1
2
12/24V
Power
Inputs
1
2
3
4
5
6
7
Digital
In/Out
terminal
strip
Door #1 Operator
Door #2 Operator

Page 11 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
Emergency Panic Switch (optional)
Should an emergency occur, and assistance from the outside
is required, the occupant can push a button or ribbon switch to
signal the EMF-2 (input #3). When activated, the EMF-2
will unlock the door (and optionally open the door). A
maintaining type input is required to keep the door held open.
Based on the settings of Dipswitch #6 & 8 either the doors will
unlock only, or the last door used will open or, both doors will
unlock and open simultaneously.
Relay #4 is now activated, which can be used to signal for
assistance, sound an alarm – whatever you choose. The
installer can choose a continuous or pulsing output, depending
on the settings of potentiometers #4 & 5.
Emergency Time-out Feature
An added safety feature in the EMF-2 is the ability to
automatically reset to standby mode after a xed lock time of
15 minutes. The door unlocks, so that personnel may enter
the restroom. This feature is engaged by turning dipswitch #7
to ON position. If not desired, simply leave dipswitch 7 OFF.
SECTION 3E - SET-UP INSTRUCTIONS
2/3 Door Airlock (Mode 5)
This is designed to control up to 3 sets of sliding, or swinging
doors. The relay allows only 1 door to be open at a time.
It accomplishes this by a Door Sense input, such as a
magnetic contact switch, located at each door. If the Door
Sense determines that a door is open, it will not allow a
second door to open, but remembers the request to open
and allows it once the rst door has closed.
For 2-door airlocks, the installer can set up “Auto-crossing”
whereby after triggering one door, the second door activates
after the rst door closes (also known as bi-directional
door sequencing).
Should a door become stuck open, a Trouble signal is output
after 5 minutes. The EMF-2 also includes a “Lock-down” input
that resets the system and/or disables all “Open” requests.
Step 1
Select MODE 5 via the rst 3 positions
of the dip switch as shown:
See Diagram 1 for location of dipswitch,
connectors, & potentiometers.
Step 2 - Dip Switch Options
Use of Relay 5 is optional, and set according to dipswitches
#4 & 5. Push switch #6 ON for “Auto Mode” (door sequencing).
In this Mode when input A is activated, rst door A opens,
then when closed again, door B opens in sequence.
Conversely, when input B is activated, rst door B opens, then
when it is closed again, door A opens sequentially. A third
door cannot be used in “Auto-Mode”. Selecting this mode
disables door C input and contact input.
Set dipswitch #7 ON for airlocks containing 2 doors only, or set
to OFF for 3 doors. Dipswitch #8 has no effect in this mode.
IMPORTANT: Any changes to Mode selector or Out2 settings
must be made with power off!
Step 3 - Connections
Refer to Diagram 6 for the following connections.
Wire all input connections to the (removable) Input terminal
strip (numbered 1-14). Firmly re-insert connector if removed.
NOTE: Magnetic contact switches: This system wants to
see a Normally Closed connection when the door is closed.
The contact will open when the door opens. Any other
conguration will cause the relay to malfunction. We suggest
standard door contacts (ie.Camden Model #CX-MDC).
Make your connections to the relay output strip (numbered
1–15). The 7-pin Digital I/O strip provides a trouble output on
pins 6 & 7 after 5 minutes of door ajar.
Connect 12 or 24V AC/DC supply to terminals 1 & 2 of the
2-pin Power Connector (Terminals are not polarity sensitive).
Step 4 - Adjustments
In this application, you will use pots 1–3 & 5.
Pot 4 is not used in this mode.
Timer 1: Door A Delay-on-Release
Timer 2: Door B Delay-on-Release
Timer 3: Door C Delay-on-Release
Timer 4: Not used
Timer 5: Timer for clearing "walk-aways"
Apply power to door operators (EMF-2), and all connected
equipment (strikes, lights, etc). Observe the red Power LED on
the unit, which should light. If not, re-conrm proper voltage
and/or terminal strip connection.
Activate an input device to one of the doors. Observe the
respective output LED, which should light immediately. The
door should unlock and/or open.
If a request to open comes in from another door while the
rst is still open, it will retain the call in memory until the
Door Sense switch indicates the rst has closed. If there is
a succeeding request on the rst door (or the door that is
already opened), it will keep that door opened.
If automatic sequential operation between doors A and B is
desired, put dipswitch #6 into ON position. Otherwise, for
normal operation, leave this dipswitch off.
Potentiometer #5 is useful if the application utilizes locks only,
and not automatic door operators.
