Cumberland Expert-32T User manual

Expert-32T
Temperature Controller
USER'S MANUAL
T


TABLE OF CONTENTS
Page
PRECAUTIONS ......................................................................... 4
FEATURES ............................................................................... 5
LOCATION OF THE CONTROLS.................................................. 8
INSTALLATION ...................................................................... 10
Mounting Instructions ............................................................ 10
Connections ........................................................................ 10
CONTROLLER SETUP ............................................................... 13
ROOM 1 / ROOM 2 .............................................................. 13
User Setup .......................................................................... 14
Relay Assignments ............................................................... 18
Probe Assignments ............................................................... 21
TEMPERATURE SETTINGS ....................................................... 22
Viewing Temperatures .......................................................... 22
Temperature Set Points ......................................................... 25
Temperature Curve............................................................... 27
TIME AND DATE FUNCTIONS ................................................... 29
MINIMUM VENTILATION ......................................................... 30
Principle of Operation ............................................................ 30
Minimum Ventilation Curve .................................................... 32
HEATER SETTINGS ................................................................. 34
FAN SETTINGS ...................................................................... 36
COOLING .............................................................................. 39
TUNNEL VENTILATION ............................................................ 41
VENT DOORS ......................................................................... 45
AIR INLET CONTROL ............................................................... 50
CLOCK OUTPUTS ................................................................... 51
ALARM SETTINGS .................................................................. 53
MONITORING FUNCTIONS ....................................................... 58
CLEAN MODE ........................................................................ 60
TEST MODE ........................................................................... 62
TECHNICAL SPECIFICATIONS .................................................. 63
FACTORY SETTINGS ............................................................... 64
USING THE CONFIGURATION MODULE ...................................... 66
Loading a Configuration ......................................................... 66
Saving a Configuration .......................................................... 67
INSTALLATION REPORT .......................................................... 68

4Expert-32T rev.03
We strongly recommend installing supplementary ventilation as
well as a back-up thermostat on at least one fan stage (refer to
the wiring diagram enclosed with this user's manual to connect
the thermostat).
Although overload and overvoltage protection is provided for the
controller circuits, we recommend installing additional protec-
tion devices in the electrical panel.
The room temperature where the controller is located MUST
ALWAYS REMAIN BETWEEN 32°F AND 104°F (0°C TO
40°C).
To avoid exposing the controller to harmful gases or excessive
humidity, it is preferable to install it in a corridor.
DO NOT SPRAY WATER ON THE CONTROLLER
PRECAUTIONS
FORCUSTOMERUSE
Enter the serial number located on
the side of the controller below for
future reference.
Model number:
Serial number:
Expert-32T

5
Expert-32T rev.03
The Expert-32T is an electronic device used for environmental control in
livestock buildings. It allows the user to maintain a specified target
temperature in two independent rooms by controlling the operation of
ventilation and heating equipment. Each room can operate up to 8
heater stages, 10 on-off fan stages, 2 cooling outputs vent doors, tunnel
curtains and 2 clock outputs. Fan stages can be configured to activate
cooling systems in timer mode. In all, the Expert-32T provides up to 32
relay outputs. In addition, if vent doors are not used, up to 12 PF-6 air
inlet controllers can be connected to the unit.
The main features of the Expert-32T are as follows:
LCD DISPLAY
An LCD display provides an efficient interface for displaying, monitoring
and adjusting parameter values.
PILOT LIGHTS
Pilot lights indicating the state of outputs allow the user to monitor the
operation of the system without having to enter the building.
MINIMUM VENTILATION CYCLE
When ventilation is not required for reducing room temperature, the first
and second fan stages can be operated either continuously or intermit-
tently to reduce the level of humidity and supply oxygen to the room.
TEMPERATURE AND MINIMUM VENTILATION CURVES
The controller can be set to automatically change the temperature set
point and the minimum ventilation cycle over a given period of time in
accordance with the user's requirements by specifying a temperature
curve and a minimum ventilation cycle curve with up to ten different
points each.
PROBE READINGS RECORDED FOR PAST DAYS
Minimum and maximum readings from temperature and static pressure
probes are recorded for the current day and the previous six days.
FEATURES

