Cumberland EXPERT 64 Plus User manual

EXPERT 64+
Temperature Controller
User’s manual

2EXPERT 64+, rev.12
EXPERT 64+
WARNINGS
The warranty can be void if this product is used in a manner
not specified by the manufacturer.
Every effort has been made to ensure that this manual is
complete, accurate and up-to-date. The information con-
tained in it is however subject to change without notice
due to further developments.

3
EXPERT 64+, rev.12
EXPERT 64+
1. INTRODUCTION...................................................6
1.1. Precautions .....................................................6
1.2. Symbols of the Manual ........................................ 6
1.3. Controller’s Overview .......................................7
1.4. Main Features of the Controller ..........................7
2. MOUNTINGINSTRUCTIONS..................................8
2.1. Installing the Controller on the Wall ....................8
2.2. Connections ....................................................8
2.2.1. Controller’s Main Wiring ................................. 8
2.2.2. Alarm Connection .......................................... 8
2.2.3. Sensor Inputs ................................................ 9
2.2.4. 0-10V Output Connection............................... 9
3. USERINTERFACE.................................................9
3.1. Location of the Controls ....................................9
3.2. How to Select & Modify the Parameters ............10
3.3. Status LEDs ..................................................10
4. CONTROLLERSETUP..........................................11
4.1. Time & Date ..................................................11
4.2. Password .....................................................11
4.3. Controller Programs ........................................12
4.3.1. Selecting a Program ..................................... 12
4.3.2. Copy/Paste Programs ................................... 12
4.4. Installation Setup ...........................................13
4.5. Probes ..........................................................14
4.5.1. Activating the probe inputs ........................... 14
4.5.2. Measuring Units .......................................... 15
4.5.3. Probe Assignment ....................................... 15
4.5.4. Probes & Water Meter Calibration .................. 16
4.6. Relative Humidity (RH) Control .........................17
4.6.1. Activating the RH Compensation Functions ..... 18
4.6.2. RH Compensation Parameters ....................... 19
4.7. Relay Assignment ..........................................20
4.7.1. Principle of Operation ................................... 20
4.7.2. Making the Assignment ................................ 21
TABLEOFCONTENTS

4EXPERT 64+, rev.12
EXPERT 64+
4.8. Alarms ..........................................................22
4.8.1. Alarm Log................................................... 22
4.8.2. Alarm Conditions ......................................... 22
4.8.2.1. Temperature Alarms .......................... 23
4.8.2.2. Empty Zone Temperature Alarms ......... 24
4.8.2.3. Water Spill Alarm .............................. 24
4.8.2.4. Static pressure Alarms ....................... 24
4.8.3. Setting the Alarm Limits ............................... 25
4.8.4. Critical Temperature Ramp .......................... 26
4.9. Clean Mode & Empty Zones ............................27
4.10. Controller’s Version ........................................28
4.11. Test Mode .....................................................28
5. TEMPERATURESETTINGS...................................29
5.1. House Set Points ............................................29
5.1.1. Principle of Operation ................................... 29
5.1.2. Settings ..................................................... 29
5.2. Set Point Ramp ..............................................30
5.3. Seasonal Temperatures ...................................31
6. VENTILATIONSETTINGS.....................................32
6.1. Minimum Ventilation .......................................32
6.1.1. Principle of Operation ................................... 32
6.1.2. Min Ventilation Ramp ................................... 33
6.1.2.1. Min Vent. Night Ramp ........................ 34
6.1.2.2. Night Start Time ................................ 34
6.1.3. Minimum Ventilation Fan/Tunnel Fan Groups ... 35
6.1.4. Fan Cycling................................................. 35
6.2. Fan & Tunnel Fan Groups ................................36
6.2.1. Principle of Operation ................................... 36
6.2.2. Settings ..................................................... 37
6.2.3. Timer-based Relays ...................................... 37
6.2.4. Fan Group Shutoff in Transitional Ventilation .. 37
6.3. Tunnel Ventilation ..........................................38
6.3.1. Transition between Sidewall and Tunnel Ventila-
tion............................................................ 38
6.3.2. Endwall Curtain ........................................... 39
6.3.2.1. Principle of Operation ......................... 39
6.3.2.2. Curtain Settings ................................ 41

