Cooper Crouse-Hinds Crouse-Hinds N2LPS SS Setup guide

IF 1630 • 01/13 Copyright © 2013, Cooper Industries, Inc. Page 1
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
APPLICATION
The LED N2LPS SS Emergency Lighting System is designed to automatically provide
illumination to designated areas during failure or interruption of power to the normal
lighting system. The N2LPS SS is factory-assembled and wired, and consists of one
battery and two light fixtures.
When properly installed, the following marine rated N2LPS SS emergency lighting
systems are UL and cUL listed for use in:
• N2LPS12222 SS Power Supply - Class I, Division 2, Groups B, C, D
• N2LPS12220 SS Power Supply - Class I, Division 2, Groups B, C, D; NEMA 4X
The N2LPS SS power supply consists of a battery supply and battery recharging
system housed inside a 316 stainless steel enclosure with all the circuitry to
automatically turn on emergency DC lighting fixture(s) when the normal power
supply fails. A pilot light indicates when normal power is being supplied to the unit. A
“push-to-test" pushbutton switch is provided for periodic testing of the unit.
The light fixture used on the N2LPS SS system is a rugged, epoxy coated corrosion-
resistant assembly, fully adjustable and lockable, and houses a high output MR16
LED lamp, which is included with the fixture.
DETAIL INDICATION LOGIC IS GIVEN BELOW:
Immediately after supply power is initiated, the indicating lamp will blink/pulse to indicate
that the unit is charging. Once installed with supply power, the N2LPS SS requires 72 hours
to charge the battery. Once the unit has completed charging, the pilot light will stop blinking
and go to steady.
Every six months, the unit will automatically perform a 90 minute battery discharge test. At
the completion of the test, if it is determined not to have met the 90 minute requirement or
if the battery connection is not adequate, the pilot lamp will blink twice, indicating battery
failure. Every 30 days, the unit will also automatically perform a 30 second self-test. If the
battery or board has been compromised the indicator light will blink accordingly.
NOTE: Ambient temperature at which N2LPS SS power supply is rated is 0ºC to +40ºC
to maximize battery capacity. Ambient temperature at which N2LPS SS S904 is rated
is 0°C to +55°C to maximize battery capacity. Lighting fixtures are permitted in higher,
+55ºC ambient temperature areas for more freedom in selecting remote installation
location.
National Electrical Code®is a registered Trademark of the National Fire Protection
Association.
WARNING
To avoid personal injury, electric shock, or equipment failure:
1. Do not use this equipment for other than intended use.
2. Do not use accessory equipment not recommended by the manufacturer.
3. Electrical power must be turned OFF before and during installation and
maintenance.
4. Equipment should be mounted in locations and at heights where it will not
readily be subjected to tampering by unauthorized personnel.
5. Do not mount near heat producing equipment.
6. In Class I areas, install and seal all equipment in accordance with the
National Electrical Code articles pertaining to hazardous (classified)
locations, plus any other applicable codes.
7. Install only wiring systems with an equipment grounding conductor (which
may be the conduit system) to supply the N2LPS SS.
8. Free installation area of hazardous atmospheres before wiring.
9. Observe all battery handling precautions contained herein.
10. To avoid shattering: Do not operate lamp in excess of rated voltage, protect
lamp against abrasion and scratches, and against liquids when lamp is
operating. Dispose of lamp properly.
LED N2LPS SS EMERGENCY LIGHTING SYSTEM
Installation & Maintenance Information
IF 1630
IMPORTANT
Emergency lighting system should be installed, inspected, operated, and maintained by
qualified and competent personnel.
RATINGS
POWER
SUPPLY
Input • 120, 230 and 277 VAC ± 5%, 50 or 60Hz
• 0.5 Amperes maximum
Output • 12 VDC; 2.5 Amperes
• 28 Watts for 1½ hours at +40°C
Ambient Temp • N2LPS SS 0ºC to +40ºC
• N2LPS SS S904 0°C to +55°C
LAMP
FIXTURES
Input • 12 VDC
Ambient Temp. • +55ºC maximum
Operating Temp. Code • Class I, Division 2 40º - T5; 55º - T4A
IMPORTANT SAFEGUARDS - READ AND FOLLOW ALL SAFETY INSTRUCTIONS
Status Indication Status Description Status Definition
No Light AC Power Removed From Circuit
* Steady Light (No blinks) Fully Charged
* - * Light Blinks Once Battery Charging
**-** Light Blinks Twice Battery Failure
***-*** Light Blinks Three Times Circuit Failure
Table 1. Detail Indication Logic

