
UK Instruction Sheet Template – V1.1 – Updated: 20/11/2020
The CLP Cleverfit Pro Dynamic Green can be installed either Ceiling or Wall Mounted. The CLP Cleverfit
Pro Dynamic Green uses a “slide connect bracket base” that is mounted and wired into position first. The
main body can be installed once the base is wired or later to avoid damage during the construction phase.
Please follow the steps below to install the CLP Cleverfit Pro Dynamic Green Exit:
•Disengage the slide connect bracket from the exit body. Position the base in the mounting position.
•Using the bracket as a guide, mark 2 holes for mounting and one for mains access. Then install the
bracket using appropriate fixings (not supplied).
•Remove the Terminal Block Cover.
•Route the AC power and 24/VF control cables through the access hole and connect to the terminal
block as shown below.
•Reinstall the terminal block cover.
•Install the exit fitting to the slide bracket.
Dynamic Green 24 Volt (24V)/Volt Free (VF) Operation and Testing
Activation of the Dynamic Green is controlled via 24V/VF control interface. The fitting comes pre-set as
normally OFF. This is switched via an intelligent circuit inside the fitting. This is controlled by the 24V/VF
input from a fire panel or other source. If you would like to change the activation of the Dynamic Green
from Normally OFF to Normally ON change the Dip Switch no.6 on the Main LED Board (found under
the Running Man diffuser) to 0.
NOTE: For the Dip Switch setting to take effect the power and battery will need to be disconnected and
reconnected.
For –SND products this operation is set depending on the part number ordered and cannot be changed
by user.
Selecting the Type of the Interface
The fitting comes pre-set to the Volt Free (VF) control interface, to change this to 24V you will have to
change the jumper on J1 from 1-2 (Image below) to 2-3 on the Contact board found next to battery
compartment. Please see image below.
Zoneworks, HIVE and DATA Monitored Options
Fittings with part numbers -ZW, -HVG, -DATA are fitted with Zoneworks communications modules
(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power
cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated
data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also
be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor,
coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a
single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides
a multifunction indication of the status of the fitting during testing and normal operation:
ZW, DATA Un-commissioned Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
HVG Un-commissioned
With network connectivity
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
HVG Un-commissioned
Without network connectivity
Batt plugged-in: yellow 250mS, green
250mS, yellow 250mS, green 250mS,
green 1s
Batt unplugged: red 250mS, off
250mS, red 250mS,off 250mS, off 1s
Emergency Light Test In Progress
LED flashes at yellow 5s , 0ff 1s
Emergency Light Test In Progress
LED flashes at yellow 1s , 0ff 1s
In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The Li-ion battery in the Exit & Emergency Unit has been selected to give
excellent long life performance in a controlled IEC 60598-2-22 testing environment. Excessive battery
cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty
claims, as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Cable Entry Point – Inside of bracket for ceiling mount, 20mm diameter, located in centre of bracket. Bracket shown
with the terminal block cover removed.