Concoa Advantium 1 Plus User manual

ADI 9525-A
European
Advantium 1 Plus
Alarm
INSTALLATION AND OPERATING INSTRUCTIONS
Carefully Read These Instructions Before Operating
Carefully Read These
Controls Corporation of America
1501 Harpers Road • Virginia Beach, VA 23454
Telephone 1-800-225-0473 or 757-422-8330 • Fax 757-422-3125
www.concoa.com February 2013
Revision A


i
SAFETY
BASIC SAFETY PRECAUTIONS MUST BE FOLLOWED TO REDUCE THE RISK OF
FIRE, ELECTRICAL SHOCK OR INJURY.
While the Advantium 1 Plus Alarm is dust and moisture resistant, it is NOT water-
proof or completely sealed. It should be installed where it will not be subjected to
rain or high concentrations of dust. Never pour or spray liquids directly onto the
product.
Install the Advantium 1 Plus where the ambient temperature range is between 0° F
and 140° F.
THIS PRODUCT IS NOT INTENDED FOR USE IN EXPLOSIVE
ENVIRONMENTS.
DO NOT INSTALL THIS PRODUCT IN ANY HAZARDOUS ENVIRONMENT.
If product appears damaged in any way, do not use and request service from
CONCOA.
USER RESPONSIBILITY
Service to this product should only be performed by CONCOA or an authorized
CONCOA agent. Requests for service may be made through CONCOA CUSTOMER
SERVICE at 1-800-225-0473. Written requests may be made using CONCOA’s FAX
CONCOA accepts no responsibility for damage or injury if this product is modified in
any way.
CONCOA assumes/accepts no liability or responsibility for damage to individuals or
equipment that may occur when using this product.

ii
Index
Power Requirements............................................................................................................1
Alarm Relay Specifications .................................................................................................1
Understanding Alarm Operation..........................................................................................2
Mounting Requirements.......................................................................................................5
Installation Instructions........................................................................................................5
Connecting Alarm to Protocol Station.................................................................................6
Connecting Alarm Outputs..................................................................................................7
Setting Remote Alarm Outputs............................................................................................9
Muting Audible Alarm.......................................................................................................11
Enabling Alarm Delay Function........................................................................................11
Changing Input Signal Polarity..........................................................................................12
Accessories ........................................................................................................................14
Warranty Information ........................................................................................................15

1
POWER REQUIREMENTS
Input Voltage: External Power Supply
` Universal input voltage 90 ~264 VAC.
Power Consumption: 5 watts
ALARM OUTPUT RELAY SPECIFICATIONS:
Contacts: Normally Open/ Normally Closed (selectable) Dry Contact
Contact Rating: 24 volts DC @.5 amps Max.

2
UNDERSTANDING ALARM OPERATION
Figure 1
Figure 1 shows the location of the various inputs, outputs and indicators for the alarm.
The Advantium 1 Plus has a universal power supply.
An ON/OFF power switch is provided on the bottom of the alarm. The switch must be in
the ON position for the alarm to work.
Input signal coming from the Protocol Station is connected to the alarm through a 6 pin
circular connector.

4
The Advantium 1 Plus provides an output signal to indicate the alarm condition of the
equipment it is monitoring. This signal is brought out through relay contacts to a 4
position circular connector. The Advantium 1 Plus is factory set so that this output signal
is brought out through Normally Closed (N.C.) contacts. Having these relay set to
Normally Closed allows for configuring multiple Advantium 1 Plus alarms for remote
locations as needed.
The contact polarity can be changed, if needed, to Normally Open. Refer to the section
in this manual “Changing Output Relay Contacts”.
Figure 1 shows a view of the front panel. It is laid out with a single status light on the
right side representing the Inlet alarm output originating from the equipment being
monitored. The System Status indicator light is a bi-colored LEDs. This means that the
same light can be turned ON as either a green indicator or a red indicator. A green LED
indicates a normal condition while a red LED indicates an alarm condition.
In the center of the front panel is an audible transducer. This transducer is used to
provide an audible indication of an alarm condition. In the upper right portion of the
front panel is a button labeled “alarm silence”. This button allows the operator to silence
the audible alarm even though an alarm condition still exists. This audible alarm can be
disabled if desired. Refer to the Section “Muting Audible Alarm” for instruction on how
this is done.
The Advantium 1 Plus input expects a switch connection across two of the pins on its
input connector. The Advantium 1 Plus supplies a +12vdc signal brought out to one of
the pins on the Input connector that serves as the supply voltage for the switch connection
on the equipment being monitored. For normal operation, this switch contact should be
normally closed (N.C.). The Advantium 1 Plus uses the Normally Closed (N.C.) contact
signal from the equipment being monitored to determine the state of the alarm of that
equipment.
If there is no alarm condition, the Advantium 1 Plus will turn ON the green indicator next
to the status being monitored.
When the switch on the equipment being monitored opens, the Advantium 1 Plus
considers this to be an alarm condition. The response from the Advantium 1 Plus is to
change the color of the indicator next to the status from Green to Red. At the same time,
if enabled, the audible buzzer in the Advantium 1 Plus will begin to beep in a pulsing
fashion. In addition, a set of contacts representing this alarm condition will open in the
output section of the Advantium 1 Plus alarm. Both the change in LED color and the
audible alarm will be delayed by 40 minutes if the “Delay Alarm” feature is enabled.

