IRIS Touch Engineering Manual Version 1.4 Page 11 of 40
Configuration
To configure your dialler, use any of the following methods:
Alarm panel integration e.g. Honeywell Galaxy (RS485 connection) Texecom Premier range (Serial TTL
connection). Please refer to Section 7.9 “Panel configuration”.
Note: For connections to Honeywell Galaxy or Texecom Premier on the serial integration ensure you
configure the alarm panel first as this will transmit configuration to the IRIS Touch dialler.
For more details on the alarm panel integration download the full panel installation manual from
http://www.chironsc.com/downloads_security.html.
Connect the board’s Micro USB connector to a laptop / PC running the IRIS Toolbox software.
Download the IRIS ToolBox user guide from http://www.chironsc.com/downloads_security.html.
Note: If you want to use the IRIS Touch dialler for Pin inputs only or HHL / ESPA serial connections then you will
need to connect a Laptop / PC and configure the dialler using the IRIS Toolbox software, using the remote Touch
screen and Installation Wizard.
Defaulting
If at any point you want to completely default the dialler you can use the following procedure:
1. Completely power down the IRIS Touch.
2. Now Press and hold down the AP button.
3. Reapply power whilst still holding down the AP button pushed down for another 10 seconds.
Panel configuration
IRIS Touch 6xxNG diallers can be configured directly by the integration with certain panel manufacturers detailed
below:
Configuration from Honeywell Galaxy Panel via RS485
The IRIS Touch dialler can simulate a Galaxy Ethernet Module (Comm’s Mod 4) and remote keypad, for both Alarms
and Remote Service Suite upload/download connection.
Note: If you want to use the SMS messaging function from the Galaxy panel then you will need to emulate the
external PSTN module, and setup the Galaxy External PSTN module settings see the IRIS Honeywell Galaxy
Installation manual.
For further information on both the Galaxy installation and Remote Service Suite upload/download connection
please refer to the IRIS Honeywell Galaxy Installation Manual or IRIS Remote Service App Client User Guide for
Honeywell Galaxy range available from http://www.chironsc.com/downloads_security.html.
Note: For GPRS/3G it is not possible to configure the settings (e.g. APN) from the Galaxy keypad as the Galaxy has
no entry method.
Connect the IRIS Touch dialler to the Galaxy Data bus as indicated in Section 7.3 “Connections”, then power up the
Galaxy control panel, if not already powered up.
IRIS Touch 600NG or 640NG with GPRS/3G connection:
The GPRS APN can be configured via an SMS message from any mobile phone.
If GPRS/3G is used, you will need to set the GPRS APN. You can do this by sending a text message to the phone
number of the SIM card being used. The text should be in the format:
AT%G10=’apn’
Where ‘apn’ is the Access Point Name for the SIM, e.g. ‘orangeinternet’.
Note: The APN must be configured before the IRIS Touch is polling as after the dialler is polling all SMS
configuration will be rejected for security.
Alternatively, the information can be set via the IRIS Toolbox software on a PC / Laptop which connects via the Micro
USB connector. This is available from http://www.chironsc.com/downloads_security.html.
The configuration menu on the Galaxy panel for the Ethernet card is found at location 56 (Communications) entry 4
(Ethernet), please enter the required information as indicated on the next page.