COMECO RT1800 User manual

1
UNIVERSAL PID CONTROLLER
RT1800
Operation Manual
Please read this Operation Manual before mounting and operating!
Save the Manual for future references!
COMECO Inc., P.O.Box 378, 4000 Plovdiv, Bulgaria
tel. +359 32 646523, 646524; fax +359 32 634089
e-mail: info@comeco.org, WWW.COMECOGROUP.COM
v12-02.11

2
CONTENTS
1. APPLICATION .................................................................................................. 3
2. TECHNICAL SPECIFICATIONS ....................................................................... 3
3. OPERATION ..................................................................................................... 5
3.1. General programming sequence .......................................................... 5
3.2. Switching among parameter levels ..................................................... 5
3.3. Parameter adjustment ........................................................................... 5
3.4. Controller programming ....................................................................... 6
3.4.1. Level 1: "Main parameters" - Set point, alarms,
auto-tuning, manual control .............................................................. 6
3.4.2. Level 2: "PID (ON/OFF) parameters
and access to the other levels".......................................................... 7
3.4.3. Level 3: "Additional parameters" - input type,
control algorithm type, alarm type and parameters,
calibration and others ..................................................................... 10
3.4.4. Level 4: "Configuration level" - parameter enabling,
input and output configuration ........................................................ 14
4. APPENDICES ................................................................................................. 16
4.1. Input type and range codes................................................................. 16
4.2. Alarm type and function ..................................................................... 17
4.3. Error messages .................................................................................... 17
4.4. Linear input adjustment ...................................................................... 19
4.5. Analog output adjustment................................................................... 19
4.6. RAMP-SOAK adjustment .................................................................... 20
4.7. Profile (pattern) control programming ............................................... 20
5. MOUNTING AND WIRING............................................................................... 22
5.1. Mounting ............................................................................................... 22
5.2. Wiring .................................................................................................... 22
5.3. Input type selection ............................................................................. 23
5.4. Electro-magnetic interference (EMI) issues ..................................... 24
6. SERIAL INTERFACE ....................................................................................... 24

3
1. APPLICATION
RT1800 is a compact, multifunctional all-purpose microprocessor controller. Its user-configurable analog input
allows on-site adaptation to various thermocouple and RTD sensors as well as current and voltage output
transducers for pressure, relative humidity, flow, etc. The RT1800 controller may be ordered with a second
analog input for cascaded operation or remote set-point setting.
A set-point profile control is an additional option.
The device may be equipped with up to 4 relay and/or analog outputs that may serve as control outputs,
limit comparators, alarm outputs, etc. The built-in timer may be programmed to fully control one of the output
relays providing convenient delay at start-up.
The controller offers all standard PID features including bumpless auto/manual changeover. The two displays
─one for the process variable and another for the set point ─plus the control-action bar-graph allow all
necessary information to be read at a glance.
The optional digital interface, either RS232 or RS485, provides connection to an operator station driven
network as well as hierarchical control.
The switch-mode power supply provides for trouble-free operation under heavy mains voltage variations
(from 85 to 265 VAC).
The unit is specially designed to sustain the heavy electromagnetic disturbances that often arouse
in industrial environment by the means of optical decoupling of all inputs and outputs and special noise
suppression circuits.
2. TECHNICAL SPECIFICATIONS
2.1. Indication: LED, IP56
Indication
Case PV Display SV Display Bar-graph LEDs
'B'
'Q'
4 red digits,
14 mm high
"MEASURED value"
4 green digits,
10 mm high
"SET POINT value"
'H' / 'V'
10-point,
yellow,
0...100%
OUT1 control
8 LEDs for:
outputs OUT1 and OUT2 (green);
alarms AL1, AL2, AL3 (red);
auto-tuning AT (yellow);
manual control MAN (yellow);
profile control PRO (yellow)
'S'
4 red digits,
8 mm high
"MEASURED value"
4 green digits,
8 mm high
"SET POINT value" none 6 LEDs (no LEDs for AL3 and MAN)
2.2. Keyboard: membrane, IP56
Keys and functions
Case SET WSTA/M
'B'
'H' / 'V'
'Q'
Manual/
Auto
'S'
setting
parameter value;
displaying
next parameter;
level switching
starting parameter value
adjustment;
selecting digit
increasing value decreasing value
no manual
control