5
MOUNTING REQUIREMENTS
Figure 3
INSTALLATIONS INSTRUCTIONS
Included with the Advantium 1 Plus Alarm are four (4) screws and wall anchors. If using
the wall anchors drill a 1/8” hole in each of the four locations of the mounting holes of
the alarm. The alarm enclosure or the template provided may be used. Place the wall
anchors into the wall and attach the alarm using the screws provided.
Attach the output cable from the equipment being monitored to the Input of the alarm. If
using the output of the alarm to connect to another alarm or system, attach the output
cable at this time.
Plug the alarm into the appropriate power. Turn alarm ON by turning the Power switch
on the bottom of the alarm to the ON position and test the system. The system may be
tested once it is connected to the equipment being monitored by activating the switch on
the equipment. In the case of a CONCOA protocol system dropping the inlet pressure on
the system to below the trip point set on the pressure gauge will activate the alarm. Refer
to the operator’s manual for the protocol system to learn how to set the trip point.

6
CONNECTING ALARM TO PROTOCOL STATION
The Advantium 1 Plus Remote Alarm is designed to interface to CONCOA’s Protocol
Stations. The 6-pin remote alarm interface connector is located at the bottom of the
Advantium 1 Plus Alarm enclosure (See Figure 1). There are two ways to connect the
product to a protocol station. Ready made cable assemblies for connecting the
Advantium 1 Plus Alarm to a protocol station are available from the factory. Contact
your local CONCOA Distributor or call 1-800-225-0473 for information. The other
option is to build your own cable assembly to connect the two devices. For convenience,
a mating 6-pin connector is provided to use in building this cable assembly. The protocol
station also comes with a mating connector that is used to attach to the protocol side of
the cable assembly. The recommended cable for this assembly is 22 AWG, 4-conductor
stranded wire (Alpha # 1174C or equivalent). The length of this cable should be limited
to 1500 feet.
Cut the 4-conductor cable to length. Remove the outer jacket of the cable to expose
approximately 3/4 inch of the internal conductors on both sides of the cable. Strip away
1/4-inch of the insulation on each of the conductors.
On the 6-pin connector, slide the protective cover, cable retainer, and locking nut over the
end of the cable as shown in Figure 4.
Figure 4
Figure 5

7
Using the pin assignments shown in Table 1 and the connector views in Figure 4 and
Figure 5, solder the wires to the appropriate pins. After soldering is complete, slide the
locking nut over the connector body. Snap the cable retainer into the body and then slide
the protective cover over the cable retainer.
Table 1— Remote Alarm Pin Assignments
Protocol
Pin Number 5750011/5740012
Alarm Pin Number Function
1 1 N.C.
2 2 N.C.
3 3 +12v (provided by the remote alarm)
4 4 Inlet Status
5 5 Alarm.
6 6 Ground (provided by the remote alarm)
CONNECTING ALARM OUTPUTS
The Advantium 1 Plus provides output signals corresponding to the alarm conditions that
it senses. These signals are presented through relay contacts and are brought out to a 4
pin circular connector on the bottom of the alarm. A mating 4 pin connector is provided
to allow for connecting the alarm to other equipment. Pre-made cables are also available.
Contact your local CONCOA Distributor or call 1-800-225-0473 for information. The
relay contacts are configurable. They are factory set as Normally Closed (N.C.) but may
be changed to Normally Open (N.O.) if needed. Refer to the Section “Setting Remote
Alarm Outputs” in the manual for the procedure.
The recommended cable for making an output cable assembly is 22 AWG, 4-conductor
stranded wire (Alpha # 1174C or equivalent). The length of this cable should be limited
to 1500 feet.
Cut the 4-conductor cable to length. Remove the outer jacket of the cable to expose
approximately 3/4 inch of the internal conductors on both sides of the cable. Strip away
1/4-inch of the insulation on each of the conductors.
On the 6-pin connector, slide the protective cover, cable retainer, and locking nut over the
end of the cable as shown in Figure 6.
Using the pin assignments shown in Table 2 and the connector views in Figure 6 and
Figure 7, solder the wires to the appropriate pins. After soldering is complete, slide the
locking nut over the connector body. Snap the cable retainer into the body and then slide
the protective cover over the cable retainer.

