Circutor CVM-MINI-ITF User manual

CVM-MINI-Ethernet
M98240101-03-18A
POWER ANALYZER
CVM-MINI-Ethernet
This manual is a quick guide to the use and operation of
the CVM-MINI-ITF & CMV-MINI-MC with Ethernet
connection. For more information, the whole manual
may be downloaded from CIRCUTOR's web page:
www.circutor.es
Before any maintenance, modification to the
connections, repair, etc., the equipment must be
disconnected from the supply. If any operation or
protection fault is suspected the equipment must
remain out of service
ensuring against any accidental
reconnection. The equipment is designed to be changed quickly
in the event of any breakdown.
The CVM-MINI is an instrument which measures,
calculates and displays the main electrical parameters
for three-phase industrial systems (balanced or
unbalanced). Measurements are in true effective value,
via three AC voltage inputs and three AC. current
inputs. (via In / 5 A or 1 A the ITF version and In0,25A
MC version). The parameters measured and calculated
are shown in the variables table, paragraph 7.
1.- INSTALLATION
The equipment is mounted on DIN rail. Also the device
has to be provided of an magnetic-thermal switch to be
disconnected. The fuses has to be type gl (IEC 269) or
type M between 0,5 to 2 A.
2.- ETHERNET NETWORK SETUP
The configuration software, IPSETUP.EXE, is available
from the CIRCUTOR Web site. It must be executed
under Windows operative system. Once executed it will
appear the following screen
In the field "MAC" it must be typed the physical address
of the unit using scripts as separator, this data is
showed on to the lateral label of the equipment and the
format is 14:A6:2C:XX:XX:XX.
In to the field "Dirección", type the assigned IP
address to the equipment into the local area network
Into the field "Netmask" type the mask for the network.
In case of routing the equipment in a different network,
setup the field "Gateway" with the IP address of the
device that allows the route. For example, if the
equipment must be accessible from Internet, will be
necessary setup the IP address for the ADSL router
that allows the Internet connection. Also the router will
need convenient programming to allow Internet enroute
and enable the traffic from/to the CVM-MINI-Ethernet.
If it is not the case leave the filed "Gateway" in blank.
3.- DHCP IP assignment
To assign the DHCP name, choose this option using
the arrow on the upper right, and select “On”. Once the
configuration fields have been enabled, enter the
“MAC”address that can be seen on the permanent side
label attached to the device, the format of which is
14:A6:2C:XX:XX:XX. In the “Dirección” field, enter an
unused, temporary IP address, which is within the
working range of your computer. In the “Host Name”
field, enter the DHCP name to be assigned to the
equipment. Optionally, the user can configure the
parameters of the “ClientID” field. The default
“VendorID”of the device is CIRCUTOR.
Once the parameters have been configured click on
"Configurar"
If the equipment is detected into the Ethernet network,
it will appear the following screen.
By clicking "Aceptar" the internal setup WEB page of
the equipment will be displayed.
If the equipment is not detected on the local network it
will appear the following screen.
Review the settings assigned to the computer, check
the connection to the router and the Ethernet
Connector LEDs are lit and / or blink. The LED on the
left side of the connector is the link status and the LED