5
EXPERT 64+, rev.12
EXPERT 64+
6.4. Vent Doors ....................................................43
6.4.1. Principle of Operation ................................... 43
6.4.2. Sidewall Vent Settings ................................. 44
6.4.3. Attic Vent Compensation.............................. 45
6.5. Cooling Outputs .............................................47
6.6. Stir Fans .......................................................49
7. HEATING...........................................................50
8. LIGHTS.............................................................51
9. CLOCKOUTPUTS...............................................54
10. MONITORINGFUNCTIONS..................................55
10.1. Current Conditions .........................................55
10.2. Individual Temperature Probe Readings .............55
10.3. History..........................................................56
10.4. Monitoring the Animal Age & Number ...............57
11. TECHNICALSPECIFICATIONS..............................59
12. TRANSFERMENU...............................................60
12.1. Screen Contrast ............................................60
12.2. Communication Speed ....................................60
12.3. Update/Backup Process ...................................60
14. INSTALLATIONREPORT......................................63
ANNEX1:CORECARD..................................................71
15. INDEX...............................................................72

6EXPERT 64+, rev.12
EXPERT 64+
1. INTRODUCTION
1.1. Precautions
WARNING: Read and save these in-
structions!
Safety may be jeopardized if the equipment
is used in a manner not specified by the
manufacturer. Carefully read and keep the
following instructions for future reference.
We strongly recommend installing supplemen-
tary natural ventilation as well as a backup
thermostat on at least one cooling stage.
Although fuses at the input and outputs of
the controller protect its circuits in case of
an overload or over-voltage, we recommend
installing an additional protection device on
the controller’s supply circuit.
The room temperature where the controller
is located must always remain between 32°F
and 104°F (0°C to 40°C). Indoor use only!
To avoid exposing the controller to harmful
gases or excessive humidity, it is preferable
to install it in a corridor.
If the equipment is used in a manner not
specified by the manufacturer, the protec-
tion provided by the equipment may be
impaired.
Do not spray water on the controller! In
order to clean the control, wipe it with a
damp cloth.
Before servicing or cleaning unit, switch
power off at service panel and lock the
switch disconnecting means to prevent
power from being switched accidentally.
When the service disconnecting means
cannot be locked, securely fasten a
prominent warning device, such as a
tag, to the service panel.
1.2. SymbolsoftheManual
Warning. Read the following text
carefully; it contains important
information which, if ignored, may
cause the controller to operate
improperly.
High Voltage. Hazard of electrical
shock. Read the message and follow
the instructions carefully.
Pay attention. The following text
contains very useful information.
Both direct and alternating current
(AC/DC).
Direct current (DC).
Alternating current (AC).
Earth Ground Terminal
Primarily used for functional earth
terminals which are generally asso-
ciated with test and measurement
circuits. These terminals are not for
safety earthing purposes but provide
an earth reference point.
For Customer Use: Enter below the serial
number located on the side of the alarm
system and keep this information for future
reference.
Model: EXPERT 64+
Serial number:
Date installed:

7
EXPERT 64+, rev.12
EXPERT 64+
1.3. Controller’sOverview
The EXPERT 64+ is an electronic device
used for environmental control in livestock
buildings. It allows the user to maintain a
specified target temperature by controlling
the operation of ventilation and heating
equipment. The controller can operate the
following inputs & outputs:
OUTPUTS:
- 8 heating stages;
- 5 fan outputs;
- 16 tunnel fan outputs;
- 6 cooling outputs;
- 12 clock outputs;
- 1 tunnel curtain output;
- 1 sidewall vent;
- 1 attic vent;
- 2 0-10V outputs to run common
light programs using LD-7000 light
dimmer modules.
- 1 Stir fan output.
INPUTS:
- 8 inside temperature probes;
- 1 outside temperature probe;
- 1 humidity sensor;
- 1 static pressure sensor;
- 2 water meters;
Refer to the end of this manual to con-
nect the sensors and loads.
1.4. MainFeaturesofthe
Controller
Very large LCD display — An LCD display
provides an efficient interface for displaying,
monitoring and adjusting parameter values.
5 Controller programs — The controller al-
lows using 5 different programs to control
the room temperature. It is thus possible to
activate a specific program, that uses par-
ticular temperature settings, in accordance
with the animal age for instance.
StatusLEDs— Pilot lights that indicate the
status of the controller outputs are located
on the faceplate of the controller. These
LEDs allow monitoring the system’s operation
without having to enter the building.
Minimumventilationcycle— When ventilation
is not required to reduce the house tempera-
ture, the fan outputs can run either continu-
ously or intermittently to reduce the humidity
level and supply oxygen to the room.
Recuperationofthewarmairintheattic— In
order to make energy savings, the controller
can extract the warm air from the attic and
send it back into the room.
Set point & minimum ventilation ramp —
The controller can automatically change
the temperature set point and the minimum
ventilation level with time as the animals are
growing up.
Probe readings recorded for past days —
Minimum and maximum readings of the static
pressure and humidity probes are recorded
for the current day and for the past 75 days.
The minimum and maximum readings of each
individual temperature probe is recorded for
the current day and for the past 7 days.
Watermonitoring— 2 pulse inputs are pro-
vided to monitor the water consumption for
the current day and the past 75 days.
Lightprograms — Up to 10 light programs
can be used.

