1
PN P85325C Copyright 2015 Cooper Wheelock, Inc. dba Cooper Notication
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL
The Wheelock Series E60H, High Fidelity Round Speakers and Speaker Strobes, are UL Listed under Standard 1971 for Signaling Devices for the Hearing Impaired, UL
Standard 1480 for Speaker Appliances and ULC Listed under Standard CAN/ULC-S541-07 AND CAN/ULC-S526-07. Speaker Strobes with amber, blue, green and red lens
are UL Listed under Standard 1638 (Visual Signaling Appliance) for Private Mode Emergency and General Utility Signaling. They are designed for multiple power require-
ments with high dBA output at each power tap. All models offer a choice of field selectable taps, 1/8W to 2W, for either 25.0 VRMS or 70.0 VRMS audio systems. The design
incorporates a high efficiency speaker for maximum output at minimum power across a frequency range of 300-8000Hz. The Series E60H appliances also incorporate a
speaker mounting plate attached to the speaker for ease of installation. The Speaker Strobes can provide a non-synchronized strobe appliance when connected directly to
a Fire Alarm Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with a Dual Sync Module (DSM), or Wheelock power supplies. The
strobes use a xenon flashtube with solid state circuitry enclosed in a polycarbonate lens to provide maximum visibility and reliability for effective visible signaling. The E60H-
24MCC and E60H-24MCCH Speaker Strobes are for ceiling mounting only. All models are Listed for indoor use only with the back boxes specified in these instructions (see
Wiring and Mounting Information). 1/8W tap setting for Private Mode only. E60H series speakers are UL rated to meet the NFPA 72 requirement for 520Hz signals in
sleeping areas when used in conjunction with Wheelock Safepath products (see SP40S manual for more details)
NOTE: All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems - CAN/ULC-S524 and Canadian Electrical
Code, Part 1. Final acceptance is subject to Authorities Having Jurisdiction.
WARNING: Please read these instructions carefully. Failure to comply with any of the following instructions, cautions and warnings could result in improper ap-
plication, installation and/or operation of these products in an emergency situation, which could result in property damage and serious injury or death to you and/
or others.
SPECIFICATIONS
Table 1A: UL/ULC Listed Models and Ratings
Speaker
Model Voltage
VRMS
dBA at 10 Feet (Rated Watts) Anechoic dBA
Per CAN/ULC-S541-07
1/8 ¼ 1/2 1 2 1/8 ¼ 1/2 1 2
E60H 25/70 74 77 80 83 85 74 78 80 83 86
E60H-24MCC 25/70 74 77 80 82 85 73 76 79 82 85
E60H-24MCCH 25/70 74 77 80 82 85 73 76 79 82 85
Table 1B: UL/ULC Listed Models and Ratings
Strobe
Model Regulated
Voltage
VDC/VRMS
Voltage
Range
VDC/VRMS
Candela Mounting
Options
E60H ---- ---- ---- A,C
E60H-24 MCC 24 16-33.0 15/30/75/95 B,C
E60H-24MCCH 24 16-33.0 115/177 B,C
NOTES
• Strobes produce 1 flash per second over the “Regulated Voltage” range.
• All models are Listed for indoor use with a temperature range of +32ºF to +120ºF (0ºC to +49ºC) and maximum humidity of 93% RH. The effect of shipping and storage
temperatures shall not adversely affect the performance of the appliance when it is stored in the original cartons and is not subjected to misuse or abuse.
• The maximum supervision voltage is 33 volts DC.
• Frequency range of speakers is 300-8000Hz.
• Strobes with clear and amber lens meet the required light distribution defined in UL1971.
• Candela ratings are for clear lens. Derate approximately 25% for amber lens, 55% for green, 70% for blue and 80% for red.Model numbers will have a letter after the H
to designate lens color (A, G, B or R).
CAUTION: Always operate audio amplifiers and speakers within their specified ratings. Excessive input may distort sound quality and may damage audio equipment. Do not
exceed 100% of speaker input voltage per UL 1480. Improper input voltage can damage speaker. If distortion is heard, check for clipping of the audio appliance with an oscil-
loscope and reduce the amplifier input level or gain level to eliminate any clipping.
WARNING: Candela setting will determine the current draw of the product.
CAUTION: These strobes are Listed as “Regulated”. They are intended to be used with FACPs whose notification circuits are Listed as “Regulated.” These appliances shall
not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the installation instructions of the FACP is identi-
fied to be compatible in this instruction manual.
\\
Table 2: Current Ratings with Strobe Only
E60H-MCC/E60H-MCCH Maximum RMS Current (AMPS)
UL Voltage 15cd 30cd 75cd 95cd 115cd 177cd
DC 16-33VDC 0.065 0.105 0.189 0.249 0.300 0.420
