
CAREL INDUSTRIES - HQs
Via dell’Industria, 11 – 35020 Brugine – Padova (Italy)
Tel. (+39) 0499716611 – Fax (+39) 0499716600
H0 Serial address MSYF - C 0 207 1
H1 Function of AUX1
0: Alarm output usually energised
1: Alarm output usually de-energised
2: Auxiliary output
3: Light output
4: Auxiliary evaporator defrost output
5: Pump down valve output
6: Condenser fan output
7: Delayed compressor output
8: Auxiliary output with deactivation when OFF
9: Light output with deactivation when OFF
10: No function associated with the output
11: Reverse output in control with dead band
12. Second compressor step output
13: Second compressor step output with
rotation
MSYF flag C 0 13 1
3
H2 Disable keypad/IR
Parameter “H2”
LIGHT
ON/OFF
AUX
HACCP
PRG/MUTE (mute)
UP/CC
DOWN/DEF
SET
Parameter F modification
Set point modification
Remote control modif.
0 • •
1
2 • • •
3 •
4 • • • •
5 • • • • •
6 • • • •
Keypad function “•” = Disabled
MSYF flag C 0 6 1
H3 Remote control enabling code MSYF - C 0 255 0
H4 Disable buzzer
0: Buzzer enabled 1: Buzzer disabled
MSYF flag C 0 1 0
H6 Lock keypad MSYF - C 0 255 0
H8 Select activation of output with time band
0: Time band linked to output config. for light
1: Time band linked to output con for aux
MSYF flag C 0 1 0
H9 Enable set point variation with time band
0: Set point variation with time band disabled
1: Set point variation with time band enabled
MSYF flag C 0 1 0
Hdh Anti-sweat heater offset MSYF °C/°F C -50 200 0.0
HAn Number of HA events recorded MSYF - C 0 15 0
HA
y__
M__
d__
h__
n__
t__
Date/time of last HA event
Year
Month
Day
Hour
Minute
Duration
MSYF -
years
months
days
hours
min.
ore
C -
0
1
1
0
0
0
-
99
12
7
23
59
99
0
0
0
0
0
0
HA1 Date/time of penultimate HA event MSYF - C - - -
HA2 Date/time of third-to-last HA event MSYF - C - - -
HFn Number of HF events recorded MSYF - C 0 15 0
HF
y__
M__
d__
h__
n__
t__
Date/time of last HF event
Year
Month
Day
Hour
Minute
Duration
MSYF -
years
months
days
hours
min.
ore
C -
0
1
1
0
0
0
-
99
12
7
23
59
99
-
0
0
0
0
0
0
HF1 Date/time of penultimate HF event MSYF - C - - -
HF2 Date/time of third-to-last HF event MSYF - C 0 - -
Htd HACCP alarm delay MSYF min C 0 250 0
td1
d__
h__
n__
Defrost time band 1
Day
Hour
Minute
SYF -
days
hours
min.
C -
0
0
0
-
11
23
59
-
0
0
0
td2 ...
td8
Defrost time band 2...8 SYF - C - - -
ton Light/aux on time band / set point varance SYF - C - - -
d__ Day days 0 11 0
h__ Hour hours 0 23 0
n__ Minute min. 0 59 0
toF Light/aux off time band / set point varance SYF - C - - -
d__ Day days 0 11 0
h__ Hour hours 0 23 0
n__ Minute min. 0 59 0
tc RTC date/time setting MSYF - C - - -
y__ Year years 0 0 99 0
M__ Mese months 1 1 12 1
d__ Day of the month days 1 1 31 1
u__ Day of the week days 1 1 7 6
h__ Hour hours 0 0 23 0
n__ Minute min. 0 0 59 0
Tab. 5
Important: for the set times to become immediately operational, the instrument must be turned off
and on again, otherwise the timers will become operational when the instrument is next started,
during the setting of the internal timers.
Table of alarms and signals: display, buzzer and relay
The following table describes the alarms and the signals on the controller, with the corresponding
description, status of the buzzer, the alarm relay and the reset mode.