on the right side indicates activity receive / transmit TX
/ RX. Both can be lit in green or amber color. If
everything appears correct, consult with your admin for
the local area network.
4.- SETTING (SETUP menu)
(Press SETUP key for 5 seconds)
The key validates the information and moves
on to the next menu.
The
max
key allows the different options in a
menu to be selected or increases a digit where a
variable is being entered.
The
min
key is used to move the cursor
among the digits.
The different options are sequentially described below.
4.1.- Voltage transformer primary
On screen the words "SET PriU" appear followed by 6
digits. These allow the voltage transformer primary to be
set (from 1to 100,000).
4.2.- Voltage transformer secondary
On screen the words "SET SEcU" appear followed by 3 digits.
These allow the voltage transformer secondary to be set (from
1to 999).
4.3.- Current transformer primary
The display show "SET PriA" followed by 5 digits. These allow
the current transformer primary to be set (from 1to 10,000).
In the case of using a transforming system type MC1,
introduces the primary of the transformer
corresponding to the relation of the selected physical
wiring. In case of using type MC3, introduces the value
of the primary that appears in the label of the
transformer.
4.4.- Current transformer secondary.
The display show "SET SecA". In the ITF versions, selection is
allowed between 1 and 5 A. In the MC version, this parameter
is not available in the equipment configuration menu.
4.5.- Measurement in 2 or 4 quadrants (power
consumption and/or generation).
On screen the words “SET QuAd” appear
(2=Power consumption / 4=consumption and
generation)
4.6.- Setting the Power demand meter:
a) Electrical parameter to control: ("SET Pd Code"):
None
00
Three-phase active power
kW III
16
Three-phase apparent power
kVA III
34
Three-phase current
AIII
36
Current per phase
A1-A2-A3
A-ph
Integrated parameter value according to the set period.
b) Integration period (1….60 minutes): ("Pd Per 15")
c) Clear maximum value recordings of Pd: ("CLr Pd
no”) “no” or “YES”.
4.7.- Setting display or omitting screens
This option allows the page display format to be
displayed ("dEF Page YES / no”):
I.YES | Standard: se all electrical parameters are
displayed.
II.no | Custom: by using the “YES” or “no” option the
pages to be displayed when the equipment is on
are selected.
4.8.- Setting the start screen
This option allows select the screen and selection
mode of display screens (“SET iniT page”):
I.Fixed page: selects which page from the possible
pages will appear first when applying voltage (or
on RESETTING) to the CVM-MINI -Ethernet .
II.Rotating pages: selecting rotating pages (when all
of the electrical parameters flash), automatically
rotates, every 5 seconds it moves on to the
following screen.
CVM-MINI-Ethernet
M98240101-03-18A
4.9.- Setting the “backlight” disconnection
time
("diSP oFF”): Setting the time in seconds, after which
the light on the CVM-MINI -Ethernet display switches
off (low consumption) after a key is pressed. If 00 is set,
the backlight is permanently on.
4.10.- Returning the energy counters to zero
"CLr EnEr" “YES” or “no” (Clear energy counters) appears
on the display.
4.11.- Setting THD or d
Two types of Harmonic distortion can be set ("SET HAr
d"):
-d%: value harmonic distortion with respect to the
fundamental.
-Thd %: value harmonic distortion with reference to
the effective value (RMS).
4.12.- Additional screen with transistor alarm
outputs
(“Out 1 CodE
” / “