4
2.3. Power supply: switch-mode
Supply voltage: 85...265 VAC
Consumption: less than 4 VA
2.4. Inputs:
2-wire - for voltage and current signals; 3-wire - for resistive signals.
2.4.1. Main input: universal, programmable
For available sensor types and input ranges ─see Appendix 4.1.
2.4.2. Auxiliary input (option): linear current, 0(4)...20 mA
Serves for remote set point or for valve position control feedback. For cases 'B',
'H', and 'V' is feasible only with absence of interface. For case 'S' ─feasible only
with absence of retransmission analog output and interface. For case 'Q' ─
mounted instead of output AL2.
2.5. Outputs: max. 4 (3 for case 'Q')
2.5.1. Relay outputs: 2 control and 2 alarm or 1 control and 3 alarm
(2 control and 1 alarm or 1 control and 2 alarm for case 'Q')
Description Parameters Location
electromechanical relay max. 3 A / 250 VAC
solid state relay (SSR) max. 1 A / 250 VAC
MOS gate max. 0.1 A / 60 V
output for external SSR 24 V, 20 mA
OUT1, OUT2, AL1, AL2
2.5.2. Analog outputs: max. 3 (2 control + 1 retransmission)
Description Parameters Location
control (0)4…20 mA, 0...10 V instead of OUT1 or OUT2
retransmission (0)4…20 mA, 0...10 V instead of AL2
For case 'S', the retransmission output is feasible only with absence of interface
or instead of AL1.
2.5.3. Serial interface (option): RS232 or RS485
For cases 'B', 'H', and 'V' ─feasible only with absence of auxiliary input.
For case 'S' ─only with absence of retransmission analog output or instead of AL1.
2.6. Operating conditions
Operating temperature / humidity 0...50 °C / 20...85% RH
Protection, front / rear IP56 / IP20
Maximum temperature drift 0.01% from span for 1 °C
Maximum warm-up time 15 min
2.7. Storage conditions
Temperature / humidity -20...65 °C / 0...95% RH

5
3. OPERATION
3.1. General programming sequence
Controller parameters are grouped in 4 levels (parameter groups) according to their frequency of use.
The following order of parameter programming is recommended:
1. Enter level 2 and set the parameter LCK= 1111 to get access to level 4.
2. Enter level 4 to configure basic controller settings (input and output number and use, which
parameters of the other levels will be available for adjustment and which will be hidden ...).
3. Switch back to level 2 and set the parameter LCK= 0000 to get access to level 3.
4. Enter level 3 and set its parameters (input type, alarm type, output action direction ...).
5. Enter level 2 and set preliminary values for the PID (ON/OFF) parameters (proportional gain,
hysteresis …).
6. Enter level 1 and adjust the set point, alarm limits, etc.
7. When the controller is already mounted in place and the system starts functioning, readjust
PID (ON/OFF) control parameters to achieve satisfactory system performance.
8. Switch over to level 2 and set the parameter LCK= 0001 or 0101 to prevent unauthorized
personnel from changing vital controller parameters (level access locking).
3.2. Switching among parameter levels
Normally, the controller operates at level 1 and shows the set-point value on its lower display
and the measured value ─on the upper display.
Switching over to level 1 may be done in either of the following ways:
•Automatically, when no key has been pressed for 1 minute, regardless of the level.
•By using the A/M key, regardless of the level.
•Automatically, after power-on. At start-up, the input type and range appear consecutively on the display,
followed by the measured value and the set point from level 1.
•Automatically, after exiting level 2, 3, or 4.
Entering level 2:
•While the device operates at level 1, press and hold SET for 5 seconds.
Exiting level 2 may be done in either of the following ways:
•By holding SET depressed for 5 seconds.
•By pressing A/M. Mind that this also toggles between AUTO and MANUAL modes. Does not function
while parameter value is being adjusted (finish parameter adjustment first by pressing SET).
To get access to level 3, set LCK= 0000 from level 2 beforehand.
To get access to level 4, set LCK= 1111 from level 2 beforehand.
Switching over to level 3 or 4:
•While the device operates at level 1 or 2, press and hold SET and Wfor 5 seconds.
Exiting level 3 or 4 may be done in either of the following ways:
•By holding SET and Wdepressed for 5 seconds.
•By pressing A/M. Mind that this also toggles between AUTO and MANUAL modes. Does not function
while parameter value is being adjusted (finish parameter adjustment first by pressing SET).
If, after parameter adjustment at level 4, the device expects readjustment at levels 2 and 3, the value
of the parameter LCKautomatically changes to 0000.
3.3. Parameter adjustment
•Display the parameter symbol on the upper (red) display and the current value on the lower (green) display.
•Press Wto enter parameter value adjustment mode. The rightmost digit starts blinking. To select
another digit, use W. To increase or decrease the blinking digit value, use respectively Sor T.