FWR 16-33VRMS 0.110 0.170 0.280 0.375 0.455 0.645
Table 3: ULC Directional Characteristics
25/70V
E60H
-3dBA +/- 34 degrees horizontal; +/- 17 degrees
vertical
-6dBA +/- 40 degrees horizontal; +/- 32 degrees
vertical
WARNING: These strobes were tested to the regulated voltage limits of 16.0-33.0 Volts for 24v models using filtered dc or unfiltered full-wave-rectified voltage. Do
not apply voltage outside of this range.
WARNING: Check the minimum and maximum output of the power supply and standby battery and subtract the voltage drop from the circuit wiring resistance to
determine the applied voltage to the strobes. The maximum wire impedance between strobes shall not exceed 35 ohms.
CAUTION: Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
WARNING: Make sure the total RMS current required by all appliances that are connected to the system’s primary and secondary power sources, notification ap-
pliance circuits, Wheelock dsm sync modules or Wheelock power supplies do not exceed the power sources’ rated capacity or the current ratings of any fuses on
the circuits to which these appliances are wired. Overloading power sources or exceeding fuse ratings could result in loss of power and failure to alert occupants
during an emergency, which could result in property damage and serious injury or death to you and/or others.
WIRING AND MOUNTING INFORMATIONCAUTION: The following figures show the maximum number of field wires (conductors) that can enter the backbox used with
each mounting option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could dam-
age the product. Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed multicon-
ductor cable or 3/4-inch (1.9-cm) conduit fittings are used.
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Cooper Notification recommends use of the largest backbox option
shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from
INSTALLATION INSTRUCTIONS
SERIES E60H HI-FIDELITY ROUND
SPEAKERS AND SPEAKER STROBES
2
PN P85325C
wiring.
Figure 1 Figure 2
NOTE: Wiring method shall be in accordance with CSA C22.1, Canadian Electrical Code, Part 1, Safety Standard for Electrical Installations, Section 32.
WARNING: Check electrical ratings specified in tables 1 and 2 (as appropriate) to ensure proper input. Be sure that speaker wiring is connected to speaker
terminals only and strobe wiring is connected to strobe terminals only. Check to ensure that wiring at FACP is correct. Improper electrical input can damage the
product or cause it to malfunction, which could result in property damage and serious injury or death to you and/or others.
Refer to Sync Module instruction sheets DSM (P83177) or Wheelock’s Power Supplies for additional information.
• This model has in-out wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at each screw terminal. Strip leads 3/8 inches (.095 cm) and con-
nect to screw terminals.
• Break all in-out wire runs on supervised circuits to ensure integrity of circuit supervision as shown in Figure 2. The polarity shown in the wiring diagrams is for operation of the appli-
ances.
1. Each doubling of rated Watts increases sound output by 3 dBA. Field selectable input terminals are provided on each unit. The following wattage selections are avail-
able: 1/8W, 1/4W, 1/2W, 1W and 2W.
2. Each letter corresponds to a plug position of the header located on the printed circuit board. Select voltage and wattage as shown in Table 3 below.
3. A 1.5µF blocking capacitor for DC supervision of audio lines by the FACP is factory wired in series with the speaker input.
GROUNDING: Connect ground wire to backbox. Install signaling appliance to backbox using mounting screws provided.
Table 4:Speaker Voltage and Wattage Connection Chart
Position 25V 70V
A 2 ------
B 1 ------
C 1/2 ------
D 1/4 2
E 1/8 1
F ------ 1/2
G ------ 1/4
H ------ 1/8
Figure 3: Tap Settings (Factory setting is 70V @ 1/2W (Tap F))
Figure 4 Expected Light Output
NOTE: The E60H-24MCC comes pre-set at 15cd. Figure 5:
NOTE: The E60H-24MCCH comes pre-set at 177cd.
WARNING: The candela select switch must be field set to the required candela intensity before installation. When changing the setting of the candela select
switch, make certain that it “clicks” in place. After changing the candela setting, the appliance must be retested to verify proper operation. Improper setting of
the candela select switch, may result in operation at the wrong candela, which could result in property damage and serious injury or death to you and/or others.
MOUNTING PROCEDURES
1. All models can be flush mounted to a 4-inch square by 2-1/8-inch (10.16-cm by 5.4 cm) deep backbox with a 4-inch 1-1/2-inch (10.16-cm by 3.8-cm) sq. extension