Code Icon on
the display
Alarm
relay Buzzer Reset Description
‘rE’ flashing active active automatic virtual control probe fault
‘E0’ flashing OFF OFF automatic room probe S1 fault
‘E1’ flashing OFF OFF automatic defrost probe S2 fault
‘E2’-3-4 flashing OFF OFF automatic probes S3-4-5 fault
‘___’ no OFF OFF automatic probe not enabled
‘LO’ flashing active active automatic low temperature alarm
‘HI’ flashing active active automatic high temperature alarm
‘AFr’ flashing active active manual antifreeze alarm
‘IA’ flashing active active automatic immediate alarm from external contact
‘dA’ flashing active active automatic delayed alarm from external contact
‘dEF’ acceso OFF OFF automatic defrost running
‘Ed1’-2 no OFF OFF autom./man. defrost on evaporator 1 and 2 ended by timeout
‘Pd’ flashing active active autom./man. maximum time pump-down alarm
‘LP’ flashing active active autom./man. low pressure alarm
‘AtS’ flashing active active autom./man. autostart in pump-down
‘cht’ nessuna OFF OFF autom./man. high condenser temperature pre-alarm
‘CHT’ flashing active active manual high condenser temperature alarm
‘dor’ flashing active active automatic door open for too long alarm
‘Etc’ flashing OFF OFF autom./man. real time clock fault
‘EE’ flashing OFF OFF automatic EEPROM error, unit parameters
‘EF’ flashing OFF OFF automatic EEPROM error, operating parameters
‘HA’ flashing OFF OFF manual HACCP alarm, type ‘HA’
‘HF’ flashing OFF OFF manual HACCP alarm, type ‘HF’
‘rCt’ Signal Instrument enabled for programming from the
remote control
‘A d d ’ Signal Automatic address assignment procedure in
progress
‘Prt’ Signal Printing report
‘LrH’ Signal Activation of the of low relative humidity
procedure
‘HrH’ Signal Activation of the of high relative humidity
procedure
‘ccb’ Signal Request to start continuous cycle
‘ccE’ Signal Request to end continuous cycle
‘d Fb’ Signal Request to start defrost
‘dFE’ Signal Request to end defrost
‘On’ Signal Switch ON
‘OFF’ Signal Switch OFF
‘rES’ Signal Reset alarms with manual reset Reset HACCP
alarms Reset temperature monitoring
‘n1’...‘n6’ flashing active active automatic Indicates an alarm on unit 1 to 6 present in the
network
‘dnL’ Signal signals download in progress
‘d1’...‘d6’ flashing OFF OFF Signals download with errors on unit 1 to 6
Tab. 6
The buzzer is enabled if enabled by the parameter‘H4’. The alarm relay is enabled if one of the auxilia-
ry outputs, AUX1 (H1) or AUX2 (H5) has been assigned the alarm relay function (normally energised
or normally di-energised). Note: the buzzer can be disabled by the CAREL Supervision System.
Disposal of the product
The appliance (or the product) must be disposed of separately in compliance with the local
standards in force on waste disposal.
IMPORTANT WARNINGS: The CAREL product is a state-of-the-art device, whose operation is
specified in the technical documentation supplied with the product or can be downloaded,
even prior to purchase, from the website www.carel.com.
he customer (manufacturer, developer or installer of the final equipment) accepts all liability
and risk relating to the configuration of the product in order to reach the expected results in relation
to the specific installation and/or equipment. The failure to complete such phase, which is required/
indicated in the user manual, may cause the final product to malfunction; CAREL accepts no liability
in such cases. The customer must use the product only in the manner described in the documenta-
tion relating to the product. The liability of CAREL in relation to its products is specified in the CAREL
general contract conditions, available on the website www.carel.com and/or by specific agreements
with customers.
Date and day for defrost event (parameters td1...td8)
0= no event; 1...7= Monday...Sunday; 8= from Monday to Friday; 9= from Monday to Saturday; 10=
from Saturday to Sunday; 1= every day.
Summary of operating parameters
UOM = Unit of measure; Def. = Default value.
Symb. Code Parameter Models UOM Type Min Max Def.