6Expert-32T rev.03
Expert-32T
WATER MONITORING
A pulse input is provided for monitoring water consumption for the
current days and the previous six days.
ALARM MANAGEMENT
Alarms are provided for high-low temperatures, defective probes and
other system functions. Alarm states are kept in memory until acknowl-
edged even if alarm situation has been rectified.
FOUR INDEPENDENT TEMPERATURE PROBE INPUTS
Up to four temperature probes can be connected to the controller in
order to obtain a more accurate reading of the average room tempera-
ture and a faster reaction time. Probes can be configured to use zoned
heaters.
STATIC PRESSURE CONTROL
A static pressure input is provided to control static pressure by opening
and closing the vent doors.
CONTROL OF AIR INLET MOVEMENT
If the Expert-32T is used in combination with one or more PF-6 control-
lers, the movement of air inlets can be coordinated with the operation of
the fans using a potentiometer located on the panel drive. This allows
the air inlets to be adjusted correctly, without the influence of uncontrol-
lable factors such as wind or air from adjoining rooms.
TWO PROBE SETS
The probe selection for calculating room temperature can be changed at
some point in the ventilation curve to compensate for changes in airflow
patterns that can distort the room temperature calculation.
PASSWORD PROTECTION
A password feature can be enabled to restrict access to the controller
setup functions.
BACKUP BATTERY
A backup battery allows the unit to keep time in case of a power failure.

7
Expert-32T rev.03
Expert-32T
OVERLOAD AND OVERVOLTAGE PROTECTION
Resettable fuses are provided at low-voltage inputs and outputs of the
controller to protect its circuitry in the case of an overload or overvolt-
age.
COMPUTER CONTROL
The controller can be connected to a computer, thus making it possible to
centralize the management of information and diversify control strate-
gies.
TEST MODE
A test mode allows you to simulate temperature changes and verify
controller performance.

8Expert-32T rev.03
LOCATION OF THE CONTROLS
T
/&'',63/$<
28738767$786
2873876(/(&7
%877216
0(186(/(&7
%877216
)81&7,216

9
Expert-32T rev.03
Expert-32T
Room Temperature Display: The display on the top right corner of the
faceplate shows the current room temperature averaged over all se-
lected room temperature probes or the static pressure.
LCD Display: The LCD display on the left gives the current readings and
parameters to be adjusted when you
select a function. The three keys to
the right of the display are used to
edit parameters and step through
the display. When the parameters
for a given function cannot all be
presented at once on the display, arrows are displayed on the right hand
side to indicate that additional parameters can be displayed using the
arrow keys . After 15 minutes of inactivity, the display
returns to the ROOM TEMPERATURE display.
Adjusting a Parameter: A parameter can be adjusted when it is flashing
on the LCD display. Use the Edit key to step through the param-
eters displayed. When the required parameter is flashing, use the arrow
keys next to the display to adjust the parameter.
To step to another display screen, it may be necessary to press
the Edit key several times to step through the remaining param-
eters displayed until the up- and down-arrows reappear to the
right of the display.
Output Status LEDs: The LEDs on the right of the control panel give the
status of each output. When the LED is turned on, the output is acti-
vated; when the LED is turned off, the output is deactivated. In the
case of the fan stages, a flashing LED indicates that the activation of the
fan stage is delayed by the opening of the curtain.
Room 76.9°F
Probes: 1 2 3