6
•Press SET to confirm the adjusted value and exit parameter value adjustment mode.
•To display the next parameter in the row, press SET.
3.4. Controller programming
Automatic PID control parameter tuning (Auto-tune)
Before starting the Auto-tune function, ensure the controller is properly installed, the system is functional,
and the main parameters from levels 3 and 4 are already adjusted. The auto-tuning function automatically sets
the values of the following parameters: P1, i1, db1, GAP1, P2, i2, d2. The operator must set
manually the duration of the on/off output relay cycle CYt1, CYt2. For current output ─set to 0, for relay
output ─try with 10.
a) Set the parameter At to YES.
b) Set a temporary automatic decrease of the set point during auto tuning via the AtVLparameter.
With AtVL = 0, the tuning process will be performed around the set point. With AtVL = 5°C
and set point SV = 200 °C, the auto-tuning will be performed around 195 °C (this avoids overheating
due to the process variable cycling during the auto-tuning process). If in doubt, set AtVL = 0.
c) Unsuccessful auto-tuning. Possible reasons are:
•Too high AtVL value (if in doubt, set to 0).
•Great system inertia. Set PID parameters manually.
3.4.1. Programming at LEVEL 1
Normally, the controller is at level 1 and displays the measured value. To view the next parameter
from this level, press SET.
95 PV Measured value
100 SV Set point
↓SET
OUtL In manual mode: output value in percents from 0 to 100%
100 In auto mode scales down control output; it is recommended to keep the value = 100%
↓SET
At Enable/disable auto-tuning
YES / nO See "Automatic PID control parameter tuning (Auto-tune)" above
↓SET
AL1 Alarm 1 limit
0
↓SET
AL2 Alarm 2 limit
0
↓SET
AL3
(
rAMP
)
Alarm 3 limit (Ramp slope)
0
↓SET
over again
!With OUtL = 0during PID control, the output is switched off.
To achieve proper output operation in AUTO mode, set OUtL = 100.

7
3.4.2. Programming at LEVEL 2
Normally, the controller is at level 1 and displays the measured value. To switch over to level 2, press and
hold SET for 5 seconds. To switch back to level 1, depress SET again.
P1 Proportional band for main control output OUT1
3 Range: 0 to 200%.
↓SET Great values correspond to small proportional gain;
value 0 sets ON/OFF control
i1 Integration time (reset time) for main control output
240 Range: 0 to 3600 s
↓SET value 0 turns integration off
d1 Derivative time for main control output
60 Range: 0 to 900 s
↓SET value 0 turns differentiation off
db1 Dead-band time for main output
0 Range: 0 to 1000 s
↓SET If in doubt, set to 0
AtVL Set-point shift during auto-tuning
0 Range: 0 to USPL
↓SET If in doubt, set to 0
CYt1 output ON / OFF period duration for the main output OUT1
(total time of both ON and OFF periods during PID control)
10 Range: 0 to 150 s
↓SET In case of SSR ─set to 0, with mechanical relay─try with 10
HYS1 Hysteresis for main output
(visible only if P1 = 0, i.e. ON/OFF control)
1 Range: 0 to 1000
↓SET Small values result in lower cycling range, but much frequent output switching
P2 Proportional band for second control output OUT2
3 Range: 0 to 200%
↓SET As for P1
i2 Integration time (reset time) for second control output
240 Range: 0 to 3600 s
↓SET As for i1

8
d2 Derivative time for second control output
60 Range: 0 to 900 s
↓SET As for d1
CYt2 output ON / OFF period duration for the second output OUT2
(total time of both ON and OFF periods during PID control)
10 Range: 0 to 150 s
↓SET As for CYt1
HYS2 Hysteresis for second output
1 Range: 0 to 1000
↓SET As for HYS1
GAP1 Dead band for main output OUT1 (only for two-output controllers)
0 Sets a gap before the set point, in which the output is inactive
↓SET If in doubt, set to 0
GAP2 Dead band for second output OUT2 (only for two-output controllers)
0 As for GAP1
↓SET If in doubt, set to 0
LCK Level access control (parameter locking)
0000 See explanation below
↓SET
over again

