Left (-)/Right (+) Buttons
The left(-)/right(+) buttons in the normal operating mode
are used to modify, decrease and increase respectively,
the currently selected preset value. If the button is pressed
and released, the preset value is changed by 1 kV at a
time. If the button is held for over a 1/2 second, the value
will begin changing by 5 kV increments.
Reset Button
The reset button is used in the normal operating mode to
clear fault or overload conditions when the trigger signal is
OFF. This will NOT prevent any other active fault conditions
from triggering a new fault.
Figure 4: 9060 Connection Interface
NOTE
There is a 5 second fault reset delay timer that
inhibits the triggering of high voltage immediately
after a fault reset.
HV Control Button
This button, shown in the center of Figure 3, is not functional
for handgun units.
.
CONNECTION INTERFACE
The 9060 Controller connection interface shown in Figure
4, provides all of the required connections for setting up a
local controlled painting system. This connection interface
consists of one (1) high voltage cable connector, one (1)
standard I/O connector, one (1) interlock I/O connector,
one (1) ground lug connection, one (1) air ow switch
connection, two (2) fuses, and one (1) AC inlet receptacle.
CONNECTORS
High Voltage Cable Connector
The high voltage cable connector is the largest connector
and is located on the far right of the connection interface.
The connector will come covered with a factory installed
red protective cap. This connector is designed for use with
standard high voltage cables such as 79518 and 79519.
The specic cable required depends on the applicator
being used. Please refer to the applicator manual for the
cable required.
Standard I/O Connector
The standard I/O connector is located just left of the high
voltage cable connector. This connector is provided as the
entry point for a shielded multi-conductor cable used for
remote I/O signals and includes the required cable grommet
hardware to keep the cable in place with minimal strain.
This connector is NOT used for handgun units.
Interlock I/O Connector
The interlock I/O connector is located just above the AC inlet
receptacle. This connector is provided as the entry point
for interlock signal wiring for the booth fan, conveyor, and
solvent supply. The connector includes the required cable
grommet hardware to keep wiring in place with minimal
strain. For more information on the interlock connections,
please see the “Installation” section of the service manual.
Ground Lug Connection
The ground lug connection is located directly below the
fuses and has a ground logo sticker directly below it. This
lug is provided as an external ground connection point
used to ground the 9060 to an earth ground via a ground
cable. This ground lug connection can also be used as the
ground point for the high voltage cable ground.
Air Flow Switch Connection
The air ow switch connection is installed to provide a
pneumatic trigger signal for handguns indicating that the
trigger has been actuated. This signal is used to turn on
the High Voltage output. Both threaded connectors of the
air ow switch will come covered with red protected caps.
AC Inlet Receptacle
The AC inlet receptacle is a standard IEC C14 Appliance
Inlet connector with a maximum rating of 250 VAC. It can
handle both 110VAC and 240 VAC inputs at 50 or 60 Hz.
The unit is shipped with the appropriate rated AC cord for
the particular installation.
CP-13-06-R5 (09/2018) 13 / 34 www.carlisleft.com
INTRODUCTION
EN