B. CONDUIT CONNECTION, WIRING, AND BATTERY INSTALLATION
1. Connect enclosure to wiring system in accordance with the National Electrical Code®plus any
other applicable codes.
NOTE: The N2LPS SS power supply is supplied with one Cooper Crouse-Hinds SSTG2
Myers™Hub (3⁄4”) and grounding bushing already installed. Use a thread sealant in conduit-to-
hub joint to maintain maximum environmental protection.
2. Make all wiring connections following wiring diagram located on power supply battery bracket
(see Figure 3).
NOTE: Although generally not required, the interior assembly may be removed to facilitate
wire pulling. Remove four (4) 1⁄4-20 screws and lock washers and disconnect wire leads at
the pilot light, DC disconnect switch, pushbuttons, and lamp heads. DO NOT handle interior
roughly or place it in an area where dirt, dust, or grime will damage it. Replace as soon as all
wiring has been pulled into enclosure.
INSTALLATION
A. INSTALL N2LPS SS SYSTEM
1. Refer to overall dimensions (see Figure 1) to select a mounting location that will provide suitable
strength and rigidity for supporting power supply and attached fixtures.
2. Loosen (do not remove) the captive cover screws (6) of the N2LPS SS power supply housing and
carefully place the cover aside for reassembly later.
3. Securely fasten the power supply enclosure to the mounting location using the appropriate length
1⁄4” diameter hardware through the four (4) mounting holes shown in Figure 1.
2a. Connect 120 VAC primary (through designated disconnect) to terminal 120. Connect 230 VAC
primary (through designated disconnect) to terminal 230. Connect 277 VAC primary (through
designated disconnect) to terminal 277. Connect common to terminal COM. Connect all
equipment grounding conductors to terminal GRD.
2b. Connect battery connector to circuit board (see Figure 3). Lamp heads will not light at this time.
Verify that transformer connector is also connected to circuit board.
2c. Standard N2LPS12222 SS system is provided with two factory-assembled and factory-wired
lighting fixture heads. (No additional fixture wiring connections need to be made by the installer).
2d. Test wiring for correctness with continuity checks and also for unwanted grounds with insulation
resistance tester.
2e. If NOT installing remote fixture assemblies for connection to the N2LPS SS power supply, proceed
to Section C, “Complete Installation.”
2f. If additional remote fixture heads are to be connected to the N2LPS SS power supply, refer to
installation instruction sheet IF 1605 (supplied with N2RF Series Remote Fixture Assemblies) and
Table 2 on page 4.
IF 1630 • 01/13 Copyright © 2013, Cooper Industries, Inc. Page 2
WARNING
To avoid explosion, electrical power must be turned OFF before and during installation and maintenance.
WARNING
To avoid potential explosion, make wiring connection using methods that comply with the NEC and
any local codes.
To prevent dangerous electrical shocks, use N2LPS SS only on grounded wiring systems.
CAUTION
To avoid impairing operation and/or damage to the equipment, mount the enclosure with the back
wall fastened to the vertical surface with the pilot light and push-to-test pushbutton located on the
right side of the enclosure.
WARNING
To avoid explosion, electrical power must be turned OFF before and during installation and
maintenance, and installation area must be free of hazardous atmospheres before wiring.
19.6
18.6
16.1
12.0
17.7
9.5
6.9
1.10
17.24
0.40
Figure 1. Dimensions
4. Adjust the lighting fixtures:
a. Loosen (do not remove) the gland
nut and the lock nut at the
mounting bracket center (see
Figure 2).
Adjust fixture head and bracket to
the desired position and re-tighten
the two nuts.
b. Loosen (do not remove) the screws
on both sides of the light fixture
(adjusting screws).
Adjust fixture head to desired position and
re-tighten the two screws.
GLAND
NUT
TOP OF BOX
LOCK
NUT
ADJUSTING
SCREW
MOUNTING
BRACKET
Figure 2
Adjust
Adjust
L- L+
TEST SWITCH
BOTON DE PRUEBA
PILOT LIGHT
LAMPARA PILOTO
RED - ROJO
RED - ROJO
YELLOW - AMARILLO
TERMINAL BLOCK
BLOCK DE TERMINALES
MAIN CHARGER
TRANSFORMER
TRANSFORMADOR
PRINCIPAL DE CARGA
ORANGE - NARANJA
BROWN - CAFE
BLACK - NEGRO
WHITE - BLANCO
RED - ROJO
YELLOW - AMARILLO
BLUE - AZUL
BATTERY
BATERIA
21G03
BATTERY DISCONNECT
SWITCH
INTERRUPTOR
DESCONECTADOR
DE BATERIA
LED LAMP#3
LED LAMP#4
LED LAMP#5
LED LAMP#6
YELLOW - AMARILLO
YELLOW - AMARILLO
BLUE - AZUL
BLUE - AZUL
EXT. LAMPS (OPTIONAL)
BLACK - NEGRO
WHITE - BLANCO
YELLOW - AMARILLO
YELLOW - AMARILLO
RED - ROJO
BLACK - NEGRO
GREEN - VERDE
GREEN - VERDE
GREEN - VERDE
BLACK - NEGRO
WHITE - BLANCO
MAIN LAMPS
LED
LAMP#2
LED
LAMP#1
BLACK - NEGRO
WHITE - BLANCO
GRD COM 120 230 277
Figure 3. N2LPS Wiring Diagram
NOTE: Main lamp head wires may vary in color. Instead of WHITE (+), BLACK (-), and GREEN (Ground),
wires may be BROWN (+), BLUE (-), and BLACK (Ground) respectively.