9
Level access control (parameter LCK)
LCK =0100 - levels 1 and 2 are accessible, and their parameters may be adjusted;
LCK =0110 - levels 1 and 2 are accessible, but only the parameters from level 1 may be adjusted;
LCK =0001 - levels 1 and 2 are accessible, but their parameters (except for set point) may not
be
adjusted;
LCK =0101 - only level access control parameter may be adjusted.
The level access control parameter may always be adjusted.
LCK =0000 allows access to level 3 (from level 2, press and hold SET иWfor 5 s)
LCK =1111 allows access to level 4 (from level 2, press and hold SET иWfor 5 s)
Proportional band (parameters P1 and P2)
The relation between the proportional band P and the proportional gain KPis as follows:
KP= 10 000 / ( P * INPUT_RANGE ),
KP[%/°C] is the proportional gain, P[%] is the proportional band,
INPUT_RANGE [°C] is the input range high limit (e.g. with input range -200...400 °C,
INPUT_RANGE = 400)
Relationship between PID input and output
when both integration and differentiation are switched off
PID control internal structure

10
3.4.3. Programming at LEVEL 3
To access level 3, first set LCK =0000 from level 2. To enter level 3, press and hold SET and W
for 5 seconds. To switch back to level 1, depress SET and Wagain.
inP1 Input type selection – sensor type and range
K2 select input range and type
↓SET See Appendix 4.1. Input type and range codes. Switching from T/C (voltage) to RTD input type
or vice-versa requires hardware adjustment (see 5.3).
AnL1 Zero adjustment of the analog input for the main output
0 Range: LSPL to USPL
↓SET Makes sense only when the selected input type code is among An1 ... An5
See Appendix 4.4. Linear input adjustment
AnH1 Span adjustment of the analog input for the main output
5000 As for AnL1
↓SET See Appendix 4.4. Linear input adjustment
dP Measured value decimal point position (display accuracy)
0000 Sets decimal point position
↓SET
LSPL Low limit for measured value and set point
)0 Sets low limit for measured value and set point (narrows input range)
↓SET With linear input, sets display value at low limit of the input range (e.g. 2 Bar for 4 mA)
USPL Higher limit for measured value and set point
40)0 Sets higher limit for measured value and set point (narrows input range)
↓SET With linear input, sets display value at high limit of the input range (e.g. 16 Bar for 20 mA)
AnL2 Zero adjustment of the analog input for the second output
0 Range: LSPL to USPL
↓SET Makes sense only when the selected input type code is among An1 ... An5
AnH2 Span adjustment of the analog input for the second output
5000 As for AnL2
↓SET

11
Alarm AL1 type
01 Range: 00 to 19 (See Appendix 4.2. Alarm type and function)
↓SET
ALt1 Delay of alarm AL1 activation in profile control mode
0 Range: 0 to 99.59 min
↓SET 0 = flicker alarm, 99.59 = continued, other values = on-delay time
ALd2 Alarm AL2 type
01 Range: 00 to 19
↓SET
ALt2 Delay of alarm AL2 activation in profile control mode
0 Range: 0 to 99.59 min
↓SET 0 = flicker alarm, 99.59 = continued, other values = on-delay time
ALd3 Alarm AL3 type
01 Range: 00 to 19
↓SET
ALt3 Delay of alarm AL3 activation in profile control mode
0 Range: 0 to 99.59 min
↓SET 0 = flicker alarm, 99.59 = continued, other values = on-delay time
HYSA Alarm hysteresis
0 Range: 0 to 1000
↓SET
CL01 Calibration of the low limit of the main control output (in case of analog output)
150 Range: LSPL to USPL
↓SET See Appendix 4.5. Analog output adjustment
CH01 Calibration of the high limit of the main control output (in case of analog output)
3500 Range: 0 to 9999
↓SET See Appendix 4.5. Analog output adjustment

