Cumberland EXPERT-50 User manual

Expert-50
Temperature Controller
USER'S MANUAL
M 890-00075 rev. 10 REV. 01


TABLE OF CONTENTS
Page
PRECAUTIONS ....................................................................... 4
FEATURES ............................................................................. 5
LOCATION OF THE CONTROLS ................................................ 7
INSTALLATION ...................................................................... 9
Mounting Instructions ............................................................ 9
Connections ........................................................................ 9
CONTROLLER SETUP ............................................................. 12
TEMPERATURE SETTINGS ..................................................... 17
Viewing Temperatures ........................................................ 17
Temperature Set Point ........................................................ 20
Temperature Curve............................................................. 21
TIME AND DATE FUNCTIONS ................................................. 24
MINIMUM VENTILATION ....................................................... 25
Principle of Operation .......................................................... 25
Minimum ventilation speed curve ........................................... 27
HUMIDITY CONTROL ............................................................ 29
AIR INLET CONTROL ............................................................. 34
HEATER SETTINGS ............................................................... 36
FAN SETTINGS .................................................................... 38
TUNNEL VENTILATION .......................................................... 44
CLOCK OUTPUTS ................................................................. 47
ALARM SETTINGS ................................................................ 49
WATER MONITORING ........................................................... 52
TEST MODE ......................................................................... 53
TECHNICAL SPECIFICATIONS ................................................ 54
FACTORY SETTINGS ............................................................. 55

4Expert-50 rev.10
We strongly recommend installing supplementary ventilation as well
as a back-up thermostat on at least one fan stage (refer to the
wiring diagram enclosed with this user's manual to connect the
thermostat).
Although overload and overvoltage protection is provided for the
controller circuits, we recommend installing additional protection
devices in the electrical panel.
The room temperature where the controller is located MUST AL-
WAYS REMAIN BETWEEN 32°F AND 104°F (0°C TO 40°C).
To avoid exposing the controller to harmful gases or excessive hu-
midity, it is preferable to install it in a corridor.
DO NOT SPRAY WATER ON THE CONTROLLER
PRECAUTIONS
FOR CUSTOMER USE
Enter the serial number located on
the side of the controller below for
future reference.
Model number:
Serial number:
Expert-50

5
Expert-50 rev.10
The Expert-50 is an electronic device used for environmental control in
livestock buildings. It allows the user to maintain a specified target
temperature by controlling the operation of ventilation and heating equip-
ment. Eight heater stages, 15 fan stages, tunnel curtains and 4 clock
outputs can be connected to the controller. Fan stages can be configured
to activate cooling systems in timer mode. In all, the Expert-50 provides
up to 32 relay outputs and 2 variable-speed outputs. In addition, up to 12
air inlet modules can be connected to the Expert-50.
The main features of the Expert-50 are as follows:
LCD DISPLAY
An LCD display provides an efficient interface for displaying, monitoring
and adjusting parameter values.
PILOT LIGHTS
Pilot lights indicating the state of outputs allow the user to monitor the
operation of the system without having to enter the building.
MINIMUM VENTILATION CYCLE
When ventilation is not required for reducing room temperature, vari-
able-speed outputs can be operated either continuously or intermittently
to reduce the level of humidity and supply oxygen to the room.
TEMPERATURE AND MINIMUM VENTILATION CURVES
The controller can be set to automatically change the temperature set
point and the minimum ventilation fan speed over a given period of time
in accordance with the user's requirements by specifying a temperature
curve and a minimum ventilation speed curve with ten different points
each.
PROBE READINGS RECORDED FOR PAST DAYS
Minimum and maximum readings from temperature and humidity probes
are recorded for the current day and the previous six days.
WATER MONITORING
A pulse input is provided for monitoring water consumption for the
current days and the previous six days.
ALARM MANAGEMENT
Alarms are provided for high-low temperatures, defective probes and
other system functions. Alarm states are kept in memory until acknowl-
edged even if alarm situation has been rectified.
FEATURES