Pw Password MSYF - C 0 200 22
/2 Measurement stability MSYF - C 1 15 4
/3 Probe display response MSYF - C 0 15 0
/4 Virtual probe MSYF - C 0 100 0
/5 Select °C or °F MSYF flag C 0 1 0
/6 Display decimal point
0: with tenths of a
degree
1: without tenths of a
degree
MSYF flag C 0 1 0
/tI Display decimal point
1: virtual probe 2: probe 1
3: probe 2 4: probe 3
5: probe 4 6: probe 5
7: set point
MSYF - C 1 7 1
/tE Display on external terminal
0: remote terminal not present
1: virtual probe 2: probe 1
3: probe 2 4: probe 3
5: probe 4 6: probe 5
MSYF - C 0 6 0
/P Select type of probe
0: NTC standard with range -50T90 °C
1: NTC enhanced with range -40T150 °C
2: PTC standard with range -50T150 °C
MSYF - C 0 2 0
/A2 Configuration of probe 2 (S2)
0: Probe absent
1: Product probe (display only)
2: Defrost probe
3: Condenser probe
4: Antifreeze probe
YF
MS
-
-
C
C
0
0
4
4
2
0
/A3 Configuration of probe 3 (S3, DI1) As for /A2 MSYF - C 0 3 0
/A4 Configuration of probe 4 (S4, DI2) As for /A2 MSYF - C 0 3 0
/A5 Configuration of probe 5 (S5, DI3) As for /A2 MSYF - C 0 3 0
/c1 Calibration of probe 1 MSYF °C/°F C -20 20 0.0
/c2 Calibration of probe 2 MSYF °C/°F C -20 20 0.0
/c3 Calibration of probe 3 MSYF °C/°F C -20 20 0.0
/c4 Calibration of probe 4 MSYF °C/°F C -20 20 0.0
St Temperature set point MSYF °C/°F F r1 r2 0.0
rd Control delta SYF °C/°F F 0.1 20 2.0
rn Dead band SYF °C/°F C 0.0 60 4.0
rr Reverse differential for control with dead band SYF °C/°F C 0.1 20 2.0
r1 Minimum set point allowed MSYF °C/°F C -50 r2 -50
r2 Maximum set point allowed MSYF °C/°F C r1 200 60
r3 Operating mode
0: Direct (cooling) with defrost control
1: Direct (cooling)
2: Reverse-cycle (heating)
SYF flag C 0 2 0
r4 Automatic night-time set point variation MSYF °C/°F C -20 20 3.0
r5 Enable temperature monitoring
0: Disabled 1: Enabled
MSYF flag C 0 1 0
rt Temperature monitoring interval MSYF ore F 0 999 -
rH Maximum temperature read MSYF °C/°F F - - -
rL Minimum temperature read MSYF °C/°F F - - -
c0 Comp., fan and AUX delay on start-up in SYF min C 0 15 0
c1 Minimum time between successive starts SYF min C 0 15 0
c2 Minimum compressor OFF time SYF min C 0 15 0
c3 Minimum compressor ON time SYF min C 0 15 0
c4 Duty setting SYF min C 0 100 0
cc Continuous cycle duration SYF ore C 0 15 0
c6 Alarm bypass after continuous cycle SYF ore C 0 250 2
c7 Maximum pump down time SYF s C 0 900 0
c8 Comp. start delay after open PD valve
(factory default= 0, not visible from display)
SYF s C 0 60 5
c9 Enable autostart function in PD SYF flag C 0 1 0
c10 Select Pump down by time or pressure
0: Pump down by pressure
1: Pump down by time
SYF flag C 0 1 0
c11 Second compressor delay SYF s C 0 250 4
d0 Type of defrost SYF
0: Electric heater defrost by temperature
1: Hot gas defrost by temperature
2: Electric heater defrost by time
3: Hot gas defrost by time
4: Electric heater defrost thermostat by time
SYF flag C 0 4 0
dI Interval between defrosts SYF ore F 0 250 8
dt1 End defrost temperature, evaporator SYF °C/°F F -50 200 4.0
dt2 End defrost temperature, aux evap. SYF °C/°F F -50 200 4.0
dP1 Maximum defrost duration, evaporator SYF min F 1 250 30
dP2 Maximum defrost duration, aux evap SYF min F 1 250 30
d3 Defrost start delay SYF min C 0 250 0
d4 Enable defrost on start-up
0: No defrost is performed when the
instrument is switched on
1: A defrost is performed when the instrument
is switched on
SYF flag C 0 1 0
d5 Defrost delay on start-up SYF min C 0 250 0
d6 Display on hold during defrost
0: Alternating display of dEF and probe value
1: Display of the last temp. shown
2: Display of dEF steady
SYF - C 0 2 1
dd Dripping time after defrost SYF min F 0 15 2
d8 Alarm bypass after defrost SYF ore F 0 250 1
d8d Alarm bypass after door open SYF min C 0 250 0
d9 Defrost priority over compressor protectors
0: The protection times c1, c2 and c3 are
observed
