19
3. Dimensions de l'appareil
Figure 5: vue de la face avant et vue du côté de l'enceinte
Figure 6: vue de la face avant et vue du côté de l'enceinte avec dispositif de
décharge de tension
132 mm
132 mm
182 mm
132 mm
44 mm
44 mm
ECx-Light/Blind Series 3/14
6. Device Dimensions
Figure 6-1: Front view and side view of the enclosure without strain relief
ohne Zugentlastung und Geräteabdeckung mit Zugentlastung und Geräteabdeckung
mm (inches)
132 (5.2) 44 (1.7)
182
(7.2)
132 (5.2)
132
(5.2)
44 (1.7)
mm (inches)
ohne Zugentlastung und Geräteabdeckung mit Zugentlastung und Geräteabdeckung
mm (inches)
(7.2)
132 (5.2)
132
(5.2)
44 (1.7)
Figure 6-2: Front view and side view of the enclosure with strain relief
mm (inches)
Model Voltage
ECx-Light-4-WD
ECx-Light-4-ST
0-240 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4-STP 0-277 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4D-WD
ECx-Light-4D-ST
0-240 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4D-STP 0-277 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4DALI-WD
ECx-Light-4DALI-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Blind-4-WD
ECx-Blind-4-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Overvoltage Category II - 2.5 kV
ECx-Blind-4LV-WD
ECx-Blind-4LV-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Overvoltage Category II - 2.5 kV
Table 7-1: ECx-Light/Blind Power Voltage
7. Power Wiring
Model Typical Consumption
Max. Consumption
ECx-Light-4
0.3 W + all external loads
6.0 A
ECx-Light-4D
0.3 W + all external loads
6.0 A
ECx-Light-4DALI < 0.9 W
+ all external loads
10.0 A
ECx-Blind-4
0.3 W + all external loads
8.0 A
ECx-Blind-4LV
< 1 W + all external loads
1.2 A
Table 7-2: ECx-Light/Blind Consumptions
Model Protection
ECx-Light-4-WD
ECx-Light-4-ST
6.0 A external circuit breaker type C (250 VAC min)
ECx-Light-4-STP 6.0 A external circuit breaker type C (300VAC min)
ECx-Light-4D-WD
ECx-Light-4D-ST
6.0 A external circuit breaker type C (250 VAC min)
ECx-Light-4D-STP 6.0 A external circuit breaker type C (300 VAC min)
ECx-Light-4DALI-WD
ECx-Light-4DALI-ST
10.0 A external circuit breaker type C (250 VAC min)
ECx-Blind-4-WD
ECx-Blind-4-ST
8.0 A external circuit breaker type C or 8.0 A fast
acting high breaking external fuse (250 VAC min)
ECx-Blind-4LV-WD
ECx-Blind-4LV-ST
2.0 A external circuit breaker type C or 2.0 A fast
acting high breaking external fuse (250 VAC min)
Table 7-3: ECx-Light/Blind Protections
Use an external circuit breaker on the mains, as specied in the table
above and shown in the gure below to protect the expansion module
against power line spikes. The protection device must remain close to
the protected device.
The power wires must remain between 17 AWG (1 mm²)
and 16 AWG (1.5 mm²). Make sure the cable performances
suit the connected loads.
Operating handling or servicing this product must be
achieved by a qualied operator. Turn off power before any
kind of servicing.
Figure 7-1: Power wiring
L
N
N
L
Module
External Circuit Breaker
Each expansion module has physical connections for four (4) inputs
(marked as DIx for Digital Inputs) that are congured in EC-gfxProgram.
All input wiring must be connected using the provided detachable
connectors.
Before connecting any device to the controller, refer to
the installation guide of the equipment manufacturer.
Connectors allow the use of cables up to 16 AWG
(1.5 mm²).
8. Input Wiring
Wiring Digital Inputs (DIx)
This input conguration is used to monitor digital dry contacts.