6Expert-50 rev.10
Expert-50
HUMIDITY COMPENSATION
The minimum ventilation speed can be adjusted automatically as a
function of relative humidity. Cooling units can be shut off when humid-
ity levels are too high. In addition, heater outputs can be activated when
humidity levels are too high.
SIX INDEPENDENT TEMPERATURE PROBE INPUTS
Up to six temperature probes can be connected to the controller in order
to obtain a more accurate reading of the average room temperature and
a faster reaction time. Probes can be configured to use zoned heaters.
PASSWORD PROTECTION
A password feature can be enabled to restrict access to the controller
setup functions.
BACKUP BATTERY
A backup battery allows the unit to keep time in case of a power failure.
OVERLOAD AND OVERVOLTAGE PROTECTION
Resettable fuses are provided at low-voltage inputs and outputs of the
controller to protect its circuitry in the case of an overload or overvolt-
age.
COMPUTER CONTROL
The controller can be connected to a computer, thus making it possible
to centralize the management of information and diversify control
strategies.
TEST MODE
A test mode allows you to simulate temperature changes and verify
controller performance, as well as manually activate each output sequen-
tially.
CONTROL OF AIR INLET MOVEMENT
If the Expert-50 is used in combination with one or more air inlet mod-
ules, the movement of air inlets can be coordinated with the operation of
the fans using a potentiometer located on the panel drive. This allows the
air inlets to be adjusted correctly, without the influence of uncontrollable
factors such as wind or air from adjoining rooms.

7
Expert-50 rev.10
LOCATION OF THE CONTROLS
/&'',63/$< 287387
67$786
2873876(/(&7
%877216
0(186(/(&7
%877216
)81&7,216
/('',63/$<
$552:
.(<6

8Expert-50 rev.10
Expert-50
Room Temperature Display: The display on the top right corner of the
faceplate shows the current room temperature averaged over all se-
lected room temperature probes.
LCD Display: The LCD display on the left gives the current readings and
parameters to be adjusted when you select a function. The three keys
to the right of the display are used to edit parameters and step through
the display. When the parameters for a given function cannot all be
presented at once on the display, arrows are displayed on the right hand
side to indicate that additional parameters can be displayed using the
arrow keys .
After 5 minutes of inactivity, the
display returns to the ROOM TEM-
PERATURE display.
Adjusting a Parameter: A parameter can be adjusted when it is flashing
on the LCD display. Use the Edit key to step through the param-
eters displayed. When the required parameter is flashing, use the arrow
keys on the top right to adjust the parameter.
To step to another display screen, it may be necessary to press
the Edit key several times to step through the remaining
parameters displayed until the up- and down-arrows reappear to
the right of the display.
Room 76.9°F
Probes: 1 2 3

9
Expert-50 rev.10
&&&& &&
ALL WIRING MUST BE DONE BY AN AUTHORIZED ELECTRICIAN
AND MUST COMPLY WITH APPLICABLE CODES, LAWS AND
REGULATIONS. BE SURE POWER IS OFF BEFORE DOING ANY
WIRINGTOAVOIDELECTRICALSHOCKSANDEQUIPMENTDAMAGE.
INSTALLATION
MOUNTING INSTRUCTIONS
Open the latch and lift the cover. Remove the black caps located on
each of the four mounting holes. Mount the enclosure on the wall using
four screws. Be sure the electrical knockouts are at the bottom of the
enclosure in order to prevent water from entering the controller. Insert
the screws in the mounting holes and tighten. Fasten the four black caps
provided with the controller onto the four mounting holes. The enclosure
must be mounted in a location that will allow the cover to be completely
opened right up against the wall.
CONNECTIONS
To connect the controller, refer to the wiring diagram enclosed with this
user's manual. Use the electrical knockouts provided at the bottom of
the enclosure. Do not make additional holes in the enclosure, particularly
on the side of the enclosure when using a computer communications
module.
1. PROBE INPUTS
!
WARNING
ROOM T° PROBES 1 TO 6
WATER
METER
HUMIDITY
PROBE INPUT
HUMIDITY PROBE
POWER

