manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Carrier
  6. •
  7. Air Conditioner
  8. •
  9. Carrier 40KMC------301 User manual

Carrier 40KMC------301 User manual

40KMC
40KMQ-- 301
301
LISTED
FAN COIL UNIT
36N2
OWNER'S MANUAL
40KMC 310/40KMQ ...... 310
Split system "Global cassette" indoor unit
IR Remote Control "Room Controller" "Zone Manager"
The unit can be used with infrared Remote Control, with the Carrier "Room
Controller" or "Zone Manager" remote control.
Carrier "Room controller" control instructions are contained in the present manual.
Infrared Remote and "Zone Manager" controls instructions are contained in the relevant
manuals.
The installation instructions for both the indoor and the outdoor unit are given in the
manuals for each unit.
Contents
Page
General information .................................................................................... 2
System description ..................................................................................... 2
Unit LEDs and controls ............................................................................... 3
Periodical checks ........................................................................................ 3
Optimum comfort and minimum power consumption ................................. 4
Correct cleaning .......................................................................................... 4
Before a long shutdown period .................................................................. 4
"Room controller" general information and characteristics ............................ 5
Unit protection devices ............................................................................... 5
"Room controller" wired control .................................................................. 6/7
Troubleshooting .......................................................................................... 8
40KMC 310/40KMQ
General information 310
Unit operation and maintenance
Read this instruction manual thoroughly before using the unit.
• This unit complies with UL 1995 directive (Usa and Canada).
• Check that the main power supply voltage and frequency are as
required for the unit; the power source must be sufficient to
operate all other appliances connected to the same line.
Also ensure that local building codes and NEC (National electrical
code) requirements have been followed for the main supply circuit.
• To avoid personal injury or damage to unit,do not service until all
power sources are shut down, locked out, and tagged out.
Failure to do so could result in personal injury or unit damage.
WARNING:
To prevent fire, explosion or injury, do not operate the unit near
dangerous substances or esposed to lighting equipment.
• All operation and maintenance manuals must be carefully looked
after and kept with the equipment, should the unit change owners.
• Check that local building codes and NEC (National electrical code)
requirements for the installation have been followed. In particular,
ensure that a properly sized and connected ground wire is in place.
• Only use the unit for factory approved applications: the unit
cannot be used in laundry premises.
• Do not use damaged equipment. In case of malfunction, turn the
unit OFF and disconnect the main supply.
• Disconnect the main power supply prior to any maintenance
operations or prior to handling any internal unit parts.
• The manufacturer declines any liability for damage resulting from
modifications or errors in the electrical or refrigerant connections,
made during the installation, or from improper use of this equipment.
This will invalidate the unit warranty conditions immediately.
• This unit will only work safely and correctly, if installed and tested
by qualified personnel.
• Do not open the remote control to avoid possible damage.
In case of malfunction contact a qualified service engineer.
• This unit contains moving parts. Ensure that these parts are kept
out of the reach of children.
• Maintain the room temperature at general comfort conditions,
especially when children, elderly or handicapped persons are present.
• In order to ensure correct use, the air conditioner must operate
within the temperature limits indicated in the "Operating Limits"
table, included in the Technical manual. Failure to observe these