12
CL02 Calibration of the low limit of the second control output (in case of analog output)
150 Range: LSPL to USPL
↓SET
CH02 Calibration of the high limit of the second control output (in case of analog output)
3500 Range: 0 to 9999
↓SET
CL03 Calibration of the low limit of the retransmission output (in case of analog output)
As for CL01
↓SET
CH03 Calibration of the high limit of the retransmission output (in case of analog output)
As for CH01
↓SET
rUCY Full travel time of motor valve (w/o slide-wire position feedback)
00 Range: 0 to 150 s
↓SET
WAit WAIT - Waiting for the current segment to end after the time is up in profile control mode
0 0 = no waiting; other values = max. admissible diversion of PV from the set point, at reaching which
the segment may end
↓SET
SEtA Additional settings
0000 SETA.1/2/3=1 changes the relays AL1/2/3 action to reverse (NC)
SETA4.4=0 or 1 sets profile program RUN ALARM or END ALARM
↓SET
idnO ID number for serial communication
↓SET
bAUd Serial communication baud rate
2400 Range: 110 to 9600 bps
↓SET

13
SVOS Set-point shift
0 Range: -1000 to 1000
↓SET Unless there is a particular reason, it is recommended to set SVOS = 0
PVOS Measured-value shift
0 Range: LSPL to USPL
↓SET Convenient for calibration
UnIt Measurement unit for measured value and set point
C Range: C= °C, F= °F, A= analog input
↓SET
PVFt PV filter
1000 Smaller values result in faster reaction, greater values – in better filtering
↓SET Adjust the filtering to avoid flickering of input measurement
CASC (reserved)
↓SET
OUd Output action direction
HEAt HEAt = heating action of output OUT1 , cooL = cooling action of output OUT1
↓SET Correspond respectively to direct and reverse action.
The action of OUT2 is always the opposite of that of OUT1
OPAd Control algorithm
Pid Range: PID, Fuzzy
↓SET PID control incorporates PID Auto-tune and ON/OFF
Hz Power supply frequency
50 Range: 50 Hz or 60 Hz
↓SET
over again
Match local mains frequency!

14
3.4.4. Programming at LEVEL 4
To access level 4, first set LCK =1111 from level 2. To enter level 4, press and hold SET and W
for 5 seconds. To switch back to level 1, depress SET and Wagain.
The parameters from level 4 grant (1) and deny (0) access to parameters from levels 1, 2, and 3.
Other parameters from level 4 enable (1) and disable (0) certain controller functions.
Parameter symbols ─SEt0 ... SEt9 ─appear on the upper (red) display. To browse among
the parameters, use SET.
Each of the four digits of the lower (green) display grants/denies parameter access or enables/disables
function. Thereby, a single parameter (e.g. SEt1) with its four digits controls four parameters or functions.
0 = denies access to parameter / disables function, 1 = grants access to parameter / enables function
SEt1
0/1for
AL2
0/1for
AL1
0/1for
At
0/1for
OUtL
denies/grants access to parameters:
OUtL, At, AL1, AL2
↓SET
SEt2
0/1for
AnL2,
AnH2
0/1for
LSPL,
USPL
0/1for
AnL1,
AnH1,
dP
0/1for
AL3
denies/grants access to parameters:
AL3, AnL1, AnH1, AnH1, dP,
LSPL, USPL, AnL2, AnH2
↓SET
SEt3
0/1for
ALt2
0/1for
ALd2
0/1for
ALt1
0/1for
ALd1
denies/grants access to parameters:
ALd1, ALt1, ALd2, ALt2
↓SET
SEt4
0/1for
CL01,
CH01
0/1for
HYSA
0/1for
ALt3
0/1for
ALd3
denies/grants access to parameters:
ALd3, ALt3, HYSA, CL01, CH01
↓SET
SEt5
0/1for
idnO,
bAUd
0/1for
rUCY,
WAit,
HYSM
0/1for
CL03,
CH03
0/1for
CL02,
CH02
denies/grants access to parameters:
CL02, CH02, CL03, CH03, rUCY,
WAit, HYSM, idnO, bAUd
↓SET