8EXPERT 64+, rev.12
EXPERT 64+
Alarmmanagement— Alarms are provided
for high-low temperatures, defective probes
and other system functions.
HumidityControl— The control offers many
ways to compensate for high or low humid-
ity levels.
9independentprobetemperatureinputs— Up
to 8 inside temperature probes and 1 outside
temperature probe can be connected to the
controller in order to obtain a more accurate
reading of the average house temperature and
a faster reaction time.
Staticpressurecontrol— A static pressure in-
put is provided to control static pressure level
by opening and closing the vent doors.
Passwordprotection— A password feature
is used to restrict access to some of the
controller setup functions.
Backupbattery— A backup battery allows
the unit to keep time in case of a power
failure.
Overloadandovervoltageprotection— Re-
settable fuses are provided at low-voltage
inputs and outputs of the controller to pro-
tect its circuitry in the case of an overload
or overvoltage.
Computer control — The controller can be
connected to a computer, thus making it
possible to centralize the management of
information and diversify control strategies.
Test mode — This mode allows you to
simulate temperature changes and verify the
controller’s performance.
2. MOUNTINGINSTRUCTIONS
2.1. InstallingtheController
ontheWall
Open the latch and lift the cover. Remove the
black caps located on each of the four mounting
holes. Mount the enclosure on the wall using
four screws. Be sure the electrical knockouts
are at the bottom of the enclosure in order to
prevent water from entering the controller. Insert
the screws in the mounting holes and tighten.
Fasten the four black caps provided with the
controller onto the four mounting holes. The
enclosure must be mounted in a location that
will allow the cover to be completely opened
right up against the wall.
2.2. Connections
2.2.1. Controller’sMainWiring
Refer to the wiring diagram enclosed with
this user’s manual to connect the controller.
Use the electrical knockouts provided at the
bottom of the enclosure. Do not make ad-
ditional holes in the enclosure, particularly
on the side of the enclosure when using a
computer communications module.
All wiring must be done by an autho-
rized electrician and must comply with
applicable codes, laws and regulations.
Make sure power is off before doing any
wiring to avoid electrical shocks and
equipment damage.
2.2.2. AlarmConnection
There are two types of alarms on the market.
One type activates when current is cut off
at its input; the other type of alarm activates
when current is supplied at its input. For an
alarm of the first type, use the NC terminal as
shown on the wiring diagram. For an alarm of
the second type, use the NO terminal.

9
EXPERT 64+, rev.12
EXPERT 64+
2.2.3. SensorInputs
Sensors operate at low voltage and are isolated
from the supply. Make sure that sensor cables
remain isolated from all high voltage sources.
In particular, do not route the sensor cables
through the same electrical knockout as other
cables. Do not connect the shield from the
sensor cable to a terminal or a ground.
Extending a sensor: Each sensor can be
extended up to 500 feet (150 meters).
To extend a sensor: Use a shielded cable of
outside diameter between 0.245 and 0.260
in (6.22 and 6.60 mm) (the cable dimensions
should not be under 18 AWG) to ensure the
cable entry is liquid tight. Do not ground
theshielding.
It is preferable to solder the cable joint to
ensure a proper contact between the two
cables.
Do not run sensor cables next to other
power cables. When crossing over other
cables, cross at 90°.
Defective sensors: An alarm is generated
when a defective sensor is detected. Defec-
tive sensors are identified in the “Alarm Log”
menu. Refer to section 4.8 for further infor-
mation on the alarms.
2.2.4. 0-10VOutputConnection
It is recommended to use a 18 to 22 AWG
wire to connect the devices to the 0-10V
outputs. This type of output can be used to
connect various devices such as lights.
3. USERINTERFACE
3.1. LocationoftheCon-
trols
Main LCD Screen — The large LCD screen
is used to display the various parameters
and menus. The Current Conditions menu is
automatically selected after 4 minutes of
inactivity.
Contrast— Open the front cover of the con-
troller to access the potentiometer to adjust
the screen contrast. If no potentiometer is
located behind the front panel, the contrast
must then be changed directly into the trans-
fer menu (see chapter 12).
LCD Potentiometer
(opt.)
LED display — This screen shows the av-
erage room temperature and/or the static
pressure level.
StatusLEDs— The status pilot lights shows
the current status of the stages and outputs
of the controller. Refer to section 3.3 for
further information about these LEDs.
Arrow keys — Use these buttons to select
an item displayed in the main screen and to
change the value of a parameter.
Enter/Modifybutton— Press this key to ac-
cess a menu on screen or to enter the editing
mode (refer to section 3.2 for further informa-
tion about this mode).
Back— Press BACK to return to the previ-
ous menu.

