10 Geothermal Heat Pump Systems
by the Programmed Demand Reduction option
selected below.
NOTE: The thermostat must be configured for
programmable mode by installer to access the
Programmed Demand Reduction settings.
5.6.5.5.1 PROGRAMMED DEMAND
REDUCTION MODE
Through Programmed Demand Reduction
Mode, you can set the unit’s limited operation
during the Programmed Demand Reduction
schedule.
Adjust the Programmed Demand Reduction
Mode settings using the up/down arrow buttons.
Press the center button to save changes.
• No Demand Reduction (default): During
the scheduled Programmed Demand
Reduction time (section 5.6.5.5.4), the
system operates normally based on the
setpoints.
• No Auxiliary Heat: During the scheduled
Programmed Demand Reduction time
(section 5.6.5.5.4), auxiliary heat will not
be activated, regardless of the heating
demand.
• No 2nd Stage Compressor: During the
scheduled Programmed Demand Reduction
time (section 5.6.5.5.4), the compressor
is limited to only part load (1st stage)
operation and auxiliary heat is turned off,
regardless of system demand.
NOTE 1: The thermostat must be configured for
auxiliary heat by installer to access the Demand
Reduction NO AUXILIARY HEAT option.
NOTE 2: The thermostat must be configured
for Multistage by installer to access the Demand
Reduction NO 2nd STAGE COMP option.
5.6.5.5.2 Climadry™ - PROGRAMMED
DEMAND REDUCTION
This option allows for the customization
of Climadry™ (Dehumidification, optional)
operation during the Programmed Demand
Reduction schedule.
Adjust the Programmed Demand Reduction
Climadry™ settings using the up/down arrow
buttons. Press the center button to save
changes.
• Suspend Climadry™ (default): During the
scheduled Programmed Demand Reduction
time (section 5.6.5.5.4), Climadry™ is
turned off, regardless of the dehumidification
demand.
• Allow Climadry: During the scheduled
Programmed Demand Reduction time
(section 5.6.5.5.4), Climadry™ will operate
normally.
NOTE: The thermostat must be configured
for humidity control by installer and the DXM2
must be configured for Climadry™ operation to
access Demand Reduction Climadry™ settings.
5.6.5.5.3 FAN - PROGRAMMED DEMAND
REDUCTION
This option allows for the customization of
fan settings during the Programmed Demand
Reduction schedule.
Adjust the Programmed Demand Reduction
Fan settings using the up/down arrow buttons.
Press the center button to save changes.
• Auto Fan Only (default): During the
scheduled Programmed Demand Reduction
time (section 5.6.5.5.4), only auto fan mode
is allowed.
• Allow Continuous Fan: During the
scheduled Programmed Demand Reduction
time (section 5.6.5.5.4), the fan will operate
normally.
5.6.5.5.4 SCHEDULE - PROGRAMMED
DEMAND REDUCTION
This option allows setting a 7-day time schedule
for Programmed Demand Reduction.
Adjust the Programmed Demand Reduction
Schedule start and end time settings using
the up/down arrow buttons in increments of
10 minutes. Press the center button to save
changes.
NOTE: To disable Programmed Demand
Reduction, set the Start time equal to the End
time for that day.
5.6.6 INTERMITTENT FAN
Intermittent Fan function allows the fan to run
periodically when the heating/cooling equipment is
off. Many times this functionality is used to improve
the performance of air cleaning or special filtration
systems.
When the Intermittent Fan function is active, the fan
output will be activated for the currently selected
Intermittent Fan On Time, and then operate using
the selected Intermittent Fan Off and On times until a
heating or cooling operation is activated again.
After the heating or cooling operation is complete,
the intermittent fan operation will resume with the
beginning of a new Intermittent Fan On Time on the ¼
hour.
• On Time (default Off): options: Off, 5 to 20
minutes (in 5 minute increments)