limits may cause unit malfunction or water leakage.
• In order to avoid electric shock, fire or injury, stop the unit and
disconnect the safety switch in case of abnormal events (such as
smell of burning) and call Carrier Service for further instructions.
• A routine maintenance should be carried out on the unit to check the
correct operation of the electric connections and protection devices.
• Extraordinary maintenance operations must be carried out by
specially trained personnel.
• Do not attempt to repair, move, modify or re-install the unit on your
own. To avoid electric shock or fire make sure these operations
are carried out by qualified personnel only.
• Contact the qualified service if one of the following events takes place:
- hot or damaged power supply cable;
- unusual noise during operation;
- frequent operation of the protection devices;
- unusual smell (such as smell of burning).
WARNING:
Never operate unit without a filter or with grille removed. Damage
to the unit or personal injury may result.
WARNING:
If air filter is not replaced in the unit, dust and dirt gather in air
conditioner and operation becomes impaired.
• A mist or cloud of vapor may be emitted from the unit, when
switching from a cooling operation to a reverse cycle heating
operation. This will occur when the unit has been operating in
cooling mode for awhile and then is switched to heating. The
combination of the evaporated indoor coil condensate and the dry
room air, may result in a cloud of vapor being emitted from the
unit. There is no need for concern.
• Inspect equipment for damage during transport. In case of
damage file an immediate claim with the shipping company.
• Non-routine maintenance of the refrigerant circuit must only be
carried out by qualified personnel.
•All of the manufacturing and packaging materials used for
this appliance are biodegradable and recyclable.
• Dispose of the packaging material and of the remote control
batteries in accordance with local requirements.
• This equipment contains refrigerant that must be disposed of
correctly. When disposing of the unit at the end of its operational
life, take the unit to an authorised waste disposal centre, for
correct disposal procedures.
z_ WARNING:
The unit must always be switched OFF using the Room
Controller. Do not switch OFF the split system by
disconnecting the electric power supply.
System description
A. Outdoor unit
B. Indoor unit
C. Room Controller
(if foreseen)
t. Air return
2. Air filters
3. Air supply
4. Operation indicator light
and receiver of remote
control signals (if foreseen)
5. Nameplate
6. Interconnecting tubing
7. Condensate drain (open)
12 3 4 5
/ /
/// /
GB- 2
40KMC 310/40KMQ ...... 310
Unit warning lights and controls -Fault code EN(;LISH
P: Green LED
Q: Red LED
R: Yellow LED
S : Remote control
signal receiver
Indoor unit LEDs
Information concerning indoor unit operation, timer status and
diagnostic is given by 3 LEDs located on the unit.
•THE GREEN LED (P) shows the following conditions:
- Fault codes (diagnostic);
- During normal operation, the LED is lit.
Once a failure occurs, the LED flashes at intervals of 0.5
seconds. The fault code is deduced from the number of times
the LED flashes. Between one flash cycle and the next a pause
of 5 seconds elapses.
•THE RED LED (Q) gives the following information:
- During normal operation, the LED is OFF;
- During defrost the LED is lit;
- During the test for wired connection, the LED flashes at 0.1
second intervals.
•THE YELLOW LED (R) shows the operation in timer mode.
During this operation the LED is lit.
If the timer mode is active and the unit is immediately
restarted after a stop, this LED flashes until a new signal is
sent to the unit.
In case the Room Controller is net working, obtain a qualified
service personnel.
Fault code
Once a failure occurs with the indoor unit in operation, the green
unit LED flashes at intervals of 0.5 seconds.
The fault code is deduced from the number of times the green
LED flashes, blocking unit operation.
Between one flash cycle and the next one, a pause of 5 seconds
elapses.
Table IX: Fault code
Code
3
2
4
6*
7
10
11
12
13
14
with enabled
Description
Room air sensor fault
Condensate discharge pump
Indoor unit coil sensor fault
Filter dirty
Outdoor unit failure
EEPROM corrupt
Card serial number damaged
Address /zone incomplete