OFF / ON
1
2
3

Page 12 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
FILENAME: EMF-2 Diagram 6.ai
DRAWING No: DRG-EMF-2_06
EMF-2 Diagram 6. 2-3 Door Airlock Application
SCALE: NONEDRAWN BY: DGW REVISED:DATE: 03/24/10
5502 Timberlea Blvd.
Mississauga, Ontario
L4W 2T7
CAMDEN DOOR CONTROLS
RELAY 5 Chart
To have Relay 5
shadow another
relay,set dipswitch
as shown:
Dip 4
OFF OFF 1
2
3
4
OFF
ON
ON
ON
OFF
ON
Dip 5
=
12 - 24 V
AC/DC
Power
N.C.
TO OPEN
PUSH
TO OPEN
PUSH
TO OPEN
PUSH
N.C.
N.C.
1
Timer Settings
Relay OnIndicators
EMF-2
1
5
2
3
4
6
7
8
9
10
11
12
13
14
15
1
5
2
3
4
6
7
1
5
2
3
4
6
7
8
9
10
11
12
13
14
Off / On
1
2
5
7
4
6
3
8
Mode
Rel 5
Opt
2 3 4 5
LED Output
12V 5V
Power
ON
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
C
C
C
C
C
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
1
2
12/24V
Power
Inputs
1
2
3
4
5
6
7
Digital
In/Out
terminal
strip
LOCK
OFF
Trouble
Door A Operator
Door A Switch
Door B Switch
Door C Switch
Door Contact A
Door Contact B
Door Contact C
Input 7 causes
all doors to lock
immediately
Trouble output after 5 minutes of door ajar.
Select 5V or 12V output with jumper.
Door B Operator
Door C Operator

Page 13 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
Should a person approach a door and request the door to
unlock, then change his/her mind and “walk-away”, pot #5 can
be set to ignore that request after an adjustable time. This
time would be set at or close to minimum. For automatic door
applications, it could be set higher (10–15 seconds.)
Switch closure on Input #7 will cause all doors to lock
immediately, regardless of pending “open” requests. Once the
desired operation is achieved, proceed to Section 4, System
Inspection Instructions.
SECTION 3F - SET-UP INSTRUCTIONS
2-5 Door Airlock (Mode 6)
This function is designed to control up to 5 sets of sliding, or
swinging doors. The relay will allow only 1 door to be open
at a time. It accomplishes this by a Door Sense input, such
as a magnetic contact switch, located at each door. If the
Door Sense determines that a door is open, it will not allow
a second door to open, but remembers the request to open
and allows it once the rst door has closed.
Should a door become stuck open, a Trouble signal is output
after 5 minutes, and may be reset with Input #7.
Step 1
Select MODE 6 via the rst 3 positions
of the dip switch as shown:
See Diagram 1 for location of dipswitch,
connectors, & potentiometers.
Step 2 - Dip Switch Options
There are no dip switch options with this mode.
Since all door contacts are wired in series and connected to
Input #6, the unit does not care if less than 5 doors are used.
IMPORTANT: Any changes to Mode selector or Out2 settings
must be made with power off!
Step 3 - Connections
Refer to Diagram 7 (page 14) for the following connections.
Wire all input connections to the (removable) Input terminal
strip (numbered 1-14). Firmly re-insert connector if removed.
NOTE: Magnetic contact switches: This system wants to
see a Normally Closed connection when the door is closed.
The contact will then open when the door opens. Any other
conguration will cause the relay to malfunction. We suggest
standard door contacts (ie. Camden Model #CX-MDC). Wire all
contacts in series as shown in the diagram.
Make your connections to the relay output strip (numbered
1–15). The 7-pin Digital I/O strip provides a trouble output on
pins 6 & 7 after 5 minutes of door ajar.
Connect 12 or 24V AC/DC supply to terminals 1 & 2 of the
2-pin Power Connector (Terminals are not polarity sensitive).
Step 4 - Adjustments
In this application, you will use pots 1 & 5.
Pot 2 - 4 are not used in this mode.
Timer 1: All Doors Delay-on-Release
Timer 2: Not used
Timer 3: Not used
Timer 4: Not used
Timer 5: Timer for clearing "walk-aways"
Apply power to door operators (EMF-2) and all connected
equipment (strikes, lights, etc). Observe the red Power LED on
the unit, which should light. If not, re-conrm proper voltage
and/or terminal strip connection.
Activate an input device to one of the doors. Observe the
respective output LED, which should light immediately. The
door should unlock and/or open.