ring (Figure A). Mounting hardware is supplied.
2. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product. Do not pass additional wires (used for other than
the signaling appliance) through the backbox. Such additional wires could result in insufficient wiring space for the signaling appliance.
3. When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the signaling appliance.
4. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is espe-
cially important for stiff, heavy gauge wires and wires with thick insulation or sheathing.
5. The speaker strobe has an integrated speaker mounting plate which must be oriented correctly before mounting the unit to the back box. See Figure B for correct
strobe orientation.
6. To move selector switch, insert screwdriver into slot shown on the bottom side of the strobe. The setting is indicated by a pointer and can be seen on the bottom side
of the lens. See Figure 5.
7. First mount the mounting plate to the backbox and fasten it with two screws. Next, snap the grille to the mounting plate. Make sure that the grille is secure and does
not move.
8. To remove the grille, insert a small flat screwdriver into the slots on either side of grille to disengage the snaps. See Figure 7.
9. Hold flat screwdriver near the tip and insert the tip about 1/8-inch (.13 cm) into one of the slots in the grille as shown.
10. Pull straight down as shown to pop off grille.
CAUTION: Prying, turning or pivoting with screwdriver in order to remove the grille may result in damage to ceiling.
NOTE: Non-strobe grille shown.
Figure 7: Grille Removal
WARNING: The E60H speaker strobe appliance is a “FIRE ALARM DEVICE-DO NOT PAINT.”
WARNING: When installing strobes in an open office or other areas containing partitions or other viewing obstructions, special attention should be given to the
location of the strobes so that their operating effect can be seen by all intended viewers, with the intensity, number, and type of strobes being sufficient to make
sure that the intended viewer is alerted by proper illumination, regardless of the viewer’s orientation. Failure to do so could result in property damage and serious
injury or death to you and/or others.
The E60H-24MCCH’s 177cd setting is Listed for use in sleeping or non-sleeping areas when installed in accordance with appropriate NFPA Standards and the Authority
Having Jurisdiction.
WARNING: A small possibility exists that the use of multiple strobes within a person’s field of view, under certain circumstances, might induce a photo-sensitive
response in persons with epilepsy. Strobe reflections in a glass or mirrored surface might also induce such a response. To minimize this possible hazard, cooper
wheelock strongly recommends that the strobes installed should not present a composite flash rate in the field of view which exceeds five (5) hz at the operating
voltage of the strobes. Cooper wheelock also strongly recommends that the intensity and composite flash rate of installed strobes comply with levels established by
applicable laws, standards, regulations, codes and guidelines.
If this appliance is required to produce a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, the appli-
ance must be used with a fire alarm control unit that can generate the temporal pattern signal. Refer to manufacturer’s installation manual for details.
NOTE: NFPA 72/ANSI 117.1 conforms to ADAAG Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within the same protected area.
CAUTION: Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or restrictions on wiring and/or locating Noti-
fication Appliance Circuits (NAC) and notification appliances. Some system communication circuits and/or audio circuits, for example, may require special precautions to
assure electrical noise immunity (e.g., audio crosstalk).
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off
and on, the user is encouraged to try to correct the interference by one or more of the following measures: 1) Reorient or relocate the receiving antenna, 2) Increase the
separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected, and 4) Consult
the dealer or an experienced radio/TV technician for help.
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM COOPER WHEELOCK MANUALS OR OTHER DOCUMENTS DESCRIBING THE PRODUCT FOR
USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE PRODUCT’S APPLICATION, OPERATION, INSTALLA-
TION AND TESTING IS USED AT THE SOLE RISK OF THE USER AND COOPER WHEELOCK WILL NOT HAVE ANY LIABILITY FOR SUCH USE.
12/15
0%
50%
100%
150%
200%
-100 -90 -80 -70 -60 -50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100
% of Rating
Angle
Expected Horizontal and Vertical Values
Expected
Horizontal
and
Vertical
Values