15
SEt6
0/1for
SOFt
0/1for
Unit
0/1for
PVOS
0/1for
SVOS
denies/grants access to parameters:
SVOS, PVOS, Unit, SOFt
↓SET
SEt7
0/1for
Hz
0/1for
OPAd
0/1for
OUd
0/1for
CASC
denies/grants access to parameters:
CASC, OUd, OPAd, Hz
↓SET
SEt8
0
do not
change
0
do not
change
0
do not
change
0/1for
INVERT
sets transmit function in case of linear input
INVERT: 0= direct (e.g. 4...20 mA →0...100 °C);
1= reverse (e.g. 4...20 mA →100...0 °C)
0
do not
change
0/1for
START
0/1for
RESUME
0/1for
REPEAT
defines controller operation in profile mode (if available)
REPAEAT: 0= single execution of profile control program;
1= set point profile program repeats cyclically
RESUME: 0= program execution ceases at power dropout;
1= program execution resumes at power restore
START:0= program starts from zero;
1= program starts from currently measured value
↓SET
SEt9 retransmission output function
0/1for
RETRANSMIT
PV
0/1for
RETRANSMIT
SV
0/1for
TIME UNITS
X
do not
change
TIME UNITS: hh:mm(0)or mm:ss (1) - with pattern set point ONLY
RETRANSMIT SV: retransmits set point
RETRANSMIT PV: retransmits measured value
↓SET
SEt0
0/1for
REMOTE
SV
X
do not
change
REMOTE SV = 1 : set point is received from the second
input and is no longer set through keyboard
X: for RT1800-S, X = 0; for the rest of the cases, X = 1
these values determine standard PID control
↓SET
inP2 second input
0= none
↓SET
OUtY number of control outputs
0= one, 1= two fewer than the physically mounted control outputs may be set
↓SET
over again

16
4. APPENDICES
4.1. Input type and range codes (inP1)
TYPE CODE RANGE
K1 0.0 ÷ 200.0 oC
K2 0.0 ÷ 400.0 oC
K3 0 ÷ 600 oC
K K4 0 ÷ 800 oC
K5 0 ÷ 1000 oC
K6 0 ÷ 1200 oC
J1 0.0 ÷ 200.0 oC
J2 0.0 ÷ 400.0 oC
J3 0 ÷ 600 oC
J J4 0 ÷ 800 oC
J5 0 ÷ 1000 oC
J6 0 ÷ 1200 oC
r1 0 ÷ 1600 oC
R r2 0 ÷ 1769 oC
S1 0 ÷ 1600 oC
S S2 0 ÷ 1769 oC
B b1 0 ÷ 1820 oC
E1 0 ÷ 800 oC
E E2 0 ÷ 1000 oC
n1 0 ÷ 1200 oC
N n2 0 ÷ 1300 oC
t1 -199.9 ÷ 400 oC
T t2 -199.9 ÷ 200 oC
t3 0.0 ÷ 350.0 oC
W1 0 ÷ 2000 oC
W W2 0 ÷ 2320 oC
PL1 0 ÷ 1300 oC
PLII PL2 0 ÷ 1390 oC
U1 -199.9 ÷ 600.0 oC
U U2 -199.9 ÷ 200.0 oC
U3 0.0 ÷ 400.0 oC
TYPE CODE RANGE
L1 0 ÷ 400 oC
L L2 0 ÷ 800 oC
JP1 -199.9 ÷ 600.0 oC
JP2 -199.9 ÷ 400.0 oC
JIS JP3 -199.9 ÷ 200.0 oC
Pt100 JP4 0 ÷ 200 oC
JP5 0 ÷ 400 oC
JP6 0 ÷ 600 oC
dP1 -199.9 ÷ 600.0 oC
dP2 -199.9 ÷ 400.0 oC
DIN dP3 -199.9 ÷ 200.0 oC
Pt100 dP4 0 ÷ 200 oC
dP5 0 ÷ 400 oC
dP6 0 ÷ 600 oC
Jp1 -199.9 ÷ 600.0 oC
Jp2 -199.9 ÷ 400.0 oC
JIS Jp3 -199.9 ÷ 200.0 oC
Pt50 Jp4 0 ÷ 200 oC
Jp5 0 ÷ 400 oC
Jp6 0 ÷ 600 oC
AN1 An1 -10 ÷ 10 mV
1999 ÷ 9999
AN2 An2
0 ÷ 10 mV
0 ÷ 20 mA w/ 0.5 Ω*
1999 ÷ 9999
AN3 An3
0 ÷ 20 mV
0 ÷ 20 mA w/ 1 Ω*
1999 ÷ 9999
AN4 An4
0 ÷ 50 mV
0 ÷ 20 mA w/ 2.5 Ω*
1999 ÷ 9999
AN5 An5
10 ÷ 50 mV
4 ÷ 20 mA w/ 2.5 Ω*
1999 ÷ 9999
*A 0.5% tolerance resistor should be connected
in parallel with the input.
!If not specially requested, the input is factory configured to type K ( K2).
!To change the input type from thermocouple to RTD or vice-versa, open / close respective jumper pads
on the PCB (see detailed explanation bellow).