Gas flow distributor corrupt
Outdoor air thermistor
code
Table Ih Periodical checks
For a good operation of the
Indoor unit Every month Every 4 months Every year airconditioneritis
recommended to carry out
Clean air filter (2) e(l/ checks and maintenance
as indicated.
Clean drain pipe (2) •Recommended
maintenance intervals may
vary depending on the
Outdoor unit Every month Every 4 months Every year installation environment,
e.g. dusty zones, etc.
Clean outdoor coil from outside
Clean outdoor coil from inside (2)
Blow air over electric parts (2)
Check electric connection tightening (2)
Clean fan wheel (2)
Check fan tightening (2)
Clean drain pan (2)
(1) Increase frequency in
dusty zones.
(2) Operations to be
carried out by qualified
service personnel.
Refer also to
'Installation Manual".
GB -3
40KMC 310/40KMQ ...... 310
Optimum comfort,,, -Correct cleaning -Before a long shutdown period
Optimum comfort and minimum power
consumption
r
r-
Keep room temperature at a comfortable level.
Only open doors and windows when strictly necessary.
When cooling, avoid direct sunlight in the room: if possible, draw
the curtains or close the shades.
Do not obstruct the air intake or outlet of the indoor unit.
Obstructions will cause a reduction in the air flow and the
conditioning effect, resulting in unit malfunction.
Ensure that the air filters are clean.
Ensure that the air distribution in the room is uniform by properly
adjusting the air flow direction.
Periodically clean the area surrounding the outdoor unit and the
air intake, in order to avoid reduced air circulation.
Keep heat sources away from the unit: panels may be damaged.
Correct cleaning
• Turn the unit OFF and switch the main supply OFF.
//
Use only a clean, damp cloth and a mild detergent.
Do not use flammable liquids, solvents or abrasive powders that
may result in damage to the panels.
Use only a dry cloth to clean the remote control.
Before a long shutdown period
Ask to clean the filter and replace it in the unit.
/
Keep the unit in operation for half a day in the ventilation
(fan only) mode in order to dry all internal parts.
o!
Switch the unit OFF and wait for at least 3 minutes before switch-
ing OFF the main electric supply.
Clean indoor and outdoor units.
GB- 4
40KMC 310/40KMQ 310
"Room controller" general information and characteristics
\\E D
BA= Display readout
B= Increase
temperature /
change louvre
setting button
C = Decrease
temperature /
change louvre
setting button
D= Fan selection
button
E = Mode selection
button
Display of selected functions
\
®® ®
(_ Automatic _ Set temperature C._ Heating
@Off (_ Operating (_ Cooling
(_ Temperature position of the air (_ Dehumidification
selected / room louvre only
temperature (_ Fan speed
Characteristics
ENGLISH
Single unit operation:
Ability to control one unit only.
Grouping:
Ability to control 2 to 6 units with one Room Controller.
Operating modes:
Off, Heat, Cool, Dry, Auto, and Fan only.
Fan speeds:
Low, Medium, High, and Auto.
Louver control:
Auto and swing.
Desired temperature:
Range between 17 and 32 °C (63 and 90 °F).
Room Thermistor Override:
Allows to use air sensor located in the Room Controller instead
of the one located into the unit.
• Diagnostics:
Detects the fault of air sensor in the Room Controller.
"AI" shown on the screen indicates this anomaly.
up
down
"up" and "DOWN" buttons
Buttons for raising or lowering the temperature or for selecting
the "AUTO" or "SWINe" louver mode.
F
MODE FAN
Button for operation mode selection.
Button for fan or louvre selection.
Table I: Unit protection devices
System Type of protection Effect of protection Operation mode When on
Cold draft prevention Indoor fan off Heating in
heat pump mode During unit operation
Heat pump Heating in
Defrost cycle Indoor fan off heat pump mode During unit operation
Indoor coil
Cooling only freeze protection Compressor off Cooling During unit operation
and
heat pump Against frequent Compressor Cooling or heating At unit start-up or
compressor cycling time delay in heat pump mode change of operating mode
WARNING:
During heat pump operation the unit will undergo several defrost cycles to remove ice that might collect on the outdoor unit in very low ambient
temperatures, In these cycles, the indoor fan will be automatically off and cannot operate until defrost cycle is completed,
GB-5