10 Expert-50 rev.10
Expert-50
Probes operate at low voltage and are isolated from the supply.
Be sure that probe cables remain isolated from all high voltage
sources. In particular, do not route the probe cables through the
same electrical knockout as other cables. Do not connect the
shield from the probe cable to a terminal or a ground.
Extending a probe: Each probe can be extended up to 500 feet (150
meters). To extend a probe:
Use a shielded cable of outside diameter between 0.245 and
0.260 in (6.22 and 6.60 mm) (the cable dimensions should not be
under 18 AWG) to ensure the cable entry is liquid tight. Do not
ground the shielding.
It is preferable to solder the cable joint to ensure a proper contact
between the two cables.
CAUTION: Do not run probe cables next to other power cables. When
crossing over other cables, cross at 90°.
Defective probes: An alarm is generated when a defective probe is
detected. To identify the defective probe, select the functions, PROBE
TEMPERATURES and RELATIVE HUMIDITY. Dashes are displayed
instead of a reading when the probe is defective. In the case of room
temperature probes, the controller will operate according to the tem-
perature of the remaining probes.
2. RELAY PANELS
Use a shielded cable with two twisted pairs. Connect the shielding to
the SH terminal. Use one pair for terminals 1 and 4 and the other pair
for terminals 2 and 3.
2 413SH
RELAY PANELS
ONE PAIR
ONE PAIR

11
Expert-50 rev.10
Expert-50
There are two types of alarms on the market. One type activates when
current is cut off at its input, whereas the other activates when current
is supplied at its input. For an alarm of the first type, use the NC termi-
nal as shown on the wiring diagram. For an alarm of the second type,
use the NO terminal.
4. AIR INLET MODULE COMMUNICATION HOOKUP
If air inlet modules are connected to the Expert-50, use id numbers
within the range 4-15. Id numbers 1,2 and 3 are reserved for the
Expert-50 and relay panel.
3. ALARM AND POWER SUPPLY
CNNC NO L
ALARM 90-260 VAC
47-70HZ

12 Expert-50 rev.10
CONTROLLER SETUP
The following section describes how to customize the controller for your
particular application. Normally, this setup needs to be done only once.
Setup parameters are grouped under two functions: USER and OUT-
PUTS. The USER setup is used for configuring display units, probe
inputs, humidity compensation, the fan differential, etc. The OUTPUTS
setup is used for configuring the outputs.
The parameters are presented below in the order they appear on the
display. Press the down-arrow key to step to the next parameter. Press
the Edit key and use the arrow keys to adjust a parameter value. When
you are finished adjusting a parameter, press the Edit key to return to
display mode or move to the next parameter. The user should step
through all the parameters under these two functions at least once.
USER SETUP
1. Display Contrast and Backlight:
Press the Edit key to adjust the display
contrast. Press the Edit key once again
to turn the display backlight on or off.
Note that the backlight is automatically
turned off after 5 minutes of inactivity
even if it is turned on. It is turned on
again when a key is pressed.
2. Time of Day Format: Press the Edit
key to select either AM-PM or 24H time.
3. Number of Temperature Probes in
the Room: Press the Edit key to set the
number of room temperature probes
wired in the controller (whether they are
selected or not). Note that probes must
be wired from left to right following the
numerical order of the terminals on the
board if 4 probes are not needed.
Contrast: 11
Backlight: Y S
Time of day
format: AM-PM
# T° sensors
in the room : 4

13
Expert-50 rev.10
Expert-50
RH influence on
min. vent.? Y S
RH influence on
Cooling? Y S
Use humidity
sensor (RH)? Y S
Use water
meter? Y S
Temperature
units: °F
Fan Start-Stop
T° diff: 1.5°F
4. Use Humidity Sensor: Press the
Edit key and set to YES if a relative
humidity sensor is connected to the
unit.
5. Use Water Meter: Press the Edit
key and set to YES if a water meter is
connected to the unit.
6. Temperature Units: Press the Edit
key and choose between Fahrenheit
and Celsius degrees for displaying
temperature values.
7. Fan Start-Stop Temperature
Difference: Press the Edit key and
adjust the maximum temperature
difference between start and stop
temperatures on fan stages.
8. Variable-Speed Fan Minimum
Speeds: Press the Edit key and adjust
the minimum speed for the first
variable output. Repeat for the second
variable output.
9. Humidity Compensation on Mini-
mum Ventilation: Press the Edit key
and set to YES to enable humidity
compensation on the minimum ventila-
tion cycle.
10. Humidity Compensation on
Heating: Press the Edit key and set to
YES to enable humidity compensation
on heating.
11. Humidity Compensation on
Cooling Stages: Press the Edit key
and set to YES to enable humidity
compensation on cooling outputs.
V1 Min. spd: 10 %
V2 Min. spd: 10 %
RH influence on
Heating ? Y S

