
5
Accessory Description and Usage
1. Coastal Filter
A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.
SUGGESTED USE: In geographic areas where salt damage could occur.
2. Compressor Start Assist—Capacitor/RelayType
Start capacitor and start relay gives ‘‘hard’’ boost to compressor motor at each start-up.
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.
Installations where outdoor design temperature exceeds 105
°
F (40.6
°
C).
3. Compressor Start Assist—PTC Type
Solid-state electrical device which gives a ‘‘soft’’boost to the compressor at each start-up.
SUGGESTED USE: Installations with marginal power supply.
4. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and
minimizes chance of refrigerant slugging. May or may not include a thermostat control.
SUGGESTED USE: When interconnecting tube length exceeds 50 ft.
When unit will be operated below 55
°
F (12.8
°
C) outdoor air temperature. (Use with low-ambient controller.)
All commercial installations.
5. Cycle Protector
Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has been interrupted
for any reason, including normal room thermostat cycling.
SUGGESTED USE: Installations in areas where power interruptions are frequent.
Where user is likely to “play” with the room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 50 ft.
High-rise applications.
6. Evaporator FreezeThermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.
SUGGESTED USE: All units where winter start control (item 14) has been added.
7. Liquid Solenoid Valve (LSV)
An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) and which stops and starts refrigerant liquid flow
in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.
NOTE:
Compressor start assist — capacitor/relay type (Item 2) must also be used, if the system contains a reciprocating compressor.
SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units (Refer to ARI Unitary Directory).
In certain long-line applications. (Refer to Application Guideline.)
8. Low-Ambient Controller
Head pressure controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle the outdoor fan
motors in order to maintain condensing temperature within normal operating limits (approximately 130 to 110
°
F high, 70 to 50
°
low). The control will maintain working
head pressure at low-ambient temperatures down to –20
°
F when properly installed.
SUGGESTED USE: Cooling operation at outdoor temperatures below 55
°
F (12.8
°
C).
9. MotorMaster® Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing temperature during
operation in cooling mode only. For outdoor temperatures down to –20
°
F, it maintains condensing temperature at 100
°
F
±
10
°
F.
SUGGESTED USE: Cooling operation at outdoor temperatures below 55
°
F.
All commercial installations.
10. Sound Blanket/Shield/Hood
Wrap-around sound attenuation cover for the compressor. Reduces the sound level by about 0.2 bels.
SUGGESTED USE: Unit installed closer than 15 ft to quiet areas — bedrooms, etc.
Unit installed between 2 houses less than 10 ft apart.
11. Support Feet
Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base; minimizes corrosion.
SUGGESTED USE: Improve sound rating.
Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
12. Thermostatic Expansion Valve (TXV) Kit
A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit
includes valve, adapter tubes, and external equalizer tube. Hard shutoff type valves are available.
SUGGESTED USE: In certain long-line applications.
Commercial installations.
13. Time-Delay Relay
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.
SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.)
14. Winter Start Control
An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start up for cooling operation under low-load conditions.
SUGGESTED USE: All air conditioners where low-ambient controller has been added.