3 Humidier selection
3.1 The essentials in brief
When tendering or ordering, it should be noted that the steam humidica-
tion system Condair Esco, type DR73 and DL40 consists of the following
components (*=optional):
1. Connection unit
2. Ceramic rotary-disk control valve
3. Rotary control valve actuator
4. Steam distribution system
5. Mounting set for insulated ducts*
6. Manometer*
7. Coupling piece for multiple piping*
Operating range for steam humidication systems Condair Esco, type
DR73 and DL40:
Primary steam pressure (for live steam): 0,2...4,0 bar
Primary steam temperature: 104...152 °C
Max. ambient temperature: 50 °C
Max. ambient humidity: 98 % r.h.
Text for tendering
Steam humidication system Condair Esco
Steam humidier for connection to an existing steam supply, consisting of:
• Connection unit with anged connection, steam-tight ceramic rotary-disk control valve, strainer, separation chamber and
primary spheric oat steam trap
• Steam distribution pipe, with steam nozzles, for a uniform discharge of live steam into air current throughout the entire
length of the pipe, and thermal secondary condensate drain
• Electric rotary actuator for connection to all commercially available humidity controllers
Type DR73
Steam humidication system consisting of: connection unit, electric
rotary actuator, horizontal main distribution pipe with condensate
drain pipe, and vertically arranged secondary pipes with steam
nozzles.
Type DL40
Steam humidication system consisting of: connection unit, electric
rotary actuator, horizontal steam distribution pipe with steam noz-
zles and condensate drain pipe.
Humidication capacity: ....................... kg/hr
Primary steam overpressure: ....................... bar
Humidity inlet/outlet: ....................... g/kg
Air volume: ....................... m
3/hr
Brand Condair Esco
Type .......................
Supplier .......................
Duct width/height in light ........................ mm
Min. inlet air temperature ........................ °C
Max. humidication distance ........................ m
Accessories, optional
• Manometer mounted to connection unit, for steam pressure 0 - 2.5 bar
• Manometer mounted to connection unit, for steam pressure 0 - 6.0 bar
• Mounting set for insulated ducts / AHU’s
• Coupling pieces for multiple piping (only type DL40)