8
CONNECTING ALARM OUTPUTS (cont.)
Figure 6
Figure 7
Table 2— Remote Alarm Output Pin Assignments
Alarm Output
Connector Pin Number Function
1 N.C.
2 Inlet Alarm
3 +12v (provided externally)
4

9
SETTING REMOTE ALARM OUTPUTS
The output signals from the Advantium 1 Plus are brought out of the alarm through relay
contacts. These contacts are set as Normally Closed (N.C.) FACTORY DEFAULT. The
relay contacts can be reconfigured as Normally Open (N.O.) . To change the relay
configuration perform the following steps:
1. Turn AC power switch OFF and unplug the alarm from AC power.
2. If the alarm is anchored to a wall remove the four screws holding it to the wall to
gain access to the back of the unit.
3. Separate the front and back of the unit by loosening the 4 screws located on the
rear of the enclosure.
4. Figure 8 shows the location of the jumpers on the circuit board for setting the
contacts.
5. Using Table 3 and Figure 8 set the jumpers to the desired contact arrangement.
6. Reattach the two sections of the enclosure with the screws previously removed.
7. Re-attach/attach the alarm to the wall with the 4 screws and the wall anchors
provided
8. Make the necessary connections to the alarm and plug the alarm cable into the
alarm connector on the bottom of the cabinet.
9. Plug the alarm back into the AC power. Turn AC power switch ON.
Table 3
Jumper Function
J2 Inlet Alarm

10
Figure 8

11
MUTING AUDIBLE ALARM
It is sometimes desirable to silence the audible alarm on the Advantium 1 Plus. This can
be accomplished by turning OFF the audible alarm switch inside the alarm. FACTORY
DEFAULT IS ON. To turn OFF the audible alarm perform the following steps:
1. Turn AC power switch OFF and unplug the alarm from AC power.
2. If the alarm is anchored to a wall remove the four screws holding it to the wall
to gain access to the back of the unit.
3. Separate the front and back of the unit by loosening the 4 screws located on
the rear of the enclosure.
4. Using Figure 9 locate SW2 switch 3 and turn it OFF.
5. Replace back cover using the previously removed screws.
6. Re-attach the alarm to the wall using the previously removed screws.
7. Plug the alarm back into AC power.
8. Turn alarm ON by turn the power switch on the bottom of the alarm to the ON
position.
9. Test unit.
ENABLING ALARM DELAY FUNCTION
The Advantium 1 Plus has a built in alarm delay feature. This feature, when set, will
delay both the visual and audible alarm signals for a period of 40 minutes. The
Advantium 1 Plus alarm is shipped from the factory with the Alarm Delay feature shut
OFF. If you wish to enable this alarm delay feature perform the following steps:
1. Turn AC power switch OFF and unplug the alarm from AC power.
2. If the alarm is anchored to a wall remove the four screws holding it to the wall
to gain access to the back of the unit.
3. Separate the front and back of the unit by loosening the 4 screws located on
the rear of the enclosure.
4. Using Figure 9 locate SW2 switch 1 and turn it ON.
5. Replace back cover using the previously removed screws.
6. Re-attach the alarm to the wall using the previously removed screws.
7. Plug the alarm back into AC power.
8. Turn alarm ON by turn the power switch on the bottom of the alarm to the ON
position.
9. Test unit.