10 Expert-32T rev.03
ALL WIRING MUST BE DONE BY AN AUTHORIZED ELECTRI-
CIAN AND MUST COMPLY WITH APPLICABLE CODES,
LAWS AND REGULATIONS. BE SURE POWER IS OFF BEFORE
DOING ANY WIRING TO AVOID ELECTRICAL SHOCKS AND
EQUIPMENT DAMAGE.
INSTALLATION
MOUNTING INSTRUCTIONS
Open the latch and lift the cover. Remove the black caps located on each
of the four mounting holes. Mount the enclosure on the wall using four
screws. Be sure the electrical knockouts are at the bottom of the
enclosure in order to prevent water from entering the controller. Insert
the screws in the mounting holes and tighten. Fasten the four black caps
provided with the controller onto the four mounting holes. The enclosure
must be mounted in a location that will allow the cover to be completely
opened right up against the wall.
CONNECTIONS
To connect the controller, refer to the wiring diagram enclosed with this
user's manual. Use the electrical knockouts provided at the bottom of
the enclosure. Do not make additional holes in the enclosure, particularly
on the side of the enclosure when using a computer communications
module.
1. PROBE INPUTS
!
WARNING
&&&&&
6(1625,1387
6
287 ,1387
&

11
Expert-32T rev.03
Expert-32T
Probes operate at low voltage and are isolated from the supply.
Be sure that probe cables remain isolated from all high voltage
sources. In particular, do not route the probe cables through the
same electrical knockout as other cables. Do not connect the
shield from the probe cable to a terminal or a ground.
Extending a probe: Each probe can be extended up to 500 feet (150
meters). To extend a probe:
Use a shielded cable of outside diameter between 0.245 and 0.260
in (6.22 and 6.60 mm) (the cable dimensions should not be under 18
AWG) to ensure the cable entry is liquid tight. Do not ground the
shielding.
It is preferable to solder the cable joint to ensure a proper contact
between the two cables.
CAUTION: Do not run probe cables next to other power cables. When
crossing over other cables, cross at 90°.
Defective probes: An alarm is generated when a defective probe is
detected. To identify the defective probe, select the functions, PROBE
TEMPERATURES and STATIC PRESSURE. Dashes are displayed instead
of a reading when the probe is defective. In the case of room tempera-
ture probes, the controller will operate according to the temperature of
the remaining probes.
2. RELAY PANELS
Use a shielded cable with two twisted pairs. Connect the shielding to the
SH terminal. Use one pair for terminals 1 and 4 and the other pair for
terminals 2 and 3.
2 413SH
RELAY PANELS
ONE PAIR
ONE PAIR

12 Expert-32T rev.03
Expert-32T
There are two types of alarms on the market. One type activates when
current is cut off at its input, whereas the other activates when current
is supplied at its input. For an alarm of the first type, use the NC termi-
nal as shown on the wiring diagram. For an alarm of the second type,
use the NO terminal.
4. COMMUNICATION HOOKUP
If PF-6 air inlet controllers are connected to the Expert-32T, use id
numbers within the range 4-15. Id numbers 1-3 are reserved.
3. ALARM AND POWER SUPPLY
CNNC NO L
ALARM 90-260 VAC
47-70HZ

13
Expert-32T rev.03
CONTROLLER SETUP
The following section describes how to customize the controller for your
particular application. Normally, this setup needs to be done only once.
Setup parameters are grouped under the functions: ROOM1 / ROOM2,
USER, RELAY ASSIGNMENT and PROBE ASSIGNMENT. The controller
can control two different rooms at the same time. The ROOM1 /
ROOM2 setup is used to select the room on which the settings will be
applied on. The USER setup is used for configuring display units, probe
inputs, etc. The RELAY ASSIGNMENT setup is used for configuring the
outputs. The PROBE ASSIGNMENT setup is used to make probe assign-
ments.
The parameters are presented below in the order they appear on the
display. Press the down-arrow key to step to the next parameter. Press
the Edit key and use the arrow keys to adjust a parameter value. When
you are finished adjusting a parameter, press the Edit key to return to
display mode or move to the next parameter. The user should step
through all the parameters under these functions at least once.
ROOM 1 / ROOM 2
The Expert-32T can operate ventilation and heating equipment in order
to maintain the target temperature in two seperate rooms. Each room
operates independently one from the other, each of them has its own
temperature set point and its own parameter settings. It is like having
two seperate controllers in one.
The pilot light next to ROOM1 or ROOM 2 of the output status indicates
which room is selected. All adjustments being done will only be effective
on the selected room. All parameters must be set seperately from one
room to the other so make sure to select the correct room before setting
any parameter. Few parameters in the user setup are common to both
rooms.
SELECTING A ROOM:
Select the Room1 / Room2 menu
using the menu select buttons. The
selected room is displayed.
Room select
Room 1