10 EXPERT 64+, rev.12
EXPERT 64+
LCD Display
Arrow keys
LED Display
Status LEDs
3.2. HowtoSelect&Modify
theParameters
1. Use the arrow keys to select the desired
parameter. The message “Change : Press
Modify” is shown at the bottom of the display.
This means that the selected parameter can
be edited.
2. Press the “Enter/Modify” button to access
3.3. StatusLEDs
LED MEANING
ALARM Turns on when an alarm is active.
Flashes when an alarm condition occurred and was re-established by itself.
CLOCKS Turns on when a clock output is active
LIGHTS Turns on when the light output is active
VENT
DOORS
OPEN Turns on when a vent door is opening (sidewall and/or attic vent)
CLOSE Turns on when a vent door is closing (sidewall and/or attic vent)
TUNNEL
CUR-
TAIN
OPEN Turns on when the tunnel curtain is opening
CLOSE Turns on when the tunnel curtain is closing
COOL-
ING
2 Turns on when cooling output 4, 5 or 6 is active
1 Turns on when cooling output 1,2 or 3 is active
TUNNEL FANS 1-16 Turns on when tunnel fan group 1-16 is active
FANS 1-16 Turns on when fan group 1-16 is active
HEATERS 1-8 Flashes when one step of the heating output is operating (regular or high fire
step). Turns on when both steps of the heating output are operating (regular
and high fire steps).
the editing mode. The parameter then flashes
on the display.
3. Use the up and down-arrow keys to
change the value of the parameter.
4. Press the “Enter/Modify” button once
again to validate the new value and to exit
the editing mode.

11
EXPERT 64+, rev.12
EXPERT 64+
4. CONTROLLERSETUP
4.1. Time&Date
1. Select:
» 12.Setup
» 8.TimeandDate
TimeandDate
WedAug2720XX
7:07:07PM
2. Press the Enter/Modify button then use the
up and down- arrow keys to set the current
day of the week.
3. Press the Enter/Modify button to step to
the next item then use the up and down-arrow
keys to set the selected item.
4. Proceed in similar fashion to set the whole
time and date.
4.2. Password
This function allows identifying 2 different
types of users. The password is made up of
4 digits and it is used to restrict access to
certain functions of the controller. When a
correct password is entered, the current user
is identified.
InstallerPassword(default=0-6-1-0)
The installer mode gives full access to all the
controller functions. The installer password
can be modified as explained below.
UserPassword(default=1-1-1-1&2-2-2-2)
The user mode gives access to the basic
functions of the controller. The controller
automatically returns to the user mode after
15 minutes of inactivity. The user passwords
cannot be modified.
1. Select:
» 12.Setup
» 4.Password
Password
CurrentUser Installer
ChangeUser ****
ChangePassword ****
ConfirmPassword ****
Enteringapassword:Press the Enter/Modify
button then use the up and down- arrow keys
to enter the first digit of the password. Press
the Enter/Modify button once again to step to
the next digit.
Enter the 4 digits of the password then press
the Enter/Modify button once again to validate.
The user is then identified. The message
“Invalid password” is displayed if a wrong
password is entered.
2. Changing the installer password: The
installer password must first be entered as
shown above to be modified. The message
“Change Password” is displayed when the cur-
rent user is identified as the Installer. The new
installer password can then be entered.