Figure 8-1: Digital input – Dry contact (NO & NC)
DIx
COM
Digital Dry Contact
NO-NC
ECx-Light/Blind Series 3/14
6. Device Dimensions
Figure 6-1: Front view and side view of the enclosure without strain relief
ohne Zugentlastung und Geräteabdeckung mit Zugentlastung und Geräteabdeckung
mm (inches)
132 (5.2) 44 (1.7)
182
(7.2)
132 (5.2)
132
(5.2)
44 (1.7)
mm (inches)
ohne Zugentlastung und Geräteabdeckung mit Zugentlastung und Geräteabdeckung
mm (inches)
(7.2)
132 (5.2)
132
(5.2)
44 (1.7)
Figure 6-2: Front view and side view of the enclosure with strain relief
mm (inches)
Model Voltage
ECx-Light-4-WD
ECx-Light-4-ST
0-240 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4-STP 0-277 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4D-WD
ECx-Light-4D-ST
0-240 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4D-STP 0-277 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4DALI-WD
ECx-Light-4DALI-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Blind-4-WD
ECx-Blind-4-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Overvoltage Category II - 2.5 kV
ECx-Blind-4LV-WD
ECx-Blind-4LV-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Overvoltage Category II - 2.5 kV
Table 7-1: ECx-Light/Blind Power Voltage
7. Power Wiring
Model Typical Consumption
Max. Consumption
ECx-Light-4
0.3 W + all external loads
6.0 A
ECx-Light-4D
0.3 W + all external loads
6.0 A
ECx-Light-4DALI < 0.9 W
+ all external loads
10.0 A
ECx-Blind-4
0.3 W + all external loads
8.0 A
ECx-Blind-4LV
< 1 W + all external loads
1.2 A
Table 7-2: ECx-Light/Blind Consumptions
Model Protection
ECx-Light-4-WD
ECx-Light-4-ST
6.0 A external circuit breaker type C (250 VAC min)
ECx-Light-4-STP 6.0 A external circuit breaker type C (300VAC min)
ECx-Light-4D-WD
ECx-Light-4D-ST
6.0 A external circuit breaker type C (250 VAC min)
ECx-Light-4D-STP 6.0 A external circuit breaker type C (300 VAC min)
ECx-Light-4DALI-WD
ECx-Light-4DALI-ST
10.0 A external circuit breaker type C (250 VAC min)
ECx-Blind-4-WD
ECx-Blind-4-ST
8.0 A external circuit breaker type C or 8.0 A fast
acting high breaking external fuse (250 VAC min)
ECx-Blind-4LV-WD
ECx-Blind-4LV-ST
2.0 A external circuit breaker type C or 2.0 A fast
acting high breaking external fuse (250 VAC min)
Table 7-3: ECx-Light/Blind Protections
Use an external circuit breaker on the mains, as specied in the table
above and shown in the gure below to protect the expansion module
against power line spikes. The protection device must remain close to
the protected device.
The power wires must remain between 17 AWG (1 mm²)
and 16 AWG (1.5 mm²). Make sure the cable performances
suit the connected loads.
Operating handling or servicing this product must be
achieved by a qualied operator. Turn off power before any
kind of servicing.
Figure 7-1: Power wiring
L
N
N
L
Module
External Circuit Breaker
Each expansion module has physical connections for four (4) inputs
(marked as DIx for Digital Inputs) that are congured in EC-gfxProgram.
All input wiring must be connected using the provided detachable
connectors.
Before connecting any device to the controller, refer to
the installation guide of the equipment manufacturer.
Connectors allow the use of cables up to 16 AWG
(1.5 mm²).
8. Input Wiring
Wiring Digital Inputs (DIx)
This input conguration is used to monitor digital dry contacts.
Figure 8-1: Digital input – Dry contact (NO & NC)
DIx
COM
Digital Dry Contact
NO-NC
ECx-Light/Blind Series 3/14
6. Device Dimensions
Figure 6-1: Front view and side view of the enclosure without strain relief
ohne Zugentlastung und Geräteabdeckung mit Zugentlastung und Geräteabdeckung
mm (inches)
132 (5.2) 44 (1.7)
182
(7.2)
132 (5.2)
132
(5.2)
44 (1.7)
mm (inches)
ohne Zugentlastung und Geräteabdeckung mit Zugentlastung und Geräteabdeckung
mm (inches)
(7.2)
132 (5.2)
132
(5.2)
44 (1.7)
Figure 6-2: Front view and side view of the enclosure with strain relief
mm (inches)
Model Voltage
ECx-Light-4-WD
ECx-Light-4-ST
0-240 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4-STP 0-277 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4D-WD
ECx-Light-4D-ST
0-240 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4D-STP 0-277 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4DALI-WD
ECx-Light-4DALI-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Blind-4-WD
ECx-Blind-4-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Overvoltage Category II - 2.5 kV
ECx-Blind-4LV-WD
ECx-Blind-4LV-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Overvoltage Category II - 2.5 kV
Table 7-1: ECx-Light/Blind Power Voltage
7. Power Wiring
Model Typical Consumption
Max. Consumption
ECx-Light-4
0.3 W + all external loads
6.0 A
ECx-Light-4D
0.3 W + all external loads
6.0 A
ECx-Light-4DALI < 0.9 W
+ all external loads
10.0 A
ECx-Blind-4
0.3 W + all external loads
8.0 A
ECx-Blind-4LV
< 1 W + all external loads
1.2 A
Table 7-2: ECx-Light/Blind Consumptions
Model Protection
ECx-Light-4-WD
ECx-Light-4-ST
6.0 A external circuit breaker type C (250 VAC min)
ECx-Light-4-STP 6.0 A external circuit breaker type C (300VAC min)
ECx-Light-4D-WD
ECx-Light-4D-ST
6.0 A external circuit breaker type C (250 VAC min)
ECx-Light-4D-STP 6.0 A external circuit breaker type C (300 VAC min)
ECx-Light-4DALI-WD
ECx-Light-4DALI-ST
10.0 A external circuit breaker type C (250 VAC min)
ECx-Blind-4-WD
ECx-Blind-4-ST
8.0 A external circuit breaker type C or 8.0 A fast
acting high breaking external fuse (250 VAC min)
ECx-Blind-4LV-WD
ECx-Blind-4LV-ST
2.0 A external circuit breaker type C or 2.0 A fast
acting high breaking external fuse (250 VAC min)
Table 7-3: ECx-Light/Blind Protections
Use an external circuit breaker on the mains, as specied in the table
above and shown in the gure below to protect the expansion module
against power line spikes. The protection device must remain close to
the protected device.