If a request to open comes in from another door while the
rst is still open, it will retain the call in memory until the
Door Sense switch indicates the rst has closed. If there is
a succeeding request on the rst door (or the door that is
already opened) it will keep that door opened.
Potentiometer #5 is useful if the application utilizes locks only,
and not automatic door operators. Should a person approach
a door and request the door to unlock, but then change his/her
mind and “walk-away”, pot #5 can be set to ignore that request
after an adjustable time. Typically this time would be set at or
close to minimum. For automatic door applications it could be
set higher (10–15 seconds).
Once the desired operation is achieved, proceed to Section 4,
System Inspection Instructions.
SECTION 3G - SET-UP INSTRUCTIONS
2 Door Mantrap (Mode 7)
This function is designed to control a 2-door mantrap with or
without automatic door operators. The relay will allow only 1
door to be open at a time.
It accomplishes this by a Door Sense input, such as a
magnetic contact switch, located at each door. If the Door
Sense determines that a door is open, it will not allow a
second door to open, but remembers the request to open
and allows it once the rst door has closed (the memory
feature may be disabled).
An input is available for a contact mat on the oor to ensure
that only one person is within the mantrap at any time.
Should a door become stuck open, a Trouble signal is output
after 5 minutes. A “Lock-down” input is available which
immediately locks all doors and disables further egress/ingress.
OFF / ON
1
2
3

Page 14 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
FILENAME: EMF-2 Diagram 7.ai
DRAWING No: DRG-EMF-2_07
EMF-2 Diagram 7. 2-5 Door Airlock Application
SCALE: NONEDRAWN BY: DGW REVISED:DATE: 03/24/10
5502 Timberlea Blvd.
Mississauga, Ontario
L4W 2T7
CAMDEN DOOR CONTROLS
Door 5 Switch
Door 4 Switch
Door 3 Switch
Door 2 Switch
Door 1 Switch
Door 1 Contact Door 2 Contact Door 3 Contact
Door 4 Contact
Clear
Trouble
Switch
Door 5 Contact
Power for Strike
Power for Strike
Power for Strike
Power for Strike
Power
for Strike
Trouble output after 5 minutes of door ajar.
Select 5V or 12V output with jumper.
12 - 24 V
AC/DC
Power
Trouble
1
Timer Settings
Relay On Indicators
EMF-2
1
5
2
3
4
6
7
8
9
10
11
12
13
14
15
1
5
2
3
4
6
7
1
5
2
3
4
6
7
8
9
10
11
12
13
14
Off / On
1
2
5
7
4
6
3
8
Mode
Rel 5
Opt
2 3 4 5
LED Output
12V 5V
Power
ON
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
C
C
C
C
C
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
1
2
12/24V
Power
Inputs
1
2
3
4
5
6
7
Digital
In/Out
terminal
strip
TO UNLOCK
PUSH
TO UNLOCK
PUSH
TO UNLOCK
PUSH
TO UNLOCK
PUSH
TO UNLOCK
PUSH
N.C. N.C.
N.C. N.C.
N.C.

Page 15 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
Step 1
Select MODE 7 via the rst 3 positions
of the dip switch as shown:
See Diagram 1 for location of dipswitch,
connectors, & potentiometers.
Step 2 - Dip Switch Options
Use of Relay 5 is optional, and set according to dipswitches
#4 & 5. Push switch #6 ON to disable the memory feature. If
left OFF, the EMF-2 will remember a request to open and open
that door when the other door has re-closed and locked.
Dipswitches #7 & 8 are not used in this mode.
IMPORTANT: Any changes to Mode selector or Out2 settings
must be made with power off!
Step 3 - Connections
Refer to Diagram 8 for the following connections.
Wire all input connections to the (removable) Input terminal
strip (numbered 1-14). Firmly re-insert connector if removed.
NOTE: Magnetic contact switches: This system wants to
see a Normally Closed connection when the door is closed.
The contact then opens when the door opens. Any other
conguration will cause the relay to malfunction. We suggest
standard door contacts (ie. Camden Model #CX-MDC).
Make your connections to the relay output strip
(numbered 1–15).
The 7-pin Digital I/O strip provides a trouble output on pins
6 & 7 after 5 minutes of door ajar. If utilizing an electric oor
mat, wire to pins 1 & 2 (This input should be normally open).
Connect 12 or 24V AC/DC supply to terminals 1 & 2 of the
2-pin Power Connector (Terminals are not polarity sensitive).
Step 4 - Adjustments
In this application, you will use pots 1,2,3 & 5.
Pot 4 is not used in this mode.