2. Flush ECD with water under line pressure (typically 30 to 75 psi). Discard the drain or breather if the
foreign material is not removed.
NOTE: Different styles and sizes of ECD fittings will allow different amounts of water or air to pass
through. To determine if a breather or drain has been cleaned, compare the volume or water passing
through a clean, unused breather or drain of the same style and size.
3. After cleaning, attach the breather or drain to a pressurized dry air supply line in a similar manner to that
used with the water line in Step 1.
4. Blow the fitting dry, inside and out, with the dry air.
PERIODIC TESTING
Article 700 of the National Electrical Code states, “Systems shall be tested periodically on a schedule
acceptable to the authority having jurisdiction to assure their maintenance in proper operating condition.” It
also states, “A written record shall be kept of such tests and maintenance.”
In the absence of periodic testing requirements by a local authority, the following recommendations from the
NFPA 101 (2003) Life Safety Code®are strongly recommended:
1. Monthly: Momentarily operate push-to-test switch. Observe that emergency lighting fixtures are on full
brightness for the entire test cycle. Record the test on the Maintenance Record Card (provided on page
5).
2. Annually: Shut off AC power at the distribution panel. Verify that the emergency lighting fixtures remain
“ON” for a minimum of 1 1⁄2hours.
NOTE: Leave the battery disconnect switch “ON” during this test so that battery circuit is not
interrupted. We suggest that this test be continued until the power supply automatically shuts the
emergency light(s) off. This will help maintain full battery capacity.
Record the test on the Maintenance Record Card.
Allow 72 hours charging time before depending on the battery to operate at full capacity.
Failure to function properly in either test may indicate the need for battery or lamp replacement.
BATTERY REPLACEMENT
1. Turn battery disconnect switch to “OFF” and lock-out the switch.
2. Loosen (do not remove) the captive cover screws (6) of the N2LPS SS power supply housing and carefully
place the cover aside for reassembly later.
3. Disconnect the wire nut attaching black negative lead from battery to the battery plug.
4. Disconnect the wire nut attaching red positive lead from battery to battery disconnect switch, taking care
not to touch the ground.
5. Remove the four (4) screws that fasten the battery hold-down bracket to the mounting plate. Remove
battery. Retain hardware for use with replacement battery.
6. Reinstall new battery using hold-down bracket and four (4) screws previously removed.
7. Reconnect black and red battery conductors using wire nuts.
8. Close cover and torque all cover (6) screws to 21-25 in.-lbs.
9. Unlock designated disconnect switch to “ON” position. You may lock switch in “ON” position to prevent
unauthorized persons from turning system “OFF.”
10. Test replacement battery following Step 3 of Section C, “Complete Installation.”
IF 1630 • 01/13 Copyright © 2013, Cooper Industries, Inc. Page 3
C. COMPLETE INSTALLATION
1. Install CID101 corrosion inhibitor device (supplied in plastic envelope with instruction sheet).
Recommended location is on the inside surface of the top of the enclosure near the right side fixture
stem. Refer to CID101 instruction for installation.
2. Close cover and torque all cover (6) screws to 21-25 in.-lbs.
3. Test emergency lighting system for proper operation (see Table 1 on page 1 for detail indication logic):
Turn on the AC power and observe:
• Indicating light marked “ON” should be operating
• Momentarily press the push-to-test button and observe - emergency lights should be operating
NOTE: If emergency lights do not operate initially, allow battery to charge for at least 15 minutes or
more, then repeat the test procedure.
4. Allow 72 hours charge time before depending on battery to operate at full capacity.
NOTE: Lock in ON position to prevent unauthorized persons from turning system OFF.
INSPECTION OF BREATHER/DRAIN
The breather/drain is installed to provide ventilation to minimize condensation and also allow liquids to
drain out. Perform visual and mechanical inspections on a regular basis. Frequency should be determined
by the environmental conditions. However, it is recommended that checks should be made at least once per
year.
1. Remove drain or breather and replace it with either a plug or clean drain or breather.
2. Clean breather/drain by following “Flush-Cleaning” instructions.
FLUSH-CLEANING
Flush-Cleaning may be required by the user’s periodic maintenance program or when a drain or breather
becomes clogged with foreign material.
1. Attach drain or breather to a clean water line with threaded end facing upstream (see Figure 4).
WARNING
To avoid electrical shock, use fixture only on systems with an equipment grounding conductor.
WARNING
To avoid potential explosion, do not short circuit the battery or connector terminals.
To avoid explosion:
1. Exercise care in handing cells/batteries in order to prevent shorting of the cell with conductive
materials such as rings, bracelets, and keys. The cell or conductor may overheat and cause burns.
2. Do not dispose of the cell/battery in open flame; cells may burst.
3. Do not open or mutilate cell/battery. Opened cells may release corrosive electrolytes which may
have harmful effects on the skin and eyes, and may be toxic if ingested.
WARNING
NOTE
Unit needs to charge for 72 hours before conducting any tests. Do not disconnect AC power until
unit is fully charged.
CAUTION
To minimize condensation, never disassemble breather or drain assemblies.
CAUTION
To avoid damaging breather/drain, do not force handle or cap during inspection.
Figure 4