17
4.2. Alarm type and function
CODE ALARM TYPE SUPPRESSION
00/10 No alarm
01 Deviation from set point - high limit YES
11 Deviation from set point - high limit NO
02 Deviation from set point - low limit YES
12 Deviation from set point - low limit NO
03 Deviation from set point – low and high limits YES
13 Deviation from set point – low and high limits NO
04/14 Deviation from set point INVERTED – low and high limits NO
05 Exceeding absolute value YES
15 Exceeding absolute value NO
06 Falling below absolute value YES
16 Falling below absolute value NO
07 End of period (only for profile control) -
17 End of program (only for profile control) -
08 System error – alarm goes ON -
18 System error – alarm goes OFF -
09 Enables RAMP-SOAK function -
19 Timer alarm activated after predefined time -
* "suppression" means that after power-on, alarm action is suppressed until the alarm situation normalizes
at least for a moment. In this way, alarm activation is avoided while the system is reaching steady state.
Detailed alarm function diagrams are given on the next page.
4.3. Error Messages
in1E sensor open
AdCF * DAC failure
CJCE * input measurement circuit failure or
loose / missing cold junction temperature compensation sensor on controller back
in2E additional input open
UUU1 measured value above high set-point limit (parameter USPL)
nnn1 measured value below low set-point limit (parameter LSPL)
UUU2 additional input signal above high range limit
nnn2 additional input signal below low range limit
rAMF * RАМ failure
intF interface problem
AUtF unsuccessful auto-tuning
!When a message marked with " * " appears and stays, send the controller for repair.

18
no alarm
deviation from set-point high limit w/o suppression
deviation from set-point low limit w/ suppression
deviation from set-point low limit w/o suppression
deviation from set-point high and low limit w/ suppression
deviation from set-point high and low limit w/o suppression
deviation from set-point high and low limit
INVERTED w/o suppression
exceeding absolute value w/ suppression
exceeding absolute value w/o suppression
falling below absolute value w/ suppression
end of period (only for profile control)
a) set Ald1, Ald2, or Ald3 = 07
b) set Al1, Al2, or Al3 = period number
c) set Alt1, Alt2, or Alt3 =
0 - momentary action alarm
99:59 - constantly activated alarm (retentive)
other value = time of activation
falling below absolute value w/o suppression
started program (only for profile control)
PROGRAM
alarm activated at system error
NORMAL
SITUATION
SYSTEM
ERROR
NORMAL
SITUATION
SYSTEM
ERROR
alarm deactivated at system error
NORMAL
SITUATION
SYSTEM
ERROR
heater break alarm (only one line is monitored)
When PV=SV(soak), the timer begins to count.
When time is up, the relay of alarm module will
activate.
Range from 00:00 to 99:59 (hours:minutes)
SV (set point)
Alarm limit
deviation from set-point high limit w/ suppression

19
4.4. Linear input adjustment
When the device input is programmed as analog linear input, the correspondence between input voltage (current)
and displayed value may be specified. For instance, the correspondence may be from 10 mV input →0 oC
to 50 mV input →1000 oC. For this purpose, the following parameters are used: AnL1,AnH1, and dP.
The displayed range defined by AnL1, AnH1 should be within the allowed input range defined
by parameters LSPL and USPL. Sometimes the allowed input range needs to be extended first.
•Connect a calibrator to the controller analog input.
•From level 4, grant access to parameters AnL1,AnH1, and dP by setting SEt2 = ХХ1Х.
•Enter level 3 and select the desired range of the analog input by setting inP1 = AnX (see Appendix 4.1).
•Set the calibrator to generate a signal (voltage or current) corresponding to the lower end of the input range.
•From level 3, enter parameter value adjustment mode for AnL1 for the displayed value at the lower
end of the input range. Values appear on both displays. The value on the upper display is the measured
value that the device would display with the current input value. To make the adjustment, increase or
decrease the value on the lower display until the upper display shows the desired measured value to be
displayed in normal operation at lower input range.
•Set the calibrator to generate a signal (voltage or current) corresponding to the higher end of the input range.
•From level 3, enter parameter value adjustment mode for AnH1 for the displayed value at the higher
end of the input range. Values appear on both displays. Increase or decrease the value on the lower
display until the upper display shows the desired measured value to be displayed in normal operation
at higher input range.
•Repeat the last four steps until satisfactory correspondence is achieved at both input range ends.
•If necessary, from level 3, adjust the position of the display decimal point via dP.
4.5. Analog output adjustment
When the device has a linear output, it is factory tuned by default. If readjustment is necessary, follow this
procedure:
•For easier adjustment, switch to manual mode by pressing the А/Мkey (The MAN LED should light up).
•Connect a mA-meter to the controller analog output.
•From level 4, grant access to parameters CL01 and CH01 by setting SEt4 = 1ХХХ.
•From level 2, set to the parameter P1 a value other than zero. Set also CYt1 = 0.
•From level 1, set 0UtL = 0(minimum output value). At this moment, if factory setting is correct,
the output current should be 4 mA.
•If adjustment of the output setting is needed, from level 3, change the value of parameter CL01
for low control range limit. Increased / decreased the value, until the miliammeter reads 4 mA.
Try with CL01 = 0192.
ATTENTION: At an attempt to achieve currents lower than 2-3 mA, considerable nonlinearity appears,
since the device is designed for output 4...20 mA, and not for 0...20 mA.
•Set 0UtL = 100. At this moment, if factory setting is correct, the output current should be 20 mA.
•If adjustment is needed, from level 3, change the value of parameter CH01 for high control range
limit. Increased / decreased the value, until the miliammeter reads 20 mA.
Try with CH01 = 3096.
•Repeat the last four steps until satisfactory correspondence is achieved at both range ends.
Note: In the case of such configuration ─first control output - analog, second control output - relay type ─
for better operation of the analog output, is advisable to disable the relay control output by setting,
from level 4, 0UtY = 0.