12
CHANGING INPUT SIGNAL POLARITY
The CONCOA Protocol station provides a normally ‘ON’ signal to the alarm input when
the protocol station is operating properly. If an alarm condition occurs, this signal turns
from ‘ON’ to ‘OFF’. It is possible to change how the alarm interprets the input if for
some reason the output of the equipment being monitored is configured as Normally
Open (N.O.). Under normal circumstances there should be no reason to change the input
polarity. NOTE: CHANGING THIS INPUT SIGNAL POLARITY WILL CAUSE THE
ALARM TO FUNCTION IMPROPERLY IF IT IS USED WITH A CONCOA
PROTOCOL STATION. FACTORY DEFAULT IS NORMALLY CLOSED (N.C.) .To
change the input so that an input is ‘OFF’ when there is no alarm and ‘ON’ when an
alarm occurs perform the following steps:
1. Turn AC power switch OFF and unplug the alarm from AC power.
2. If the alarm is anchored to a wall remove the four screws holding it to the wall
to gain access to the back of the unit.
3. Separate the front and back of the unit by loosening the 4 screws located on
the rear of the enclosure.
4. Using Figure 9 locate SW2 switch 2 and turn it ON.
5. Replace back cover using the previously removed screws.
6. Re-attach the alarm to the wall using the previously removed screws.
7. Plug the alarm back into AC power.
8. Turn alarm ON by turn the power switch on the bottom of the alarm to the ON
position.
9. Test unit.

13
Figure 9
Table 4
SWITCH FUNCTION
1 Alarm Delay
2 Input Signal Polarity
3 Audible Alarm Mute

14
ACCESSORIES
Pre-assembled cables for connecting a CONCOA Protocol Station to the Advantium 1
Plus Alarm are available from your CONCOA distributor. Refer to the table below for
cable assembly descriptions and part numbers.
Cable Description Part Number
Advantium Input Cable 5295316-xx*
Advantium Input Extension Cable 5295317-xx*
Advantium Output Cable 5295320-xx*
Advantium Interconnect Cable 5295329-xx*
* - Replace ‘–xx’ with cable length. Length is in feet. Choices are -03 (3ft.), --10
(10ft.), -25 (25ft.), -50 (50 ft.), -100 (100ft.)
Example: Order 25 ft. Advantium Input Cable
PN 5295316-25

15
WARRANTY INFORMATION
This equipment is sold by CONTROLS CORPORATION OF AMERICA under the
warranties set forth in the following paragraphs. Such warranties are extended only with
respect to the purchase of this equipment directly from CONTROLS CORPORATION
OF AMERICA or its Authorized Distributors as new merchandise and are extended to
the first Buyer thereof other than for the purpose of resale.
For a period of one (1) year from the date of original delivery (90 days in corrosive
service) to Buyer or to Buyer’s order, this equipment is warranted to be free from
functional defects in materials and workmanship and to conform to the description of this
equipment contained in this manual and any accompanying labels and/or inserts,
provided that the same is properly operated under conditions of normal use and that
regular periodic maintenance and service is performed or replacements made in
accordance with the instructions provided. The foregoing warranties shall not apply if the
equipment has been repaired: other than by CONTROLS CORPORATION OF
AMERICA or a designated service facility or in accordance with written instructions
provided by CONTROLS CORPORATION OF AMERICA, or altered by anyone other
than CONTROLS CORPORATION OF AMERICA, or if the equipment has been subject
to abuse, misuse, negligence or accident.
CONTROLS CORPORATION OF AMERICA’s sole and exclusive obligation and
Buyer’s sole and exclusive remedy under the above warranties is limited to repairing or
replacing, free of charge, at CONTROLS CORPORATION OF AMERICA’s option, the
equipment or part, which is reported to its Authorized Distributor from whom purchased,
and which if so advised, is returned with a statement of the observed deficiency, and
proof of purchase of equipment or part not later than seven (7) days after the expiration
date of the applicable warranty, to the nearest designated service facility during normal
business hours, transportation charges prepaid, and which upon examination, is found not
to comply with the above warranties. Return trip transportation charges for the equipment
or part shall be paid by Buyer.
CONTROLS CORPORATION OF AMERICA SHALL NOT BE OTHERWISE
LIABLE FOR ANY DAMAGES INCLUDING BUT NOT LIMITED TO:
INCIDENTAL DAMAGES, CONSEQUENTIAL DAMAGES, OR SPECIAL
DAMAGES, WHETHER SUCH DAMAGES RESULT FROM NEGLIGENCE,
BREACH OF WARRANTY OR OTHERWISE.
THERE ARE NO EXPRESS OR IMPLIED WARRANTIES WHICH EXTEND
BEYOND THE WARRANTIES HEREINABOVE SET FORTH. CONTROLS
CORPORATION OF AMERICA MAKES NO WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH
RESPECT TO THE EQUIPMENT OR PARTS THEREOF.


ADI 9525A
Certified ISO 9001:2000
Controls Corporation of America
1501 Harpers Road Virginia Beach, VA 23454
Telephone 1-800-225-0473 or 757-422-8330 • Fax 757-422-3125
www.concoa.com
Table of contents
Other Concoa Security System manuals