
Cooper Industries Inc.
Crouse-Hinds Division IF 1544
PO Box 4999, Rev 1
Syracuse, New York 13221 • U.S.A. New 01/08
Copyright© 2007, Cooper Industries, Inc.
See Figure 2-4 – Wiring Overview of a
System. System wiring consists of primary
power and signal distribution wiring.
Primary power is usually taken from a
load center to the various items of
equipment. Signal wiring is between the
beacons and the system controller. Make
connections to beacons at nearby junction
boxes. Always position junction boxes
below the beacons with drain holes facing
downward.
Beacon Wiring
Three-phase power often supplies large
systems. However, the beacons are single-
phase units that are connected from line-
to-line (A-B, B-C, A-C). Therefore, phase
differences occur between groups of
beacons in the same three-phase system. In
a three-phase system, phase A-C must
supply the controller (not C-A) to allow
the controller to be compatible with all
beacons. Failure to ensure optimum
phasing as described could result in
intensity control problems.
Use circuit breakers or a safety switch
with fuses for the primary power load
center. Insulation should be rated at 600
VDC minimum. Wire size is a factor
affected by the service voltage, the number
of beacons in the system, and the length of
the wire run to the beacons. To determine
wire gauge, consider each beacon as a 400
volt-ampere load and do not permit the
voltage drop caused by wire resistance to
exceed 5% at any beacon. You may use
this volt-ampere value to determine ratings
for slow-acting fuses or circuit breakers
for the system. For fast-acting fuses and a
system feeder transformer (if used)
consider a peak load of 600 volt-amperes
for each beacon. CHCA recommends that
you use National Electric Code guidelines
for all primary wiring.
A label inside the beacon near the fuse
block indicates the operating voltage and
frequency of your beacon. Two internal
fuses are sized according to the operating
voltage. When Line 2 is neutral, the
factory replaces the F2 fuse with a jumper
wire.
Make connections to distribution wiring at
a nearby junction box. Consult the
following installation wiring diagrams to
guide you in wiring the equipment at your
installation:
CAUTION
These figures are guidelines only. If
they differ from the installation drawings
for your site, use the site installation
drawings.
Installation drawings in this manual are as
follows:
•Figure 2-5 – Junction Box; Three-
phase Installation Wiring
•Figure 2-6 – Single-Phase Installation
Wiring for CHB 204 or 207
•Figure 2-7 – Single-Phase Installation
Wiring for CHB 205 or 208
Lightning Protection
Though ElectroFlash equipment is
designed to withstand severe transient
over-voltages, a lightning arresting system
must be installed to prevent damage by
lightning. Install a lightning arresting
system to protect a light at the top of a
mast or antenna. Transient suppressors
from line-to-line and line-to-neutral are
recommended at the primary power load
center.