FIXTURE HEAD REPLACEMENT
1. Disconnect AC power by opening the supply circuit at the distribution panel.
2. Disconnect DC power by turning designated disconnect selector switch to “OFF.”
3. After removing all AC and DC power to the fixture, loosen (do not remove) the captive cover screws of
the N2LPS SS power supply enclosure and carefully place the cover aside for reassembly later.
4. Disconnect battery lead from charger board.
5. Disconnect fixture head wire leads, noting color coding of wires.
6. Remove nut from underside of fixture head threaded stem and remove fixture head/CGB fitting
assembly from the power supply housing.
NOTE: Do not discard the nut, which will be used with the replacement fixture head.
7. Insert wiring for new fixture head assembly through the power supply opening, and insert the fixture
CGB fitting.
8. Install the nut (removed in Step 6) while holding the fixture head assembly in the desired position.
MAINTENANCE
1. Conduct periodic testing in accordance with local authority and Periodic Testing section of these
instructions.
2. Clean fixture lens and exterior surfaces periodically. We recommend every three months or more
frequently, if appropriate.
3. Frequent interior inspection should be made. A schedule for maintenance check should be determined
by the environment and frequency of use. It is recommended that it should be at least once a year.
4. Perform visual, electrical, and mechanical checks on all components on a regular basis.
• Visually check for undue heating evidenced by discoloration of wires or other components,
damage, or worn parts, or leakage evidenced by water or corrosion in the interior.
• Electrically check to make sure that all connections are clean and tight.
• Mechanically check that all parts are properly assembled.
5. Do not attempt field replacement or repair of N2LPS SS power supply cover gasket. Instead, remove
damaged gasket and continue to use cover without gasket. This will assure safety for use in Class I and
Class II hazardous (classified) locations. However, the enclosure will not be raintight.
IF 1630 • 01/13 Copyright © 2013, Cooper Industries, Inc. Page 4
Table 2
Wire Sizing for Remote Installation
(for copper wire)
Running Distance* (ft.) Between Power Supply and Remote Lighting Fixture
Ambient Temp. ºC 25 40 55
Lighting Fixture
Load-Max. Watts 12 24 30 12 24 30 12 24 30
Wire Size
• 14 AWG 125 63 50 117 58 47 109 55 44
• 12 AWG 198 99 79 185 92 74 173 87 69
• 10 AWG 317 158 127 295 148 118 276 138 110
• 8 AWG 505 253 202 471 235 188 440 220 176
WARNING
To avoid explosion, always disconnect primary power source using designated disconnect switch
before opening enclosure for inspection or service.
WARNING
WARNING
To prevent injury from electric shock, all power must be removed from the fixture during
maintenance.
Even after disconnect, batteries will still be live. To prevent electrical shock and explosion, take
extra care not to touch leads together or to ground.
TROUBLESHOOTING GUIDE
SYMPTOM SOLUTION
1. Pilot light does not light. 1a. Verify power to fixture.
1b. Verify transformer is properly connected to circuit
board.
2. Pilot is blinking twice. 2. Verify battery is properly connected to circuit
board.
3. After 72 hours, unit is not fully charged
(pilot light steady) and lamp heads flash.
3. Remove leads from pushbutton N/C contacts and
terminate the leads on the N/O contacts.
4. Pilot light is blinking three times.
4. Verify battery voltage under no load is 13.0V or
higher after 72 hour charge. If less than 13.0V,
consult factory for battery replacement. If more
than 13 volts, consult factory for complete interior
replacement as transformer and/or circuit board
could be responsible.
REPLACEMENT CIRCUIT BOARD AND BATTERY KIT
N2LPS K57 KIT CONSISTS OF:
(1) Circuit Board and Charger Assembly with Mounting Bracket
(1) IF 1595A
(1) Sealed Ni-Cad Battery (A high temp. rated battery for N2LPS K57 S904 kit is included)
(1) 2 Volt LED for Pilot Light
(1) CID101 Corrosion Inhibitor Device
(See IF 1595A for replacement).
NOTE: If the rating of your LED N2LPS Emergency Lighting System is from 0°C to 55°C, make sure you
use a N2LPS K57 S904 replacement kit. Otherwise, use N2LPS K57 kit (see Figure 5 for temperature
rating reference).
WARNING
All electrical power must be turned OFF before and during installation and maintenance. Area should be
free of hazardous atmospheres before maintenance is performed to reduce the risk of accidental
explosion due to inadvertent shorting of battery during maintenance.
*Maximum distance to limit line voltage drop to 5%.
Figure 5