1: The protection times c1, c2 and c3 are not
observed
SYF flag C 0 1 0
d/1 Display of defrost probe 1 MSYF °C/°F F - - -
d/2 Display of defrost probe 2 MSYF °C/°F F - - -
dC Time base for defrost
0: dI in hours, dP1 and dP2 in minutes
1: dI in minutes, dP1 and dP2 in seconds
SYF flag C 0 1 0
d10 Compressor running time SYF ore C 0 250 0
d11 Running time temperature threshold SYF °C/°F C -20 20 1.0
d12 Advanced defrost SYF - C 0 3 0
dn Nominal defrost duration SYF - C 1 100 65
dH Proportional factor, variation in dI SYF - C 0 100 50
A0 Alarm and fan differential MSYF °C/°F C 0.1 20 2.0
A1 Type of threshold‘AL’and ‘AH
0: AL and AH are relative thresholds to the
set point
1: AL and AH are absolute thresholds
MSYF flag C 0 1 0
AL Low temperature alarm threshold MSYF °C/°F F -50 200 0.0
AH High temperature alarm threshold MSYF °C/°F F -50 200 0.0
Ad Low and high temperature signal delay MSYF min F 0 250 120
A4 Digital input 1 configuration
0: Input not active 1: Immediate external
alarm
2: Delayed external
alarm
3: Enable defrost (model
M probe selection)
4: Start defrost
5: Door switch with
compressor and fan
stop
6: Remote on/off 7: Curtain switch
8: Low pressure
switch
9: Door switch with fan
stop only
10: Direct/reverse 11: Light sensor
12: Activation of the
AUX output
13: Door switch with
compressor and fans off
and light not managed
14: Door switch with fans only off and light
not managed
SYF
M
-
-
C
C
0
0
14
14
0
3
A5 Digital input 2 configuration (DI2) - As for A4 MSYF - C 0 14 0
A6 Stop compressor from external alarm SYF min C 0 100 0
A7 External alarm detection delay SYF min C 0 250 0
A8 Enable alarms ‘Ed1’ and ‘Ed2’
0: Alarm signals Ed1 and Ed2 enabled
1: Alarm signals Ed1 and Ed2 disabled
SYF flag C 0 1 0
0
1
Ado Light management mode with door switch MSYF flag C 0 1 0
Ac High condenser temperature alarm SYF °C/°F C 0.0 200 70.0
AE High condenser temperature alarm differential SYF °C/°F C 0.1 20 10
Acd High condenser temperature alarm delay SYF min C 0 250 0
AF Light sensor OFF time SYF s C 0 250 0
ALF Antifreeze alarm threshold MSYF °C/°F C -50 200 -5.0
AdF Antifreeze alarm delay MSYF min C 0 15 1
F0 Fan management
0: Fans always on
1: Fans controlled according to the temperatu-
re difference between the virtual control probe
and the evaporator temperature
2: Fans controlled according to the evaporator
temperature
F flag C 0 2 0
F1 Fan start temperature F °C/°F F -50 200 5.0
F2 Fan OFF with compressor OFF
0: Fans always on
1: Fans off with compressor off
F flag C 0 1 1
F3 Fans in defrost
0: Fans operate during defrosts
1: Fans do not operate during defrosts
F flag C 0 1 1
Fd Fan OFF after dripping F min F 0 15 1
F4 Condenser fan stop temperature MSYF °C/°F C -50 200 40
F5 Condenser fan start differential MSYF °C/°F C 0.1 20 5.0
+0500019EN - rel. 3.4 del 07.02.2018
IROPZDSP00:
Opzione interfaccia
display
Display interface option
IROPZ48500:
Interfaccia scheda seriale RS485
Serial board interface RS485
IROPZKEY**:
Chiave di programmazione
Programming key
Fig. 9
Technical specication
Power supply
Model Voltage Power
S115...230 V~ (switching)
(+10%, -15%), 50/60 HZ 6 VA, 50 mA~ max
Insulation guaranteed
by the power supply
insulation in reference to very low voltage parts reinforced 6 mm in air, 8 mm
on surface 3750 V insulation
insulation from relay outputs primary 3 mm in air, 4 mm
on surface 1250 V insulation
Inputs
S1 NTC or PTC, depending on the model
S2 NTC or PTC, depending on the model
DI1/S3 free contact, contact resistance < 10 Ω, closing current 6 mA
NTC or PTC, depending on the model
DI2 / S4 free contact, contact resistance < 10 Ω, closing current 6 mA
NTC or PTC, depending on the model
Maximum distance of probes and digital inputs less than 10 m
Note: During installation keep the power and load connections separate probe
cables, digital inputs, repeater display and supervisory system.