14 Expert-32T rev.03
Expert-32T
Press the Edit key to modify the selected room then use the up or
down-arrow key to select the desired room. Note that the Room1 /
Room2 feature must be activated in the user setup in order to select
room 2 (see User Setup #18).
Press the Edit key once again to validate. The pilot light next to the
selected room is turned on in the output status.
USER SETUP
1. Display Contrast: Press the Edit key
then use the up and down-arrow keys
to adjust the display contrast. This
parameter is commun to both rooms.
2. Time of Day Format: Press the Edit
key then use the up or down-arrow key
to select either AM-PM or 24H time.
This parameter is commun to both
rooms.
3. Number of Temperature Probes in
the Room: Press the Edit key to set the
number of room temperature probes
wired in the controller (whether they
are selected or not). Note that probes
must be wired from left to right follow-
ing the numerical order of the terminals
on the board if 4 probes are not
needed.
4. Probe Set 2 Starting Stage: This
parameter determines the fan stage at
which probe set 2 is used to calculate
the average temperature. Press the Edit
key to set the fan stage number (set to
OFF to use only one probe set).
Contrast: 50
Time of da
format: AM-PM
#T° sensors in
the room: 4
Use probe set 2
at stage: OFF

15
Expert-32T rev.03
Expert-32T
5. Probe Set 1 - Probes Used: The
selected probes for probe set 1 flash on
the display. Press the Edit key and use
the arrow keys to select or deselect
each probe individually for set 1.
6. Probe Set 2 - Probes Used: The
selected probes for probe set 2 flash on
the display. Press the Edit key and use
the arrow keys to select or deselect
each probe individually for set 2.
7. Use Water Meter: Press the Edit
key and set to YES if a water meter is
connected to the unit.
8. Use Outside Temperature Probe:
Press the Edit key and set to YES if an
outside temperature sensor is con-
nected to the unit.
9. Use Static Pressure Sensor: Press
the Edit key and set to YES if a static
pressure sensor is connected to the
unit.
10. Temperature Units: Press the Edit
key and choose between Fahrenheit
and Celsius degrees for displaying
temperature values. This parameter is
commun to both rooms.
11. Water Meter Units: Press the Edit
key and choose between gallons and
litres for displaying water consumption.
This parameter is commun to both
rooms.
12. Water Meter Calibration: Press the
Edit key and adjust the number of
gallons or liters per water meter pulse.
Set 2 Probes
1234
Use water
meter? NO
Use Out T°
sensor? NO
Use Static P
sensor? NO
Temperature
units: °F
Water meter
units: gal
Water meter
unit/pulse 1
Set 1 Probes
1234

16 Expert-32T rev.03
Expert-32T
13. Number of Heaters and Fan
Stages: Press the Edit key to adjust the
number of heaters used. Press the Edit
key once again to adjust the number of
fan stages.
14. Number of Cooling and Clock
Outputs: Press the Edit key to adjust
the number of cooling outputs used.
Press the Edit key once again to adjust
the number of clock outputs used.
15. Number of Inlet Outputs / Tunnel
Ventilation: Press the Edit key to adjust
the number of inlets used. Press the
Edit key once again to enable or disable
tunnel ventilation. Note that the inlet
cannot be modified if the control uses
the static pressure sensor.
16. Vent Doors: Press the Edit key to
enable or disable vent doors. Note that
the vent doors can be modified only if
the control uses the static pressure
sensor.
17. LED Display Mode: Press the Edit
key to change the display mode on the
LED display on the top right of the
control panel. You can choose between
the temperature (T), the static pressure
(SP) or an alternating display of both
the temperature and the static pressure
(T/SP).
18. Room 1 / Room 2 Mode: Press the
Edit key and set to yes to activate the
two rooms. If they already have been
set, room 2 parameters are kept in
memory if the two room mode is deactivated.
#Heaters: 4
#Fan stages: 10
#Cooling: 2
#Clocks: 0
#Inlets: 0
Use tunnel? NO
Use vent door?
NO
Displa :
T onl
Use Room 1/
Room 2? NO