12 EXPERT 64+, rev.12
EXPERT 64+
3. Confirming the newinstaller password:
Once the new installer password is entered,
the message “Conrm Password” is displayed.
Enter the new password once again to con-
firm the password. Press the Enter/Modify
button at the end to validate.
4.3. ControllerPrograms
Programdefinition:Programs are an assem-
bly of settings (temperature settings, relay
assignment, probe assignment, etc.) that
can be enabled at different moment of the
breeding process. In all, the controller can
use 5 different programs.
Make sure the right program is selected
before adjusting any parameter.
4.3.1. SelectingaProgram
1. Select:
»10.SelectProgram
SelectProgram
Runningprogram Program1
CleanModeStatus Off
DetectLoTemperature? No
2. Set the following parameters:
Runningprogram— Select the program that
must be used by the controller and then press
the Enter/Modify key to validate.
4.3.2. Copy/PastePrograms
Use the copy-paste function to duplicate all pa-
rameter settings associated to a program onto
another program. This avoids repeating the
same programming sequence several times.
1. Select:
» 12.ControllerSetup
» 5.Copy/PastePrograms*
* This menu is only accessible from the installer
mode (sec. 4.2).
Copy/PasteProgram
CopyFromProgram: 1
CopytoProgram: 3
Confirm? Yes
CopyInProgress... PleaseWait...
2. Set the following parameters:
Copy From Program — Select the source
program. The one that will be duplicated.
Copy to Program — Select the target pro-
gram. The one on which the copied program
will be pasted.
3. Once a different source and target
programs are selected, the message “Con-
rm?” is displayed. Select “Yes” to start the
program duplication. The message “Copy in
progress” is displayed. Wait until the data
transfer is over.

13
EXPERT 64+, rev.12
EXPERT 64+
4.4. InstallationSetup
The following section shows how to cus-
tomize the controller for your particular
application. It shows how to enable and set
the outputs of your controller. Normally, this
setup needs to be done only once.
Hint: A worksheet is available at the
end of this manual to write down your
Installation Setup parameters.
1. Select:
» 12.Setup
» 4.Installation*
* This menu is only accessible from the installer
mode (sec. 4.2).
2. Set the following parameters:
NumberofPrograms— The controller can use
several temperature programs. Enable the de-
sired number of programs (1 to 5 programs)
*This parameter is common to all programs of the
controller.
NumberofTemperatureProbes— Select the
number of inside temperature probes that are
connected to the controller (1 to 8 probes).
*This parameter is common to all programs of the
controller.
Number of Heaters — Enable the proper
number of heating outputs (0 to 8 outputs).
*Refer to the “Hi Fire” option below to increase the
number of heating outputs.
NumberofFans— Enable the proper number
of fan groups (1 to 5 groups).
NumberofTunnelFans— Enable the proper
number of tunnel fan groups (from 0 to
16 groups).
UseStirFans?— Select “Yes” to use the stir
fan output.
NumberofCooling— Enable the proper num-
ber of cooling outputs (0 to 6 outputs).
NumberofClocks— Enable the proper num-
ber of clock outputs. Adjustable from 0 to
12 outputs.
Number of Light Programs — Enable the
proper number of light programs (0 to 10 pro-
grams. *This parameter is common to all programs
of the controller.
ClockOutputs’OperationMode— The clock
mode allows stopping a clock output at a
certain time of the day or after a certain run
time. Select “Start/Stop” to specify the time at
which each cycle starts and stops or select
“Start/Run” to specify the running time of each
cycle. Note that the “Start/Run” option allows
stopping cycles with more precision since this
mode allows adjusting the seconds. Refer to
chapter 9 for further information about the
clock outputs. *This parameter is common to all
programs of the controller.
UseHeaterLo/HiFire?— Select “Yes” to acti-
vate the heating outputs’ Lo & Hi fire option.
This function allows doubling the number of
heating outputs.
Exit:PressBack Change:PressModify
Press toselectanitem
Installation
NumberofPrograms 3
NumberofProbes 8
NumberofHeaters 4
NumberofFans 3
NumberofTunnelFans 8
UseStirFans? Yes
NumberofCooling 6
NumberofClock 2
NumberofLightPrograms 2
ClockMode Start/Stop
UseHeaterLo/HiFire? Yes
UseDay/NightOnTime? Yes
NumberofVentDoors? 2
UseAtticProbe? Yes
UseTunnelCurtain? Yes
CurtainControl SP
Numberofrelays 32
MonitorBreakerTemperature? Yes
ShowOnDigitDisplay T°/SP