20
4.6. RAMP-SOAK adjustment
The Ramp-Soak function is available ONLY for models with standard PID-Fuzzy algorithm (not with pattern
set point)! To program the RAMP function, follow the procedure below:
•From level 4, set SEt2 = ХХХ1to enable AL3 access
•From level 4, set SEt4 = ХХХ1to access ALd3
•From level 3, set ALd3 = 9to enable RAMP function - it will replace AL3 by rAMP
•From level 1, adjust the rAMP slope from 00.00 to 99.99 [°C/min]
To program the SOAK function, follow the procedure below:
•From level 3, set ALd1 (ALd2)= 19 to use SOAK timer function
•From level 1, adjust the AL1 (AL2)Soak time from 00.00 to 99.59 [h.min]
The following example illustrates RAMP-SOAK function:
•Let SV = 100 °C, rAMP = 10.00 °C/min, AL1 = 00.10 min, PV = 25 °C
4.7. Profile (pattern) control programming
The profile control with is available ONLY for models with PID-Fuzzy algorithm with pattern set point!
To program the profile control, follow the procedure below:
•From level 4, set SEt8 to adjust profile program repeat, start and power failure options
•From level 4, set SEt9 to adjust time units
•From level 3, set SEtA to adjust profile program run or end alarm
•From level 3, set WAit to adjust WAIT option
•Set the alarm type "07" and alarm functions as described in 4.2
•From level 1 follow the steps below to create a pattern, consisting of RAMP and SOAK segments
(up to 2 patterns with 8 segments or 1 pattern with 16 segments can be created)
Note: If you want the program to stop before the 8th or 16th segment just set the last segment OUtto '0'.
4.7.1. Keyboard operating commands
•Program starts by pressing S. PRO front panel LED starts to blink
•Program holds by pressing T(pause). PRO stops blinking but lights
•To jump to previous segment press S+SET
•To continue a stopped program at segment end (WAit message) press S+SET
•Program stops (RESET) by pressing T+SET. PRO front panel LED will be off.
Table of contents
Other COMECO Controllers manuals
Popular Controllers manuals by other brands

Carrier
Carrier XCT7 40VCW217FQEE Installation and owner's manual

White Rodgers
White Rodgers 1F98EZ-1621 installation instructions

Hunter
Hunter WVC Owner's manual and installation instructions

RC4 Wireless
RC4 Wireless LumenDimM4 quick start guide

Central Boiler
Central Boiler FireStar Operation manual

SuperLightingLED
SuperLightingLED C5304RF quick start guide

Contour Design
Contour Design ShuttlePROv2 user guide

birddog
birddog PTZ KEYBOARD user guide

ASCO Numatics
ASCO Numatics 342 Series Installation & maintenance instructions

Emerson
Emerson Fisher HSR Series installation guide

Eliwell
Eliwell EWRC 300 NT Series quick start

Murphy
Murphy Auto-Start/Stop Controller Cascade owner's manual