Timer 1: Door Lock Delay-on-Release
Timer 2: Operator Delay-on-Activate
Timer 3: Operator Delay-on-Release
Timer 4: Not used
Timer 5: Timer for clearing "walk-aways"
Apply power to door operators (EMF-2) and all connected
equipment (strikes, lights, etc). Observe the red Power LED on
the unit, which should light. If not, re-conrm proper voltage
and/or terminal strip connection.
Activate an input device to one of the doors. Observe the
respective output LED, which should light immediately.
The door should unlock and/or open.
If a request to open comes in from another door while the
rst is still open, it will retain the call in memory until the
Door Sense switch indicates the rst has closed. If there is
a succeeding request on the rst door (or the door that is
already opened) it will keep that door opened. This memory
feature can be disabled by setting dipswitch #6 ON.
Potentiometer #5 is useful if the man-trap utilizes locks only,
and not automatic door operators. Should a person approach
a door and request the door to unlock, but then change his/
her mind and “walk-away”, pot #5 can be set to ignore that
request after an adjustable time. Typically this time would be
set at or close to minimum. For automatic door applications it
could be set higher (5–10 seconds.)
Once the desired operation is achieved, proceed to Section 4,
System Inspection Instructions.
SECTION 4 - SYSTEM INSPECTION INSTRUCTIONS
After the installation and operational check of the system:
1. Place warning label on the door (as per ANSI A156.10 or
A156.19 guidelines). This will advise the person entering
the swing side zone that the door will move.
2. Instruct the owner on door system operation and how to
test it. This should be checked on a daily basis.
3. Instruct the owner on what to do if the door or any of it's
components become damaged.
4. Strongly recommend to the owner that the complete entry
be inspected twice a year as part of the service agreement.
SECTION 5 - WARRANTY
Camden Door Controls guarantees the EMF-2 (or EMF-2m /
EMF-2ABM) to be free from manufacturing defects for 3 years
from date of sale. If during the rst 3 years the CX-EMF-2
/ EMF-2ABM) fails to perform correctly, it may be returned
to our factory where it will be repaired or replaced (at our
discretion) without charge. Except as stated herein, Camden
extends no warranties expressed or implied regarding
function, performance or service.
OFF / ON
1
2
3

Page 16 of 16
CX-EMF-2 MULTI-FUNCTION TIMER
INSTALLATION INSTRUCTIONS
FILENAME: EMF-2 Diagram 8.ai
DRAWING No: DRG-EMF-2_08
EMF-2 Diagram 8. 2 Door Mantrap Application
SCALE: NONEDRAWN BY: DGW REVISED: 05/04/11DATE: 03/24/10
5502 Timberlea Blvd.
Mississauga, Ontario
L4W 2T7
CAMDEN DOOR CONTROLS
Power for Lock
Power for Lock
Normally Open input will disable Door #2
Common device is a specially constructed
electric switch mat
RELAY 5 Chart
To have Relay 5
shadow another
relay,set dipswitch
as shown:
Dip 4
OFF OFF 1
2
3
4
OFF
ON
ON
ON
OFF
ON
Dip 5
=
Inside
Wall Switch
Door #1
12 - 24 V
AC/DC
Power
Door #1 Lock
TO OPEN
PUSH
Door #2 Lock
TO OPEN
PUSH
Inside
Wall Switch
Door #2
LOCK
DOWN N.C.
N.C.
Trouble
Trouble output after 5
minutes of door ajar.
Select 5V or 12V
output with jumper
STEP
HERE
ONLY
Trouble
Output
1
Timer Settings
Relay OnIndicators
EMF-2
1
5
2
3
4
6
7
8
9
10
11
12
13
14
15
1
5
2
3
4
6
7
1
5
2
3
4
6
7
8
9
10
11
12
13
14
Off / On
1
2
5
7
4
6
3
8
Mode
Rel 5
Opt
2 3 4 5
LED Output
12V 5V
Power
ON
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
C
C
C
C
C
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
1
2
12/24V
Power
Inputs
1
2
3
4
5
6
7
Digital
In/Out
terminal
strip
Input
disables
Door #2
Fail-Secure Electric Strike Shown
(if Fail-Safe lock is used, wire to
Terminals 1 & 2, and 7 & 8)
Door #1 Operator
Card Reader
Door #1
Card Reader
Door #2
Magnetic
Contact
Switch
Door #1
Magnetic
Contact
Switch
Door #2
Lock Down
Switch Disables
Both Door Inputs
Door #2 Operator
This manual suits for next models
2
Table of contents
Other CAMDEN Timer manuals