Out 2 CodE”) With these outputs the
CVM-MINI-Ethernet transistor output is set for:
I.Impulse every nkW.h or kvar.h (Energy): The
value in kW.h is set corresponding to one impulse
(100 msec long.): kW.h / 1 impulse or kvar.h / 1
impulse. Maximum 5 imp/sec. (see variable
codes).
II.ALARM conditions: each output is set per
transistor the variable to be controlled, the
maximum value, minimum value and the (delay)
(see variable codes).
Note:The list of variable appears in the table below.
5.- CVM-MINI-Ethernet Blocking SET UP
This menu allows to block the setup parameter to avoid
changes. To access to this menu:
Press the
resetN
key and pressing the
Nsetup
key
for five seconds until Set-Up is entered.
Briefly appear on the display “set up init” and afther
“Set up” with the option::
Unlo Allows configuration of the device parameters
using the keypad.
Loc Bloquea la configuración de los parámetros del
equipo mediante el teclado.
If the Loc, option is selected, it is only possible to see
the setting on entering SETUP and the changes are
not allowed.
To select this options press
max
NOTE: to disable the unlock mode enter the password
1234 when asked.
If a previously set option is to be changed, then it is
necessary to enter a password. PASSWORD CVM-
MINI -Ethernet 1234.
6.- CVM-MINI-Ethernet COMMUNICATIONS
One or more analysers CVM-MINI-Ethernet can be
connected to a "router" or "switch" Ethernet and access
their information through a PC connected to the same
Ethernet local area network. This system allows
centralizing data on a single registration point (Studio ®
Power System).
To change the communication settings see section 2.
The network analyzer type CVM-MINI-ETHERNET
communicates using MODBUS TCP © (Pulling
Question / Answer).
7. - LIST OF VARIABLES AND ALARMS CODES FOR THE CVM-MINI -
Ethernet
If no variable is required enter No. par.= 00.
Parameter
Symbol
L1 Code
L2 Code
L3 Code
Voltage (phase-neutral)
V
01
06
11
Current
A
02
07
12
Active power
kW
03
08
13
Reactive power -(Ind/Cap)
kvar
04
09
14
Apparent power
kVA
38
39
40
Power factor
PF
05
10
15
% THD V
THD V
25
26
27
% THD A
THD A
28
29
30
Parameter
Symbol
Code
Parameter
Symbol
Code
Three-phase active power
kW III
16
Neutral current
IN
37
3 pha. inductive power
kvarL III
17
Max demand (L1)
Md (Pd)
35*
3 pha. capacitve power
kvarC III
18
Max demand (L2)
Md (Pd)
42*
cos ϕthree-phase
cos
ϕ
19
Max demand (L3)
Md (Pd)
43*
3 pha. power factor
PF III
20
Active energy
kW.h III
31
Frequency (L1)
Hz
21
Inductive reactive energy
Kvar·h L III
32
V phase phase L1- L2
V 12
22
Capacitive reactive energy
Kvar·h C III
33
V phase phase L2 - L3
V 23
23
Apparent energy
KVA·h III
44
V phase phase L3 - L1
V 31
24
Active energy generated
Kw·h III -
45
Apparent power
kVA III
34
Inductive energy generated
Kvar·h L III -
46
Maximum demand
Md (Pd)
35
Capacitive energy generated
Kvar·h C III -
47
Three-phase current
AIII
36
Apparent energy generated
KVA·h III -
48
Temperature
ºC
41
*Variables only valid if the Maximum Demand for current has been set per phase.
There are also some variables that refer to the three-phases at the same time. If one
of these variables has been selected, the alarm will go off when any of the three-
phases meet the preset conditions.
Parameter
Symbol
Code
Parameter
Symbol
Code
Voltages (phase-neutral)
V1 or V2 or V3
90
Power factors
PF1 or PF2 or PF3
94
Currents
I1 or I2 or I3
91
Voltages (phase-phase)
V12 or V23 or V31
95
Active powers
kW1 or kW2 or kW3
92
% THD V
THDV1 or V2 or V3
96
Reactive powers