40KMC 310/40KMQ ...... 310
"Room controller" wired control
Power up
All segments of the LCD should be energized for five seconds.
The mode, fan, louver, desired temperature and configuration
information should be read from the EEPROM.
If the EEPROM values are not valid, the following should be used
as defaults.
Operating Mode = AUTO
Fan Speed = AUTO
Desired Temperature = 72°F
°Fo°C = F
Louver = AUTO
Room Thermistor Override = OFF
Cooling only vs Heat/Cool Remote = Heat/Cool
Example of normal operation
When switched on, the control display appears.
Setting mode operation
"MODE"button
Pressing the "MODE" button will cause the mode to change.
The "MODE" button must be released and then pressed again in
order to change to the next mode.
The active mode will always be lit in normal operation.
Available modes to select are:
Heat/Cool Remote:
(_)OFF, O COOL, (_DRY, _ FAN ONLY, AAUTO, ",b,":-HEAT
Cooling Only Remote:
(_) OFF, _COOL, _DRY and _FAN ONLY
When the "MODE"button is not pressed for 15 seconds, the next
press will always switch the mode to OFF.
OFF Mode:
ICONS Energized:
•OFF Mode
• Room Temperature if configured for Room Thermistor Override,
otherwise nothing
Buttons available:
• "MODE" button
AUTO, HEAT, COOL and DRY Modes:
ICONS Energized:
• Operation Mode ICON.
• Room Temperature if configured for Room Thermistor Override
(operated by Room Controller), otherwise user selected
temperature with the "SETTEMP"Icon.
• FAN/LOUVER Icon with the user selected Fan and Louver
settings.
Buttons available:
• All Buttons are available.
AAUTO Automatic operation
NOTE:
The compressor and electric heater must be off for at least 30
Minutes, this time being necessary to pass from Heating to
Cooling, or Cooling to Heating.
This will prevent the system from switching between Heating
and Cooling continuously.
COOL Cooling operation
DRY Drying operation.
:6.'-HEAT Heating operation.
"s l, _
GB- 6
40KMC 310/40KMQ 310
"Room controller" wired control
FAN ONLY Mode:
ICONS Energized:
• Room Temperature if configured for Room Thermistor Override
(operated by Room Controller), otherwise nothing.
• FAN/LOUVER Icon with the user selected Fan and Louver
settings.
Buttons available:
• "MODE" and "FAN" buttons are available.
,_ fan only Ventilation operation only.
"uP" and "DOWN"button
(Selecting the desired temperature)
up
down
Pressing either the "up" or "DOWN" buttons will modify the desired
temperature.
The maximum desired temperature is 32°0 (90°F) and the
minimum desired temperature is 17°C (63°F).
Whenever the setpoint is being displayed, the "SETTEMP" icon is
illuminated.
Whenever the display mode is changed from C to F, the setpoint is
set to the default start-up values of 22°C for "C" mode and 72°F for
"F" mode.
J
If the air sensor built in the Room Control is enabled, the
display will indicate the room temperature after few seconds.
j
"FAN"button
(Adjusting the ventilation speed)
Pressing the "FAN"button will cause the fan speed to change.
The "FAN" SPEED button must be pressed and then released
to reach the desired speed (Low, Medium, High or Auto).
The icon on the display indicates that change has occurred.
ENGLISH
Auto mode setting will be displayed by blinking the fan Medium
speed and High speed icons in order (Med then Hi then repeat).
|_l_'l Low
(€÷J) Medium
High
Automatic
(Fan speed will automatically switch to the
value required for optimum comfort).
When this function is activated, the dotted
symbols will flash.
Louver mode selection
To enter louver mode selection, make sure the Room Controller is
on and hold the "FAN"button down for 5 seconds.
After 5 seconds, the selected louver setting will be displayed.
By pressing the up and down buttons the user can modify
the louver desired configuration.
The two settings will be displayed in the following way:
"S" with Swing Louver Icon - represents Swing Louver.
"A" with Auto Louver Icon - represents Auto Louver.
Press "FAN"button to exit LOUVER Mode Selection.
This mode will exit automatically after 10 seconds if no buttons are
pressed.
The only way to change the operation mode, is to go back to this
menu.
NOTE:
• If units are grouped to one Room Controller, all units will end
up having the same louver value.
• Louver Mode selection is not available during OFF mode.
R:AUTO Automatic louvre positioning to the best position
for the selected operating mode.