The power wires must remain between 17 AWG (1 mm²)
and 16 AWG (1.5 mm²). Make sure the cable performances
suit the connected loads.
Operating handling or servicing this product must be
achieved by a qualied operator. Turn off power before any
kind of servicing.
Figure 7-1: Power wiring
L
N
N
L
Module
External Circuit Breaker
Each expansion module has physical connections for four (4) inputs
(marked as DIx for Digital Inputs) that are congured in EC-gfxProgram.
All input wiring must be connected using the provided detachable
connectors.
Before connecting any device to the controller, refer to
the installation guide of the equipment manufacturer.
Connectors allow the use of cables up to 16 AWG
(1.5 mm²).
8. Input Wiring
Wiring Digital Inputs (DIx)
This input conguration is used to monitor digital dry contacts.
Figure 8-1: Digital input – Dry contact (NO & NC)
DIx
COM
Digital Dry Contact
NO-NC
ECx-Light/Blind Series 3/14
6. Device Dimensions
Figure 6-1: Front view and side view of the enclosure without strain relief
ohne Zugentlastung und Geräteabdeckung mit Zugentlastung und Geräteabdeckung
mm (inches)
132 (5.2) 44 (1.7)
182
(7.2)
132 (5.2)
132
(5.2)
44 (1.7)
mm (inches)
ohne Zugentlastung und Geräteabdeckung mit Zugentlastung und Geräteabdeckung
mm (inches)
(7.2)
132 (5.2)
132
(5.2)
44 (1.7)
Figure 6-2: Front view and side view of the enclosure with strain relief
mm (inches)
Model Voltage
ECx-Light-4-WD
ECx-Light-4-ST
0-240 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4-STP 0-277 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4D-WD
ECx-Light-4D-ST
0-240 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4D-STP 0-277 VAC/DC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Light-4DALI-WD
ECx-Light-4DALI-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Only to power light outputs. The module is
powered via the subnetwork.
Overvoltage Category II - 2.5 kV
ECx-Blind-4-WD
ECx-Blind-4-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Overvoltage Category II - 2.5 kV
ECx-Blind-4LV-WD
ECx-Blind-4LV-ST
100-240 VAC; -15%/+10%; 50/60 Hz;
Overvoltage Category II - 2.5 kV
Table 7-1: ECx-Light/Blind Power Voltage
7. Power Wiring
Model Typical Consumption
Max. Consumption
ECx-Light-4
0.3 W + all external loads
6.0 A
ECx-Light-4D
0.3 W + all external loads
6.0 A
ECx-Light-4DALI < 0.9 W
+ all external loads
10.0 A
ECx-Blind-4
0.3 W + all external loads
8.0 A
ECx-Blind-4LV
< 1 W + all external loads
1.2 A
Table 7-2: ECx-Light/Blind Consumptions
Model Protection
ECx-Light-4-WD
ECx-Light-4-ST
6.0 A external circuit breaker type C (250 VAC min)
ECx-Light-4-STP 6.0 A external circuit breaker type C (300VAC min)
ECx-Light-4D-WD
ECx-Light-4D-ST
6.0 A external circuit breaker type C (250 VAC min)
ECx-Light-4D-STP 6.0 A external circuit breaker type C (300 VAC min)
ECx-Light-4DALI-WD
ECx-Light-4DALI-ST
10.0 A external circuit breaker type C (250 VAC min)
ECx-Blind-4-WD
ECx-Blind-4-ST
8.0 A external circuit breaker type C or 8.0 A fast
acting high breaking external fuse (250 VAC min)
ECx-Blind-4LV-WD
ECx-Blind-4LV-ST
2.0 A external circuit breaker type C or 2.0 A fast
acting high breaking external fuse (250 VAC min)
Table 7-3: ECx-Light/Blind Protections
Use an external circuit breaker on the mains, as specied in the table
above and shown in the gure below to protect the expansion module
against power line spikes. The protection device must remain close to
the protected device.
The power wires must remain between 17 AWG (1 mm²)
and 16 AWG (1.5 mm²). Make sure the cable performances
suit the connected loads.
Operating handling or servicing this product must be
achieved by a qualied operator. Turn off power before any
kind of servicing.
Figure 7-1: Power wiring
L
N
N
L
Module
External Circuit Breaker
Each expansion module has physical connections for four (4) inputs
(marked as DIx for Digital Inputs) that are congured in EC-gfxProgram.
All input wiring must be connected using the provided detachable
connectors.
Before connecting any device to the controller, refer to
the installation guide of the equipment manufacturer.
Connectors allow the use of cables up to 16 AWG
(1.5 mm²).
8. Input Wiring
Wiring Digital Inputs (DIx)
This input conguration is used to monitor digital dry contacts.
Figure 8-1: Digital input – Dry contact (NO & NC)
DIx
COM
Digital Dry Contact
NO-NC