17
Expert-32T rev.03
Expert-32T
19. Day/Night Set Points: Press the
Edit key to enable or disable separate
day and night set points.
20. Clean Mode in room 1: Press the
Edit key and set to yes to activate
clean mode in room 1.
21. Clean Mode in room 2: Press the
Edit key and set to yes to activate
clean mode in room 2.
22. Change Password: The user can define a password to restrict
access to the functions contained in the SETUP section (USER, OUTPUTS
and TEST). The password must be entered each time one of these
functions is selected. When the correct password is entered, it does not
need to be re-entered until the display times out (i.e. after 15 minutes of
inactivity). The password is a sequence of three numbers from 0 to 99.
By default, the password is set to 0 0 0.
The new password must be
entered, one number at a time.
Use the arrow keys to enter the
first number. Press the Edit key to
step to the next number. Use the
arrow keys to enter the second
number, etc.
21. Program Version Number : The
program version number of the con-
troller is displayed.
Clean Mode in
Room1? NO
Clean Mode in
Room2? NO
Use Night
settings? NO
Expert 32T
X.X
New password?
0 ** **

18 Expert-32T rev.03
Expert-32T
Rela s 1-8
12345678
Rela s 9-16
90123456
Rela s 17-24
78901234
RELAY ASSIGNMENTS
The user can now configure each output separately by selecting the
output using the output select buttons and adjusting the parameters
displayed. Configuration parameters vary according to the type of
output.
Use the up- and down-arrow keys to step through all the display screens
for a given output. The last display screen for all outputs is the relay
assignment.
Relay Assignments: The Expert-32T
can control up to 32 output relays.
The relay panel contains 32 relay
outputs. The mapping between the
stages and the relays must be deter-
mined by the user. The relays are
displayed in groups of 8 relays at a
time. The relays assigned to an output
correspond to the flashing numbers on
the display. Press the Edit key to
display each relay state and use the
arrow keys to assign (ON) or deassign
(OFF) the relay. Use the down-arrow
key to step to the next bank of relays
(see example on following pages). Use
the template at the end of this manual
to map the relays before assigning
them from the front panel.
Rela s 25-32
56789012

19
Expert-32T rev.03
Expert-32T
Relay Assignment Example: Relays 1-16
Relay 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Heater 1 ON
Heater 2 ON
Heater 3 ON
Heater 4 ON
Fan 1 ON ON
Fan 2 ON ON
Fan 3 ON ON ON ON
Fan 4 ON ON ON ON ON ON
Fan 5 ON
Fan 6 ON ON
Fan 7 ON ON
Fan 8 ON ON
Fan 9 ON ON
Fan 10 ON ON
Cool 1
Cool 2
Vent
Doors
Open
Vent
Doors
Close
Tunnel
Open
Tunnel
Close
Clock 1
Clock 2

20 Expert-32T rev.03
Expert-32T
Relay Assignment Example: Relays 17-32
Relay 1718 19 20212223242526272829303132
Heater 1
Heater 2
Heater 3
Heater 4
Fan 1
Fan 2
Fan 3
Fan 4
Fan 5
Fan 6
Fan 7 ON
Fan 8 ON ON
Fan 9 TIMER
Fan 10 TIMER
Cool 1 ON
Cool 2 ON
Vent
Doors
Open ON
Vent
Doors
Close ON
Tunnel
Open ON
Tunnel
Close ON
Clock 1 ON ON
Clock 2 ON ON
Table of contents
Other Cumberland Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Viessmann
Viessmann VITOTROL 100 operating instructions

Bresser
Bresser 7009998 instruction manual

RKC INSTRUMENT
RKC INSTRUMENT Z-TIO Host Communication Quick instruction manual

Rinnai
Rinnai BC 70 2A Installation and user manual

Johnson Controls
Johnson Controls PENN A70 Series Installation Sheets Manual

IVT
IVT PRINETO manual