14 Expert-50 rev.10
Expert-50
Change
password NO
Old password?
0 ** **
New password?
0 ** **
Confirm new:
0 ** **
12. Water meter units: Press the Edit
key and choose between gallons and li-
ters for displaying water consumption.
13. Water Meter Calibration: Press
the Edit key and adjust the number of
gallons or liters per water meter pulse.
14 Change Password: The user can define a password to restrict access
to the functions contained in the SETUP section (USER, OUTPUTS and
TEST). The password must be entered each time one of these functions is
selected. When the correct password is entered, it does not need to be re-
entered until the display times out (i.e. after 5 minutes of inactivity). The
password is a sequence of three numbers from 0 to 99. To disable the
password feature, set the password to 0 0 0.
Press the Edit key. The change
password state flashes. Use the
arrow keys to set the change pass-
word state to YES.
The old password must be entered,
one number at a time. Use the ar-
row keys to enter the first number.
Press the Edit key to step to the next
number. Use the arrow keys to enter the second number, etc.
The new password must be entered,
one number at a time. Use the ar-
row keys to enter the first number.
Press the Edit key to step to the next
number. Use the arrow keys to
enter the second number, etc.
The new password must be con-
firmed, one number at a time. Use
the arrow keys to enter the first
number. Press the Edit key to step
to the next number. Use the arrow
keys to enter the second number,
etc.
Water meter
units: gallons
Water meter
gal/pulse 1.00

15
Expert-50 rev.10
Expert-50
Output Setup
1. Number of Heaters and Fan
Stages: Press the Edit key to adjust
the number of heaters used. Press
the Edit key once again to adjust the
number of fan stages.
2. Number of Clock Outputs/Tunnel
Ventilation : Press the Edit key to set
the number of clock outputs used.
Press the Edit key once again to
enable or disable tunnel ventilation.
3. Number of Inlets : Press the Edit
key to set the number of air inlet
modules.
4. Heater Probes on Heaters 1 - 8 :
Use the adjustment knob to select a
heater stage. The probes assigned to
the heater appear flashing on the dis-
play. Press the Edit key and use the arrow keys to enable or disable each
probe individually for the heater. Press the down-arrow key to configure
the relays for each heater (see below).
When the down-arrow key is pressed at this point, the LED of the last
heater configured above flashes and the probe assignments for that heater
are displayed. The user can now configure each output separately by
selecting the output using the output select buttons and adjusting the pa-
rameters displayed. Configuration parameters vary according to the type
of output. For example, probes are assigned when configuring a heater
stage. Use the up- and down-arrow keys to step through all the display
screens for a given output. The last display screen for all outputs is the
relay assignment.
#Heaters: 8
#Fan stages: 15
#Clocks: 4
Use tunnel? Y S
#Inlets 12
Heater 8 Probes
1 2 3 4

16 Expert-50 rev.10
Expert-50
Use some relays
on timer? NO
Relays 1-8
12t45678
Relay Assignments: The Expert-50 can
control up to 32 output relays. The
mapping between the stages and the re-
lays must be determined by the user.
The relays are displayed in groups of 8
relays at a time. The relays assigned to
an output correspond to the flashing
numbers on the display. Press the Edit
key to display each relay state and use
the arrow keys to assign (ON) or
deassign (OFF) the relay. Use the down-
arrow key to step to the next bank of
relays. Use the template at the end of
this manual to map the relays before
assigning them from the front panel. Use the TEST function to test all relay
assignments.
Variable Output Assignments: The Ex-
pert-50 controls two variable outputs
for variable-speed fans. Each fan stage
can use these outputs in variable or on-
off mode. Press the Edit key and set the mode to 'Var' for variable, 'ON'
for ON-OFF or 'OFF' to deactivate the output. Note that the variable out-
puts cannot be configured in variable mode on the last fan stage.
5. Relays with Timer on Fan Stages 2-
15: For these fan stages, the user can
configure certain relays to operate in
timer mode for cooling while other re-
lays operate in on-off mode. Press the
Edit key and set the timer mode to YES
to configure certain relays in timer mode
for cooling. Press the down-arrow key
to map the relays. If timer mode is set to YES, the user can choose be-
tween ON, OFF and timer when selecting a relay. When a relay is in timer
mode, the digit of the relay alternates with the letter t.
6. Clock Mode on Clock Outputs: The
user must choose between Start-Stop
and Start-Running Time for the clock
outputs. Press the Edit key and use the
arrow keys to configure each output. Press the down-arrow key to map
the relays to the output (see above).
Relays 1-8
12345678
Relays 9-16
90123456
Relays 17-24
78901234
Relays 25-32
56789012
Clock Mode:
Start-Stop
V1 : Var
V2 : Var