kvar1 or kvar2 or kvar 3
93
% THD I
THDI1 or I2 or I3
97
Apparent powers
kVA1 or kVA 2 or kVA 3
98
8. - FOUR QUADRANTS OF THE CVM-MINI -Ethernet
0º
90º
180º
-90º
Consumed
Power
Generated
Power
Single Phase
KW +
Kvar +
P.F +
Single Phase
KW +
KvarC -
P.F -
Single Phase
KW -
Kvar -
P.F -
Single Phase
KW -
KvarL+
P.F +
Three Phase
KW III +
KVA III +
KvarL III +
Three Phase
KW III +
KVA III +
KvarC III +
Three Phase
KW III -
KVA III -
KvarC III-
Three Phase
KW III -
KVA III -
KvarL III -
Capacitive
Inductive
Inductive
Capacitive
CVM-MINI-Ethernet
M98240101-03-18A
9.- TECHNICAL FEATURES
Power supply circuit:
-Single-phase:
-Voltage tolerance:
-Frequency:
-Maximum consumption:
-Operating temperature:
-Humidity (without condensation):
AC. version
230 V AC.
-15 % / +10 %
50 - 60 Hz
3,0 VA
-10ºC …..+ 50ºC
5% ….. 95%
Plus version: AC. & DC.
85..265 V AC./ 95..300V DC.
50 - 60 Hz (AC. mode)
3,0 VA
-10ºC …..+ 50 º C
5% ….. 95%
Measurement circuit:
-Rated voltage: phase-neutral / between phases
-Frequency:
-Rated current:
-Permanent overload:
-Power consumption voltage circuit:
-Power consumption current circuit: ITF / Shunt
300 V AC. / 520 V AC.
45 ~ 65 Hz
ITF In/ 5A-1A
1.2 In
0.7 VA
0.18 VA
Mechanical features:
-Casing material:
-Protection:
Assembled equipment (front):
Non assembled equipment (sides and rear cover):
-Dimensions (mm):
-Weight:
-Voltage measure and supply wires:
-Secondary current transformers wires:
-Maximum altitude:
Self extinguishing V0 plastic
IP 51
IP 31
85 x 52 x 70 mm (3 step)
0.210 kg
Minimum section 1 mm²
Minimum section 2,5 mm²
2.000 m.
Output transistors features
-Type: Opto-islolated transistor (open collector).
-Maximum operating voltage:
-Maximum operating current:
-Maximum frequency:
-Impulse length:
NPN
24 V DC.
50 mA
5 impulses / second
100 ms
Ethernet connexion
Internal WEB for Ethernet setup.
IP address assignment by DHCP or name
Password access protection
RJ45 connection
Left LED Connector Indicator. Link Status:
Right LED Connector Indicator 10M/100M:
Standard IEEE802-3u
Greem FULLDUPLEX
Ambar HALFDUPLEX
Green 100 Mb/s
Ambar 10 Mb/s
Accuracy class:
-Voltage:
-Current :
-Power / Energy:
Measurement loggers: Current / Voltage
Power factor:
Scale range measurement margin: ITF / Shunt
Temperature sensor: Accuracy / Operating window
-Tª measurement: Without / with forced ventilation
0.5 % ± 1 digit
0.5 % ± 1 digit
0.5 % ± 1 digit
External transformers / direct voltage
0.5 to 1
0.2 % ..... 120 % / 2 % ..... 120 %
± 2ºC / -10ºC ….. +50ºC
+ 14.0 ºC / + 3.5 ºC
Safety:
Category III - 300 V AC. / 520 AC. EN-61010 Class II double insulation against
electric shock
Standards:
IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-6-3,
EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 55011
10.- CONNECTIONS
4 wire / 3 wire (low voltage)
Detail of MC3 connection
Detail of MC1 connection - 4 wire / 3 wire
S2
P2
S1
P1
L1
L2
L3
N
S2
P2
S1
P1
S2
P2
S1
P1
N
Alimentacion
Power Supply
S2
P2
S1
P1
L1
L2
L3
N
S2
P2
S1
P1
S2
P2
S1
P1
N
Alimentacion
Power Supply
In case of using transformes type MC1, the selected relation
must be the same in the three transforming and must be agree
with the programmed in the CVM-MINI-MCEthernet-C2
11.- TECHNICAL SERVICE
In the event of any equipment failure or any operational queries please contact the technical service of CIRCUTOR.
CIRCUTOR, S.A. - Technical Assistance Service (S.A.T)
Vial Sant Jordi, s/n
08232 -Viladecavalls (Barcelona)
Tel.: (+34)93 745 29 19
Fax - 93 745 29 14
E-mail : s[email protected]