14 EXPERT 64+, rev.12
EXPERT 64+
4.5. Probes
4.5.1. Activatingtheprobeinputs
Follow these steps to enable or disable the
probe inputs.
1. Select:
» 12.Setup
» 4.Installation*
* This menu is only accessible from the installer
mode (sec. 4.2).
OptionalProbes
UseRelativeHumidity? Yes
NumberofWaterMeters 2
UseOutdoorTemperature? Yes
UseStaticPressure? Yes
2. Activate the desired probes:
- Humidity probe
- Water meters (0 to 2 meters)
- Outside temperature probe
- Static pressure probe
* These settings are common to all programs of the
controller.
UseDay/NightOnTime?— Select “Yes” to
use different minimum ventilation parameters
at night. *This parameter is common to all pro-
grams of the controller.
NumberofVentDoor?— Enable the proper
number of vent door outputs (0 to 2 vent
doors). * This parameter is available if the static
pressure sensor is enabled (sec. 4.5.1).
Use attic T° probe ? — Select “Yes” if a
temperature sensor is present in the attic.
* This parameter is accessible if 2 vent doors are
enabled above.
UseTunnelCurtain?— Select “Yes” to enable
the tunnel curtain output.
CurtainControl— Select whether the curtain
is controlled by the static pressure (SP) or by
the average house temperature. *This parameter
is available if the tunnel curtain is activated above. In
addition, the static pressure control can only be used if
the static pressure sensor is activated (sec. 4.5.1).
#of Relays — Select the number of relays
required (32, 40, 48, 56 or 64 relays. *This
parameter is common to all programs of the con-
troller.
MonitortheBreakerTemperature?— Select
“Yes” to monitor the temperature of the main
breaker. When this function is enabled, the
controller sounds an alarm if the breaker’s
temperature gets too high.
Shown on Digit Display — This is the in-
formation that is displayed on the red LED
display on the control panel. Choose the
information to be displayed: average house
temperature (T°), static pressure level (SP)
or an alternating display between the average
temperature and the static pressure level (T°/
SP). *The static pressure level can only be displayed
if the static pressure sensor is activated (sec. 4.5.1).
This parameter is common to all programs of the
controller.

15
EXPERT 64+, rev.12
EXPERT 64+
4.5.2. MeasuringUnits
1. Select:
» 12.Setup
» 2.Units
OptionalProbes
TimeMode AM/PM
Temperature °F
Water gal
StaticPressure “WC
2. Select the desired measuring units:
- Time display: AM/PM or 24 h;
- Temperature display: Celsius (°C) or
Fahrenheit (°F);
- Water: liters or gallons;
- Static pressure: Inches of water (“WC)
or Pascals (Pa).
* These settings are common to all programs of the
controller.
4.5.3. ProbeAssignment
PrincipleofOperation:This section explain how
to select temperature probes that are used to
measure the room temperature and how to assign
temperature probes that are used to control/
monitor the outputs of the controller.
HouseTemperature: Most cooling outputs of
the controller operate according to the aver-
age temperature in the room. The user must
choose what temperature probes are used to
measure this room temperature.
TunnelFans(TunnelProbeSet): The selec-
tion of probes that is used to measure the
room temperature can be changed in tunnel
ventilation to compensate for changes in
airflow patterns that can distort the room
temperature. If the second probe set is
enabled in the Installation Setup (sec. 4.4),
you must assign temperature probes to this
second probe set.
HeatingOutputs: Each regular heating out-
put and each Hi Fire heating output operates
according to the average temperature of its
assigned probes.
EmptyZones:A heating output that exclu-
sively uses probes that are not assigned to
the average room temperature is automati-
cally considered as being in an empty zone
(sec. 4.9).
CoolingOutputs: In sidewall ventilation, cool-
ing outputs operate according to the average
house temperature; in tunnel ventilation, they
operate according to the average temperature
measured by user-defined probes.
Attic Vent: The controller automatically in-
creases the “On Time” portion of the minimum
ventilation timer as the attic temperature de-
parts from its set point. Refer to section 6.4.3
for further information about this feature.
MainBreaker:A probe can be used to moni-
tor the temperature of the main breaker so
that the controller can sound an alarm if the
breaker’s temperature gets too high. Note
that the breaker’s probe selection is common
to all programs.