17
Expert-50 rev.10
TEMPERATURE SETTINGS
VIEWING TEMPERATURES
The user can display the current average room temperature and indi-
vidual probe temperatures. The controller also records the minimum and
maximum temperature values for the current day and the past 6 days
along with the clock time. The controller starts recording minimum and
maximum values at midnight every day.
Viewing Room Temperature
The room temperature is the average value of all temperatures measured
by selected probes in proper operating condition.
Set the function to ROOM TEM-
PERATURE using the menu select
buttons. The average room
temperature is displayed as well as
the probes selected for room
average.
Press the down-arrow key. The
minimum temperature value for
the current day is displayed, along
with the time and date.
Press the down-arrow key once again. The maximum temperature
value for the current day is displayed, along with the time and date.
Keep pressing the down-arrow key to display the minimum and
maximum temperature values for the previous six days. Use the up-
arrow key to return to the previous display screens.
Room 03/10/00
min 74.1 09:06A
Room 76.7°F
Probes: 1 2 3 4

18 Expert-50 rev.10
Expert-50
Viewing Probe Temperatures
The controller can display probe temperatures individually whether the
probe is selected or not for room average. Unconnected probes are
displayed as OFF and their minimum and maximum values cannot be
displayed. For example, if two probes are wired to the controller, then
probes 5 and 6 will be displayed as OFF.
Set the function to PROBE TEMPERATURE using the menu select
buttons. Individual probe temperatures are displayed for the first
four probes connected to the controller.
Press the down-arrow key. The temperature of probes 5 and 6 are
displayed.
Press the down-arrow key. The minimum temperature value for
Probe 1 for the current day is displayed, along with the time and
date.
Press the down-arrow key once again. The maximum temperature
value for Probe 1 for the current day is displayed, along with the
time and date.
Keep pressing the down-arrow key to display the minimum and
maximum temperature values for the remaining probes. Once all
probes have been displayed, the display shows recorded minimum
and maximum probe temperatures for the previous six days. Use the
up-arrow key to return to the previous display screens.

19
Expert-50 rev.10
Expert-50
Probes: 123-5
Average Temperature Probes
The controller uses the average reading of the activated probes to
calculate the room temperature. Select the temperature probes that are
used to monitor the ambient temperature. At least 1 temperature probe
must be selected.
Set the function to ACTIVE TEMPERATURE PROBES using the menu
select buttons. The temperature probes are displayed.
Press the Edit key in order to
select the desired probe.
Use the arrow keys to set the probe status. A dash indicates that the
probe is not used to calculate the average room temperature.

20 Expert-50 rev.10
Expert-50
TEMPERATURE SET POINT
The temperature set point is the target room temperature. It can be
adjusted between -40.0°F and 100°F (-40.0°C and 37.8°C). Note that
the temperature curve must be turned off to adjust this value.
Adjusting Temperature Set Point
Set the function to ROOM SET
POINT / CURVE using the menu
select buttons. The current set
point is displayed, as well as the
on/off state of the temperature curve.
If the temperature curve is OFF, press the Edit key once. The set
point flashes on the display. Use the arrow keys to adjust the set
point to the desired value.
If the temperature curve is ON, the temperature value displayed is
the set point as determined by the temperature curve. Press the Edit
key. The on/off state of the temperature curve starts flashing. Use
the adjustment knob to turn the curve off. Press the Edit key twice.
The temperature set point flashes on the display. Use the arrow
keys to adjust the set point to the desired value.
74.5°F curveOFF
Table of contents
Other Cumberland Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Water-Loo
Water-Loo ABM 300 Series Operating and maintenance instructions

Bitron Video
Bitron Video AV2010/27A quick start guide

Austro Flamm
Austro Flamm SmartSpot User instructions

flakt woods
flakt woods STRA-04 Installation & maintenance manual

Thermo Solar
Thermo Solar SR24 Installation and operating instructions

Pro-tec
Pro-tec PROFLAT PRTR Series instruction manual