MAINTENANCE RECORD
NFPA 101 (2003) REQUIREMENTS
" A FUNCTIONAL TEST SHALL BE CONDUCTED ON EVERY REQUIRED EMERGENCY LIGHTING SYSTEM AT 30
DAY INTERVALS FOR A MINIMUM OF 30 SECONDS. AN ANNUAL TEST SHALL BE CONDUCTED FOR THE 1 1⁄2
HOUR DURATION.
EQUIPMENT SHALL BE FULLY OPERATIONAL FOR THE DURATION OF THE TEST. WRITTEN RECORDS OF
TESTING SHALL BE KEPT BY THE OWNER FOR INSPECTION BY THE AUTHORITY HAVING JURISDICTION.”
N2LPS EMERGENCY LIGHTING POWER SUPPLY
N2LPS EVI EMERGENCY LIGHTING FIXTURE (EXIT SIGN)
N2LPS EVA GB EMERGENCY LIGHTING FIXTURE (GB [Group B] EXIT SIGN)
SEE INSTALLATION AND MAINTENANCE
INSTRUCTION SHEETS FOR METHODS OF TESTING
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness
thereof are not guaranteed. In accordance with Crouse-Hinds “Terms and Conditions of Sale”, and since conditions of use are outside our control, the purchaser should
determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
Cooper Industries Inc. IF 1630
Crouse-Hinds Division Revision 3
PO Box 4999, Syracuse, New York 13221 • U.S.A. Revised 01/13
Copyright © 2013, Cooper Industries, Inc. Supercedes 12/12
DATE 30 SEC 1-1/2 OTHER BATTERY INSPECTED LAMP REPLACED NOTES
HOUR REPLACED BY (RECORD FIXTURE LOCATION)
DURATION OF TEST
Table of contents
Other Cooper Crouse-Hinds Lighting Equipment manuals

Cooper Crouse-Hinds
Cooper Crouse-Hinds eLL. 92 LED 400 User manual

Cooper Crouse-Hinds
Cooper Crouse-Hinds CCB Series Setup guide

Cooper Crouse-Hinds
Cooper Crouse-Hinds CHB 204 User manual

Cooper Crouse-Hinds
Cooper Crouse-Hinds CEAG eBK 02 User manual

Cooper Crouse-Hinds
Cooper Crouse-Hinds eLLK 92 NIB Series User manual

Cooper Crouse-Hinds
Cooper Crouse-Hinds CEAG SEB 9 User manual

Cooper Crouse-Hinds
Cooper Crouse-Hinds Champ VMV High Wattage Series User manual

Cooper Crouse-Hinds
Cooper Crouse-Hinds LP1 Series Setup guide

Cooper Crouse-Hinds
Cooper Crouse-Hinds 858 Series User manual

Cooper Crouse-Hinds
Cooper Crouse-Hinds CHC 140 Series User manual