16 EXPERT 64+, rev.12
EXPERT 64+
4.5.4. Probes&WaterMeterCali-
bration
You can slightly adjust the reading of each
probe input in order to obtain accurate and
uniform readings from all probes. In addition,
if a water meter is used, you must calibrate
its water flow rate.
1. Select:
» 9.AdvancedSettings
»12.ProbeCalibrations*
* Only accessible from the installer mode (s.4.2).
ProbeCalibrations
RHProbeOffset 0%
SPProbeOffset .00“WC
WaterMeter1Calibration 1gal/p
WaterMeter2Calibration 1gal/p
OutTem.ProbeOffset 0.0°F
Temp.Probe1Offset 0.0°F
Temp.Probe2Offset 0.0°F
Temp.Probe3Offset 0.0°F
2. Adjust the reading of the probes (if
required).
RelativeHumidityProbe—The reading of the
humidity sensor can adjusted of ±3%.
StaticPressure(SP)Probe—The reading of
the static pressure probe can adjusted of ±
0.030”WC (±7Pa).
WaterMeters— Set the water flow per pulse
of each water meter. Adjustable from 1 to
100 gallons (or liters) per pulse.
TemperatureProbeOffsets— The reading of
the inside and outside temperature sensors
can adjusted of ±3°F (±1.7°C).
A template is available at the end of this
manual to write down your selection
of sensors.
1. Select
» 9.AdvancedSettings
»11.ProbeAssignment*
* This menu is only accessible from the installer
mode (sec. 4.2).
1 2 3 4 5 6 7 8
--- --- --- --- --- --- --- ---
HouseTemperatureProbeAssignment
2. Select the desired assignment menu:
House Temperature;
Tunnel Fans;
Heaters;
Coolings
Attic
Main Breaker.
3. Assign the desired temperature probes to
the selected output: select “ “ to assign a
probe or select “- - -“ for probes that are not
assigned to the output.

17
EXPERT 64+, rev.12
EXPERT 64+
4.6. RelativeHumidity(RH)
Control
The controller offers different ways to com-
pensate for high and low relative humidity
(RH) levels in the barn. This section shows
how to enable the desired RH compensation
functions.
1. RH Compensation on the Min Ventila-
tion Run Time: The humidity level can be
decreased by increasing the fans’ running
time (On Time) within the minimum ventila-
tion cycles. The fans’ running time increases
gradually as the house’s humidity level
exceeds the humidity set point. The entire
compensated running time is reached when
the humidity level exceeds the RH set point
by 10%.
RHComp.onMinimum
VentilationCycles
RHLevel
(%)
10%
RH Set Point
Maximum
On Time
Regular
On Time
Min Vent.
Run Time
Time
added
2. RHCompensationwiththeHeatingOut-
puts:The controller can compensate for high
humidity levels by activating the heaters in
timer mode. As the RH level increases, the
controller increases the “On Time” portion
of the heating timer to compensate for the
change. The maximum compensated heating
“On Time” is reached when the RH level is
10% above the RH Set Point.
RHComp.with
HeatingOutputs
RHLevel
(%)
10%
RH Set Point
Maximum
On Time
Minimum
On Time
Off Time
On Time of
the Heating
Timer
The RH heat timer is composed of an “On
Time” and of a “Cycle Time”. The heaters run
during the “On Time” and then stop until the
end of the “Cycle Time”. The “On Time” por-
tion of this cycle increases as the RH level
increases.
ON
OFF
Output
Status RHHeatTimer
Time
ON Time
Cycle
Time

18 EXPERT 64+, rev.12
EXPERT 64+
4.6.1. ActivatingtheRHCompen-
sationFunctions
1. Select:
» 12.Setup
» 3.RHCompensation*
* This menu is accessible if the humidity probe is
activated.
RelativeHumidityCompensation
Minimumventilation? Yes
Heaters? Yes
UseMistShutoff? Yes
MistonLowR.Humidity? Yes
2. Set the following parameters:
MinimumVentilation?— Select “Yes” to en-
able the RH compensation on the minimum
ventilation run time.
Heaters?— Select “Yes” to activate the heat-
ing outputs to compensate for hi humidity
levels.
Mist Shutoff? — Select “Yes” to stop the
cooling outputs when the humidity level is
too high. *This parameter is accessible if a cooling
output is enabled (sec. 4.4).
MistonLowR.Humidity?— Select “Yes” to
activate the cooling outputs, according to
a timer, when the humidity level is too low.
*This parameter is accessible if a cooling output is
enabled (sec. 4.4).
3. RH Compensation with the Cooling
Outputs
•HighRHcompensationwiththemist
cooling output: the controller can dis-
able the mist output if the RH level gets
higher than the “Mist Shutoff” limit.
•LowRHcompensationwithmistout-
puts:To compensate for low RH levels,
the controller can activate the misting
output in timer mode. The misting output
starts when RH levels drops below the
“Low RH Set Point”.