S:SWING Louvres swing continuously.
GB -7
40KMC 310/40KMQ ...... 310
Troubleshooting
No Room controller LCD display:
•Mis-wiring of the 12 volt power to Room Controller control;
verify that + 12 V and Ground are connected to the proper
terrminals of the Controller (Reference Installation wiring
section for correct connections): after disconnecting the
power, correct the wiring problem and re-cycle power.
• Power not online; check that the units main power is
connected.
The main control board should be operating normally: after
verifing the wiring to the Room Controller, re-cycle the unit
power.
• No 12 volts between P and G of terminal block; check the
installation of the J6 plug on the main control board: after
disconnecting the power, correct the wiring problem and
re-cycle power.
Note." Those verificationsneed to be carried out by qualified
personnel only.
+12 volts applied to Room Controller at the correct terminals
and still does not operate:
• The Room Controller is damaged; change the Room
Controller and re-cycle power.
Note." 7-hisoperation needs tobe carriedout by qualified
personnel only.
Air conditioner will not start:
• The main switch is switched OFF, place the switch in the ON
position.
• The fuses on the main switch are burnt out; replace the fuses.
(thisoperationneed tobe carriedout by qualifiedpersonnelonly).
• Wait for 3 minutes: protection against frequent compressor
cycling is ON.
• Selected temperature is higher than the room temperature (or
lower in the heating mode).
Air conditioner is not supplying enough cooling (or heating):
• Air cannot circulate freely.
• Dirty filter reduces air quantity circulating.
Filter must be cleaned by skilled personnel only.
• Doors and/or windows are open.
• Fan speed has been set to 'low'.
• Air flow direction is not correct for optimum ventilation.
• Selected temperature is not correct.
A slight mist is emitted from the unit:
• A slight mist, coming out of the unit air outlet, is sometimes
noticed during cooling operation. This is due to the cool air
coming into contact with the room air.
A slight whistling noise is heard when the air conditioner
starts or stops:
• This is due to the refrigerant beginning to circulate or an
adjustment of the refrigerant pressures. This is a normal
operating condition.
P (Green LED) indicator is flashing:
System malfunction.
Contact service organisation after having ensured that:
• Air circulation is not obstructed.
• Outdoor unit coil is not obstructed and causing severe reduction
of air circulation.
• Condensate drainage tube is not obstructed.
As regards fault codes to be communicated to the after-sales
service, please refer to the installation instructions.
Restart air conditioner after having corrected the faults.
Q (Red LED) indicator is illuminated:
• In the heating mode, the LED switches on to indicate an active
defrost condition.
The unit emits unpleasant smells:
• Unpleasant smells can accumulate on the air filters and then be
dispersed into the room during air conditioner operation.
Switch the unit OFF and contact an authorised service centre to
have the filters cleaned.
Restart unit in the ventilation (fan only) mode and open windows
to change room air.
The unit makes strange noises:
• Occasionally the unit makes strange noises at start-up, during
operation or when it has stopped.
These are generally due to the effect of temperature changes on
the plastic parts.
Mist or Vapor Cloud emitted at start-up of Heating operation:
• A mist or cloud of vapor may be emitted from the unit, when
switching from a cooling operation to a reverse cycle heating
operation. This will occur when the unit has been operating in
cooling mode for awhile and then is switched to heating. The
combination of the evaporated indoor coil condensate and the dry
room air, may result in a cloud of vapor being emitted from the
unit. There is no need for concern.
WARNING:
(models with electric heaters):
• If the manual reset, thermal trip device cuts out, switch the unit
OFF and ON again at the main switch to reset.
If the malfunction persists, contact your local authorised dealer.
GB-8
[L010127H09-03061
Via R. Sanzio, 9 - 20058 Villasanta (MI) Italy -Tel. 039/3636.1
The manufacturer reserves the right to change any product specifications without notice.
March, 2006. Printed in Italy