This manual suits for next models

2

Other Circutor Measuring Instrument manuals

Circutor CVM-C4 Series User manual

Circutor

Circutor CVM-C4 Series User manual

Circutor AR5-L User manual

Circutor

Circutor AR5-L User manual

Circutor DM45 AD User manual

Circutor

Circutor DM45 AD User manual

Circutor CVM-C11 User manual

Circutor

Circutor CVM-C11 User manual

Circutor DCP-96 Aac User manual

Circutor

Circutor DCP-96 Aac User manual

Circutor DM45 V User manual

Circutor

Circutor DM45 V User manual

Circutor Wibeee Max User manual

Circutor

Circutor Wibeee Max User manual

Circutor CVM-C10 User manual

Circutor

Circutor CVM-C10 User manual

Circutor CVM-NET4+-MC User manual

Circutor

Circutor CVM-NET4+-MC User manual

Circutor DCB-72 Aac User manual

Circutor

Circutor DCB-72 Aac User manual

Circutor M20951 User manual

Circutor

Circutor M20951 User manual

Circutor GETEST MPC-5 User manual

Circutor

Circutor GETEST MPC-5 User manual

Circutor Wibeee Max Plus User manual

Circutor

Circutor Wibeee Max Plus User manual

Circutor CEM-C31-T1 User manual

Circutor

Circutor CEM-C31-T1 User manual

Circutor CEM-C12c User manual

Circutor

Circutor CEM-C12c User manual

Circutor CVM-B100 User manual

Circutor

Circutor CVM-B100 User manual

Circutor DHC-96 Aac User manual

Circutor

Circutor DHC-96 Aac User manual

Circutor CVM-C5 Series User manual

Circutor

Circutor CVM-C5 Series User manual

Circutor CVM-C11 User manual

Circutor

Circutor CVM-C11 User manual

Circutor CVM-B100 User manual

Circutor

Circutor CVM-B100 User manual

Circutor T-3V User manual

Circutor

Circutor T-3V User manual

Circutor DM45 A User manual

Circutor

Circutor DM45 A User manual

Circutor MYeBOX 150 User manual

Circutor

Circutor MYeBOX 150 User manual

Circutor AR5-L User manual

Circutor

Circutor AR5-L User manual

Popular Measuring Instrument manuals by other brands

PQ Plus UMD 707 Quick start manual

PQ Plus

PQ Plus UMD 707 Quick start manual

Fluke 3210-PR instruction sheet

Fluke

Fluke 3210-PR instruction sheet

YOKOGAWA FLXA402T user manual

YOKOGAWA

YOKOGAWA FLXA402T user manual

Simex SRP-73-XC user manual

Simex

Simex SRP-73-XC user manual

BRONKHORST MASS-STREAMT D-6300 instruction manual

BRONKHORST

BRONKHORST MASS-STREAMT D-6300 instruction manual

Norsonic nor103 instruction manual

Norsonic

Norsonic nor103 instruction manual

Fluke 726 Manual supplement

Fluke

Fluke 726 Manual supplement

ETC PENKO SGM800 manual

ETC

ETC PENKO SGM800 manual

Refco REF-VAC Installation and operating guide

Refco

Refco REF-VAC Installation and operating guide

RS PRO DT-388 instruction manual

RS PRO

RS PRO DT-388 instruction manual

Tenmars TM-206 user manual

Tenmars

Tenmars TM-206 user manual

NLS FM-7 instruction manual

NLS

NLS FM-7 instruction manual

Bosch Professional GLM 50-23 G Original instructions

Bosch

Bosch Professional GLM 50-23 G Original instructions

Dakota Digital HLY-3027 manual

Dakota Digital

Dakota Digital HLY-3027 manual

Observator Instruments NEP-9500 Series user manual

Observator Instruments

Observator Instruments NEP-9500 Series user manual

Campbell CNR4 product manual

Campbell

Campbell CNR4 product manual

Triplett AM320-NIST user manual

Triplett

Triplett AM320-NIST user manual

Silverline 250582 quick start guide

Silverline

Silverline 250582 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.