19
EXPERT 64+, rev.12
EXPERT 64+
4.6.2. RHCompensationParameters
1. Select
» 9.AdvancedSettings
»10.RelativeHumidityCompensation
* This menu is accessible if the humidity probe is
enabled.
Exit:PressBack Change:PressModify
Press toselectanitem
RHCompensationSettings
RelativeHumidityCompensation
AddMinVentsec 60sec
RHSetpoint 65%
HeaterCompensation
MinimumOnTime 15sec
MaximumOnTime 45sec
CycleTime 300sec
MistShutoff 85%
MistOnLow%RelativeHumidity
LowSetpoint 30%
OnTime 0:30(m:s)
OffTime 2:00(m:s)
2. Set the following parameters:
AddMinVentsec— Time that is added to
the fans’ running time, within the minimum
ventilation cycles, when the relative humidity
exceeds the RH Set Point by 10%. Adjustable
from 15 to 900 seconds in increments of
15 seconds. Select “Off” to deactivate this
function. *This parameter is accessible if the
RH compensation on the minimum ventilation is
activated.
RH Set Point — This is the humidity level
above which high RH compensation func-
tions start. Adjustable from 20 to 99% of
humidity (select Off to disable all high RH
comp functions). *This parameter is accessible if
the RH compensation on heaters or on the minimum
ventilation is activated.
Heatercompensation
The timer used by heating outputs is made
of an “On Time” and of a “Cycle Time”. Heating
outputs run during the “On Time” then stop
until the end of the “Cycle Time”. The “On
Time” portion of this cycle increases as RH
levels increase.
Minimum&MaximumOnTimes— Set the
minimum and maximum “On Times” of the
heating timer. The minimum “On Time” starts
being used when indoor humidity levels reach
the RH set point; the maximum “On Time” is
used when humidity levels are 10% above
the RH set point. * This parameter is accessible
if RH compensation with heating outputs is enabled
in section 4.6.
Cycle Time: — Set the “Cycle Time” of the
heating timer. *This parameter is accessible if RH
compensation with heating outputs is enabled.
MistShutoff— Set the humidity level above
which the cooling outputs stop running. *This
parameter is accessible if the mist shutoff compensa-
tion function is enabled.
LoSetPoint— Set the humidity level below
which misting units start running in timer
mode or select “Off” to disable this function.
*This parameter is accessible if the mist on low RH
compensation function is enabled.
On/Off Times— Set the “On Time” and the
“Off Time” of the misting timer.

20 EXPERT 64+, rev.12
EXPERT 64+
4.7. RelayAssignment
4.7.1. PrincipleofOperation
RelayPanels:The controller can activate up
to 64 On/Off relays; these relays are located
in external relay boxes. Up to two RP-32 relay
panels can be connected to the controller. Refer
to the wiring diagram enclosed with this manual
to connect relay panels to the controller.
VentDoor&TunnelCurtainRelays:Relays
13-14, 15-16, 29-30 and 31-32 the relay
panels have specially been designed to open/
close the vent doors and the tunnel curtain.
It is strongly recommend using these relays
for this specific purpose: this prevents acti-
vating both the OPEN and CLOSE relays, by
inadvertence, at the same time.
Fan&TunnelFanRelays:
•Timer-basedrelays:Fan groups and tunnel
fan groups can activate relays that operate
in timer mode. These relays allow activating
cooling devices such as mist units while a
specific fan/tunnel fan group is running. Se-
lect “TMR” on a relay to use this function.
•Open/closerelays:Relays can be used to
slightly open an air inlet at the start-up of a
fan/tunnel group and to close it when the
fan/tunnel fan group returns to a stop. The
inlet opens only once at the start-up of the
chosen fan/tunnel fan group and closes only
once when the group is disabled. The inlet’s
running time corresponds to the timer-based
relay’s On Time. Select “OPN” to assign an
opening relay or “CLO” to assign a closing
relay on a fan/tunnel fan group.
1 2 3 4 5 6 7 8
--- TMR --- --- --- --- ---
9 10 11 12 13 14 15 16
--- --- --- --- --- --- --- ---
17 18 19 20 21 22 23 24
OPN --- CLO --- --- --- --- ---
FanGroup1RelayAssignment
Selected output
This relay will run in timer
mode when fan group 1
is active
This relay will
runs when
fan group 1 is
active
This relay switches at the
startup of fan group 1. The
inlet opens once, during
the timer-based relays’
On time.
The relay switches when
fan group 1 returns to a stop.
The inlet closes once, during
the timer-based relays’
On time.
Relays 13-16 and 29-32 of the relay
panels have been designed to open
and close actuators (vent doors or
tunnel curtains).
Table of contents
Other Cumberland Temperature Controllers manuals