This manual suits for next models

5

Other Cooper Notification Speakers manuals

Cooper Notification E50H-241575W User manual

Cooper Notification

Cooper Notification E50H-241575W User manual

Cooper Notification LSPK User manual

Cooper Notification

Cooper Notification LSPK User manual

Cooper Notification Wheelock E60H Series User manual

Cooper Notification

Cooper Notification Wheelock E60H Series User manual

Cooper Notification LSPKC User manual

Cooper Notification

Cooper Notification LSPKC User manual

Cooper Notification E70H Series User manual

Cooper Notification

Cooper Notification E70H Series User manual

Cooper Notification SPMNS User manual

Cooper Notification

Cooper Notification SPMNS User manual

Cooper Notification ET70-24MCC Series User manual

Cooper Notification

Cooper Notification ET70-24MCC Series User manual

Cooper Notification SA-S70 User manual

Cooper Notification

Cooper Notification SA-S70 User manual

Cooper Notification E70H Series User manual

Cooper Notification

Cooper Notification E70H Series User manual

Cooper Notification ET70-24MCW Series User manual

Cooper Notification

Cooper Notification ET70-24MCW Series User manual

Cooper Notification E70 User manual

Cooper Notification

Cooper Notification E70 User manual

Cooper Notification E70-24MCW-FW User manual

Cooper Notification

Cooper Notification E70-24MCW-FW User manual

Popular Speakers manuals by other brands

DAPAudio Pure-15 manual

DAPAudio

DAPAudio Pure-15 manual

PodSpeakers BassStation user manual

PodSpeakers

PodSpeakers BassStation user manual

DAPAudio DRX Active Series manual

DAPAudio

DAPAudio DRX Active Series manual

Eaton MC5-EN installation manual

Eaton

Eaton MC5-EN installation manual

ESI Unik Pus user guide

ESI

ESI Unik Pus user guide

The box Oval 4 user manual

The box

The box Oval 4 user manual

Martin Audio LE12JB - SCHEMATICS manual

Martin Audio

Martin Audio LE12JB - SCHEMATICS manual

ENERGY SISTEM Energy Soundbar 200 user manual

ENERGY SISTEM

ENERGY SISTEM Energy Soundbar 200 user manual

Audioplex OA-602 brochure

Audioplex

Audioplex OA-602 brochure

DAPAudio PSS-10 manual

DAPAudio

DAPAudio PSS-10 manual

Monitor Audio Loudspeaker Platinum Series Brochure & specs

Monitor Audio

Monitor Audio Loudspeaker Platinum Series Brochure & specs

Genelec 8040B Operation manual

Genelec

Genelec 8040B Operation manual

Klipsch KIO-650 owner's manual

Klipsch

Klipsch KIO-650 owner's manual

OWI T5753 Specifications

OWI

OWI T5753 Specifications

CyberData Syn-Apps 011200 Installation quick reference

CyberData

CyberData Syn-Apps 011200 Installation quick reference

EAW JFX590 Specifications

EAW

EAW JFX590 Specifications

Kenwood KFC-1674 Service manual

Kenwood

Kenwood KFC-1674 Service manual

Tellur Hydra user manual

Tellur

Tellur Hydra user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.