Other manuals for 40KMC------301

1

This manual suits for next models

1

Other Carrier Air Conditioner manuals

Carrier 50TJ016 Dimensions and installation guide

Carrier

Carrier 50TJ016 Dimensions and installation guide

Carrier 51FE User guide

Carrier

Carrier 51FE User guide

Carrier 42TSV0131CP User manual

Carrier

Carrier 42TSV0131CP User manual

Carrier WeatherMaker 50TCQ 17-24 Series Installation and user guide

Carrier

Carrier WeatherMaker 50TCQ 17-24 Series Installation and user guide

Carrier AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS... Operation manual

Carrier

Carrier AQUASNAP AIR COOLED CHILLERS WITH COMFORTLINK CONTROLS... Operation manual

Carrier TOSHIBA MMU-UP0071HP-UL User manual

Carrier

Carrier TOSHIBA MMU-UP0071HP-UL User manual

Carrier 38CKC User manual

Carrier

Carrier 38CKC User manual

Carrier 52F Series User manual

Carrier

Carrier 52F Series User manual

Carrier RAV180 User manual

Carrier

Carrier RAV180 User manual

Carrier 42VMC---N User manual

Carrier

Carrier 42VMC---N User manual

Carrier 024-048 User manual

Carrier

Carrier 024-048 User manual

Carrier 42TVBA010 User manual

Carrier

Carrier 42TVBA010 User manual

Carrier PA4G User manual

Carrier

Carrier PA4G User manual

Carrier 50GL030 Instructions and recipes

Carrier

Carrier 50GL030 Instructions and recipes

Carrier 50LJ008-014 Dimensions and installation guide

Carrier

Carrier 50LJ008-014 Dimensions and installation guide

Carrier 38MGR Series User manual

Carrier

Carrier 38MGR Series User manual

Carrier 40TGF UP Series User manual

Carrier

Carrier 40TGF UP Series User manual

Carrier 38MVC User manual

Carrier

Carrier 38MVC User manual

Carrier 09DK054-084 Dimensions and installation guide

Carrier

Carrier 09DK054-084 Dimensions and installation guide

Carrier 50ZPC Instruction Manual

Carrier

Carrier 50ZPC Instruction Manual

Carrier FDT21 User manual

Carrier

Carrier FDT21 User manual

Carrier 38HD018 Dimensions and installation guide

Carrier

Carrier 38HD018 Dimensions and installation guide

Carrier 24ACC6 Comfort Operation manual

Carrier

Carrier 24ACC6 Comfort Operation manual

Carrier Air V User manual

Carrier

Carrier Air V User manual

Popular Air Conditioner manuals by other brands

Daikin R32 Split Series installation manual

Daikin

Daikin R32 Split Series installation manual

Mitsubishi Heavy Industries DXK05ZTLA-WF user manual

Mitsubishi Heavy Industries

Mitsubishi Heavy Industries DXK05ZTLA-WF user manual

Argo SWAN EVO operating instructions

Argo

Argo SWAN EVO operating instructions

Vivax ACP-12CH35REWI R32 user manual

Vivax

Vivax ACP-12CH35REWI R32 user manual

Frigidaire CRA073PU11 use & care

Frigidaire

Frigidaire CRA073PU11 use & care

Webasto Frigo Top 25 DS Instructions for use

Webasto

Webasto Frigo Top 25 DS Instructions for use

Mitsubishi Electric Mr.Slim PUZ-SM100VKA Service manual

Mitsubishi Electric

Mitsubishi Electric Mr.Slim PUZ-SM100VKA Service manual

Challenge MPPHA-05CRN1-QB6 instruction manual

Challenge

Challenge MPPHA-05CRN1-QB6 instruction manual

LG LS-J0761CL Service manual

LG

LG LS-J0761CL Service manual

MegaLife NEBULA GREEN R32 Use and Installation Instructions

MegaLife

MegaLife NEBULA GREEN R32 Use and Installation Instructions

Haier AU362XHERA installation manual

Haier

Haier AU362XHERA installation manual

Haier 1U25MECFRA-3 Service manual

Haier

Haier 1U25MECFRA-3 Service manual

Haier AS072AIAAA Operation manual

Haier

Haier AS072AIAAA Operation manual

Sharp AU-1802Y Operation manual

Sharp

Sharp AU-1802Y Operation manual

Daikin FFQ12LVJU Operation manual

Daikin

Daikin FFQ12LVJU Operation manual

Panasonic CS-LZ9ZKA operating instructions

Panasonic

Panasonic CS-LZ9ZKA operating instructions

LG LSN-HSV2 owner's manual

LG

LG LSN-HSV2 owner's manual

Hitachi YUTAKI Series instruction manual

Hitachi

Hitachi YUTAKI Series instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.