Probe type
NTC high
temperature
50 kΩat 25 °C,
range from –40T150 °C
measurement error
1.5 °C in the –40T150 °C range
4 °C in the external range at
-20T115 °C
Std. CAREL NTC 10 kΩat 25 °C,
range from –50T90 °C
measurement error
1 °C in the –50T50 °C range
3 °C in the –50T90 °C range
Std. CAREL PTC
(specific model)
985 Ωat 25 °C,
range from -50T150 °C
measurement error:
2 °C in the –50T50 °C range
4 °C in the –50T150 °C range
Relay outputs
depending on the model
EN60730-1 UL 873
250 V~ operating
cycles 250 V~ operating
cycles
5 A *5 (1) A 100000 5 A resistive 1 FLA
6 LRA C 300 30000
8 A *
8 (4) A on N.O. 6
(4) A on N.C. 2 (2)
A if the N.C. and
N.O. contacts are
connected con-
temporaneously
100000 8 A resistive 2
FLA 12 LRA C300
30000
Uscite relè
30 A 12 (10) A su N.O. 100000 12 A res. 12FLA
72LRA 30000
insulation from very low voltage
parts
reinforced 6 mm in air, 8 mm on surface
3750 V insulation
* relay not suitable for uorescent loads (neon lights, ...) that use starters (ballasts) with phase-shift
capacitors. Fluorescent lamps with electronic control devices or without phase-shift capacitors can be
used, within the operating limits specied for each type of relay.
Connections
Type of connection Cross-section Maximum
current
fixed screw-on removable for screw
blocks faston with crimped contacts for wires from 0.5 to 2.5 mm212 A
The installer has to provide the correct dimensioning of the power supply and
cable connection between the instrument and the loads. In max load and max
operating temp. conditions, cables rated for operation at up to 105 °C are required.
Case plastic dimensions 36x167x45 mm
mount-in depth 40 mm
Mounting
panel drilling template
using screws from front panel dimensions
29x138.5 mm distance between fastening
screws 153.5 mm
fastening screws countersunk with tread diameter 3.9 mm
maximum
Case (wide version) plastic dimensions 39.4x183x45 mm
mounting depth 40 mm
Installation
(wide version)
on smooth, hard and indeformable
panel using screws from the front or brackets
drilling template
dimensions from 138.5x29 to 150x31
spacing between fastening screws 165 mm
or 153.5 mm
fastening screws
countersunk with maximum thread diameter
3.9 mm for 165 mm spacing; for 153 spacing,
flat head with max. thread diameter 3 mm
Display
digits 3 digit LED
display range from –99 to 999
operating status indicated by graphic icons on the display
Keypad 8 rubber silicon buttons
Infrared receiver available depending on the model
Clock with backup
battery available depending on the model
Buzzer available on all models
Clock
error at 25 °C ±10 ppm (±5,3 min/year)
error in the temperature range
-10T60 °C -50 ppm (-27 min/year)
ageing < ±5 ppm (±2,7 min/year)
discharge time 6 months (max. 8 months)
recharge time typical 5 hours (<8 hours max.)
Operating temperature -10T60 °C
Operating humidity <90% r.H. non-condensing
Storage temperature -20T70 °C
Storage humidity <90% r.H. non-condensing
Front panel index of protection smooth and stiff panel installation with gasket IP65
Environmental pollution normal
PTI of the insulating material > 250 V
Period of electric stress across insulating parts long
Category of resistance to re category D (UL 94-V0)
Class of protection against voltage surges category II
Tipo di azione e disconnessione relè contacts 1c (microdisconnection)
Construction of control incorporated control, electronically
Classication according to protection against
electric shock Class II, by appropriate incorporation
Software class and structure class A
Front panel cleaning only use neutral detergents and water
Serial interface for CAREL network external, available on all models
Interface for repeater display external, available on models with H and 0 power supply
Max. distance between interface and display 10 mt
Programming key available for all models
The powercompact small range fitted with the standard CAREL NTC probe is compliant with stan-
dard EN 13485 on thermometers for measuring the air temperature in applications on units for the
conservation and sale of refrigerated, frozen and deep-frozen food and ice cream. Designation of
the instrument: EN13485, air, S, A, 1, - 50T90 °C. The standard CAREL NTC probe is identifiable by
the printed laser code on “WP” models, or the code “103AT-11”on “HP” models, both visible on the
sensor part.
Safety standards: compliant with the European reference standards.
Precautions for installation:
• the connection cables must guarantee insulation at up to 90 °C;
• adequately secure the connection cables to the outputs so as to avoid contact with very low
voltage components.
Optional connections: