Daiichi Electronics FINE Series User manual

FSDLC-220-047
INSTRUCTION MANUAL
PLUG-IN TRANSDUCER
FINE SERIES
ALARM SETTER
FSDLC

FSDLC-220-047
1
Thank you for purchasing DAIICHI ELECTRONICS product.
Please read this instruction manual carefully before using.
Safety precautions
Environment conditions
Please be sure to use this product in a place that meets the following conditions. In places that do not meet
this condition, malfunctions and failures, and performance and product life may be reduced.
Within the range of ambient temperature -10 to +55 ℃, humidity 5 to 90% RH.
Place free of dust, corrosive gas, salt and oily smoke. (Corrosive gas:SO2
/
H2S, etc.)
Location that is not affected by vibration and shock.
Location that is not affected by external noise.
Altitude 1000m or less.
Outdoor use conditions
These products are not a dustproof, waterproof, and splash proof construction.
Please avoid the place with much dust. Moreover, please install in the place not exposed to rain or
water drop.
Please do not install in the place where sunlight hits directly.
Discoloration and degradation of a name plate, and deformation of the case by the surface temperature
rise may occur.
Mounting and wiring
Please refer to this instruction manual for mounting and the wiring.
Please refer to connection diagram for the wiring.
Please avoid hot line work.
Please use an electrical wire size suitable with the rated current.
Please check the tightening of the screw.
Preparation
This product must be set before use. Please set correctly after reading this instruction manual.
Maintenance and inspection
Inspection in energized state is dangerous.
This product does not include parts to be replaced at periodic inspection.
In case you need to check an input and control power supply by the hot line condition, please be warned
not to touch output wiring and a human body to other terminals.
Please make sure that the power LED (POWER) is lit properly.
Please regularly to see if wiring and mounting screws and fixing screws are not loose.
Please wipe off lightly with the dry soft cloth. Please do not use the organic solvent, chemicals, cleaners,
etc., such as an alcohol, for cleaning.
Storage
Please store in a place that meets the following conditions.
The ambient temperature within -25 to +70 ℃ (storage temperature).
Daily average temperature 40 ℃ or less.
Location corresponding to the usage environment and use conditions.
Location that is not affected by vibration and shock.
Aluminum electrolytic capacitors are used in products. Please energize the power supply within one year
after purchase.
Countermeasures against troubles
If trouble occurs within the warranty period, DAIICHI ELECTRONICS will repairs this product.
Disposal
Please dispose this product as industrial waste (non-combustible).
Mercury parts and a nickel-cadmium battery are not used for this product.
Warranty period
The warranty period of the product is one year after the date of delivery.

FSDLC-220-047
2
Contents
1. Outline on the product ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 3
1.1 Features of product ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 3
2. Installation
2.1 Outline dimensions ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 3
2.2 Connections ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 5
2.3 About of auxiliary supply ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 6
2.4 Cautions on installation ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 6
2.5 LCD viewing angle ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 6
3. Operation method
3.1 The name and function of each part ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 7
3.2 Each display mode and operation ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 7
3.3 Measurement mode ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 8
3.4 Display mode ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 9
3.5 Setting mode ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 10
3.6 Calibration ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 12
4. Block-diagram and principle of operation
4.1 Block-diagram ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 12
4.2 Principle of operation ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 12
5. Specification and performance
5.1 Alarm output specifications ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 13
5.2 Operation of alarm output ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 13
5.3 Relay action ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 15
5.4 Pre-alarm function ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 16
5.5 Setting value ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 17
5.6 Performance ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 18
6. Trouble shooting ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 19
7. Composition of type and specification code ・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 20

FSDLC-220-047
3
1. Outline on the product
This product is a small plug-in structure alarm setter.
This product takes a DC voltage or DC current signal as input, compares it with the preset operating point,
and outputs the excess or deficiency as a contact signal.
The full scale of the input can be arbitrarily set on the actual scale according to the process amount, and
each set value (operating value, contact delay, etc.) can also be set freely.
This product is used in combination with a mounting base (FWBA-□, hardware model B).
1.1 Features of product
The setting accuracy is ±0.1% (% of input span).
The display accuracy is ±0.1% ±1 digit (% of input span).
(±0.2% for voltage input less than 1V)
Various settings can be changed with the front switch.
The measured value (real scale) and various set values can be confirmed on the LCD.
The backlight lights when a key is pressed.
The backlight lights off 30 seconds after the key operation is completed.
The set value is guaranteed by the non-volatile memory E2PROM even during a power failure.
The pre-alarm function displays the progress of the contact delay time by blinking the monitor lamp.
(Pre-alarm ON/OFF can be selected by setting)
2. Installation
2.1 Outline dimensions (Unit mm)
(1) FSDLC
72
For 2 contacts For 3 contacts For 4 contacts
48
Fixing screw
11
Name plate
85

FSDLC-220-047
4
(2) Precision Resistance Unit, Type:UR-2 (option)
5.5 φ3.7 0.5 9.5
21.5
31.3
28.5
11.2
AWG22 (60mm)
Resistance in input signal
Input
Resistance
DC0‐1mA DC0‐10mA DC0‐16mA DC0‐20mA DC2‐10mA DC4‐20mA DC10‐50mA
10Ω - DC0‐100mV DC0‐160mV DC0‐200mV DC20‐100mV DC40‐200mV DC100‐500mV
50Ω - - - DC0‐1V DC100‐500mV DC0.2‐1V DC0.5‐2.5V
62.5Ω - - DC0‐1V - - DC0.25‐1.25V -
100Ω DC0‐100mV DC0‐1V - - - DC0.4‐ 2V DC1‐5V
250Ω - - - DC0‐5V - DC1‐5V -
500Ω - DC0‐5V - DC0‐10V DC1‐5V - -
1kΩ DC0‐1V DC0‐10V - - - - -
<How to mount UR-2>
When using UR-2 (resistor module), install it as shown in the figure below.
(3) Mounting base
12
34
12
34
UR-2
INPUT
(
Voltage input
)
Electrical wire
Attach as nameplate surface is
upward.
Attach as the main body case is
downward.
Mounting base
UR-2 combines an alarm setter of voltage input, and please
use it. When open measures are necessary when they change
an alarm setter with hot line condition in current input,
they connect UR-2 to socket, and please use it by voltage
signal.
(UR-2, Specify resistance value)
Socket:Two units of space are required to mount this product.
Input terminal:Wire the input line of the alarm setter.
Auxiliary supply terminal:Wiring for the power supply unit that supplies
Output terminal:Output terminal of alarm setter.
DATE TP-****
FWBA-16PY-A00TYPE
the alarm setter and each plug-in transducer.
(Refer to the connection diagram for details)

FSDLC-220-047
5
Output
contact
contact
Output R
Diode
load
Inductive
External power supply
R
Surge killer
~
C
R
load
Inductive
ALARM OUTPUT
COM2
UNITn+1
COM2
ALARM OUTPUT
UNITn+1
AL1
COM1
5
AL2
7
6
INPUT
UNITn
1
+
2
-
AL4
AL3
567
AL1
6
COM1
5
AL2
7
INPUT
UNITn
1
+
2
-
AL4
7
AL3
56
2.2 Connections
■ Connection diagram
2 contacts
Each change over contact (1c)
3 contacts
Each normally open contact (1a)
3 contacts
Each normally close contact (1b)
4 contacts
Each normally open contact (1a)
4 contacts
Each normally close contact (1b)
<Caution>
Please shut off the auxiliary power supply and input before starting work.
Touching terminals etc. while wet hands may cause electric shock.
Because burnout accident may be caused by wiring differences, please be careful of wiring.
Also, it is dangerous to inspect it in places with inflammables and flammable chemicals and gases.
When inductive loads (electromagnetic relay, etc.) are connected to output contact, it recommends
attaching diode or surge killer etc. near the load.
《Spark elimination circuit example》
Connect 1(+) and 2(-) of the left
unit to INPUT of this product.
* When mounting this product on a
multiple base (FWBA-08□ or
FWBA-16□), the space for 2 units
is used.
ALARM OUTPUT
AL3
5
UNITn+1
COM2
ALARM OUTPUT
a1
AL1
COM1 b1 b2
AL2
a2 AL1 AL2
UNITn+1
+-
5
1
6 7
2
INPUT
UNITn
756
-+
5 6
1
7 8
2
INPUT
UNITn
ALARM OUTPUT
AL3AL1 AL2
5
UNITn+1
6
-+
5 6
1
7 8
2
INPUT
UNITn
6

FSDLC-220-047
6
Front view
Fixing screw
(LED lights on)
POWER LED
Front view
Fixing screw
(LED lights off)
POWER LED
2.3 About of auxiliary supply
By applying auxiliary power to the power supply (AUX. SUPPLY) terminal of mounting base, power is supplied
to each unit.
When mounting base has unit individual power switch.
Please insert this product into the mounting base and tighten the screw to fix the main body.
An auxiliary power is supplied. Also, when removing, by loosening the screw, supply of auxiliary power
supply is cut off. (When the auxiliary power is supplied, the power LED of this product lights on, and it
lights off when it is shut off.)
Without individual unit power supply switch.
Regardless of the tightening of the fixing screw on the main unit, auxiliary power is supplied.
2.4 Cautions on installation
● Wiring state
Please separate wiring of input and output and perform consideration to noise. And, please separate
from a line with the power line used as the source of a noise and steep voltage, and current as much
as possible. Please use shielding wire for the bottom of the remarkable environment of a noise.
● Environmental condition
(1) Ambient temperature and humidity range
The ambient temperature and humidity during the operation of each equipment should be in the
following range.
Temperature: -10 to 55 ℃, humidity: 5 to 90% RH (Non condensing)
(2) Ambient atmosphere
Please be careful when using in dusty environments.
Also, please consult us when using under corrosive gas [hydrogen sulfide (H2S), chlorine (Cl), etc.]
environment.
2.5 LCD viewing angle
Mount the LCD to obtain an optimum angle,
since the contrast changes according to
the monitoring angle.
If the unit has an individual power switch, auxiliary power will not be supplied to this product
unless the fixing screws are securely tightened. Be sure to tighten the fixing screw.
Tighten the fixing screw to supply auxiliary
power supply. (Power LED lights on)
Loosening the fixing screw will shut off the
auxiliary power supply. (Power LED lights off)
Front
30゜
15゜
Top
Back
Under
Front
Back
FSDLC
Mounting base
45゜ 45゜
Side view Top view

FSDLC-220-047
7
For 4 contacts
lights LED. LED disappears
Supply of an auxiliary power
Auxiliary supply (POWER) LED
by auxiliary power cut off.
For 2 contacts For 3 contacts
Movement of a setting item, and change of settings.
The LED (AL1 to AL4) is lighted at the time of
If it is set as those with a pre-alarm (No.28
PREAL:ON), LED blinks from value detection of
operation to the end of delay time.
Settings check. Update data.
Move the digit of settings.
Monitor LED
relay excitation.
Change the mode to display.
Fixing screw
Display of measured value (real scale) and various settings.
The backlight lighted when the key switch is operated.
Backlight will be off, if 30 second passes without doing
key switch operation.
Key switch
LCD
3. Operation method
3.1 The name and function of each part
Note(1) Please operate at a moderate force without applying excessive force to the key switch.
If you press the key switch in excessive force, there is a possibility that affect the display
becomes a stress on the front plate.
3.2 Each display mode and operation
Shift in each mode
A display mode shifts to each mode by those with four type, and the following switch operations.
① Measurement mode
Input value, maximum value, and minimum value are displayed.
② Display mode
Setting item is displayed in order and the check of set value can be performed.
Change of set value cannot be performed.
③ Setting mode
Setting item is displayed in order and change of set value can be performed.
Please perform the check of set value with a display mode.
④ Setting error display
After setting change in setting value change mode, an error code is displayed when combination error
occurs.
№ Contents of error Measures
ERROR 0 Scaling combination error Set again so that MAX>MIN.
ERROR 1 COMP1 setting range outside error
Set again so that the measurement display range
is -25 to +125%.
ERROR 2 COMP2 setting range outside error
ERROR 3 COMP3 setting range outside error
ERROR 4 COMP4 setting range outside error
(1)
Power supply
① Measurement mode ② Display mode
(Settings display)
③ Setting mode (Setting change)
If key switch operation is not performed for
30 seconds in a display mode, it shifts to
measurement mode.
UP
MODE
Pushes for 3 seconds simultaneously.
④ Setting error
display
ERROR
Y
UP
MODE
Pushes for 3 seconds
simultaneously.
ENT Key
Push
N
UP
MODE
Pushes for 3 seconds
simultaneously.
Push key
Push key
MODE
MODE

FSDLC-220-047
8
3.3 Measurement mode
After turning on the power supply, measurement mode is entered. The display switches each time the UP key
is pressed, and you can check each display (measurement value display, maximum value display, minimum value
display).
UP
UP
UP
UP
ENT
ENT
UP
Measurement value display
Reset by push 3
seconds of ENT key
Reset by push 3
seconds of ENT key
Reset of minimum
value display
Measurement value
Unit
50.0
%
Maximum value display
+PEAK
100.0
Reset of maximum
value display
-PEAK
50.0
Minimum value display
-PEAK
20.0
+PEA
K
50.0
● Explanation of a key switch
Mode (Measurement display) change
Reset of maximum value and minimum value.
Display change
Not use
< Notes of maximum value and minimum value >
After set value change, please reset a maximum value
display and a minimum value display.

FSDLC-220-047
9
3.4 Display mode
Setting item is displayed in order and the set value check of all items can be performed.
Once it pushes the MODE key, it will change to a display mode.
Common item (AL1 to AL4) is changed by the UP key. Each setting item is displayed as the SHIFT key.
5 0 . 0
%
UP UP
UP UP UP
UP
UP
SHIFT SHIFT SHIFT SHIFT SHIFT
COMP1
080.0
SHIFT SHIFT SHIFT SHIFT SHIFT
UP UP
UP UP UP
UP UP
UP UP UP
SHIFT SHIFT SHIFT SHIFT SHIFT
SHIFT SHIFT SHIFT SHIFT SHIFT
SHIFT SHIFT SHIFT SHIFT SHIFT
UP UP UP UP UP
UP UP
UP UP UP
UP
SHIFT
Measurement value display
UNIT
%
MIN
000.0
MAX
100.0
CBIAS
00.00
CSPAN
00.00
S.D.
000s
AVE
1
MODE
SHIFT
C.D.1
000s
ALMD1
High
D.B.1
03.0%
EXMD1
ON
ALMD2
High
COMP2
070.0
D.B.2
03.0%
EXMD2
ON
C.D.2
000s
ALMD3
Low
COMP3
030.0
D.B.3
03.0%
EXMD3
ON
C.D.3
000s
ALMD4
Low
COMP4
020.0
D.B.4
03.0%
EXMD4
ON
C.D.4
000s
AL1
setting
item
AL2
setting
item
AL3
setting
item
AL4
setting
item
PREAL
OFF
SHIFT
Common
setting
item
2 contact
specification
4 contact
specification
3 contact
specification
● Explanation of key switch
Mode (Measurement display) change.
Not use.
Common item (AL1 to AL4) is changed.
Each setting item is changed.

FSDLC-220-047
10
3.5 Setting mode
Change of each set value is possible. If the MODE+UP key is pushed 3 seconds or more simultaneously,
it will change to setting mode.
By the same operation as a display mode, a setting item is shifted and it displays.
The ENT key is pushed by the item to make a setting change, and setting is changed.
● Operation in setting mode
In setting mode, a setting item or set value is blinking.
In setting mode, the back light is always turn on a light.
After a setting mode is ended, it restarts.
● Explanation of key switch
Not used alone.
MODE+UP key is pushed 3 seconds or more simultaneously. Mode (Measurement setting) change.
Set value decision(Update of data)
Determination of setting item(Blinking is upper section lower section)
Setting item movement and change of set value.
MODE+UP key is pushed 3 seconds or more simultaneously. Mode (Measurement setting) change.
Movement of the setting item of AL1 to AL4, and the shift of set value.
Measurement value display
Blinking
Pushed for 3 seconds simultaneously.
50.0
%
UP
MODE
C.D.1
000s
UNIT
%
MIN
000.0
MAX
100.0
CBIAS
00.00
CSPAN
00.00
S.D.
000s
AVE
1
ALMD1
High
COMP1
080.0
D.B.1
03.0
EXMD1
ON
ALMD2
High
COMP2
070.0
D.B.2
03.0
EXMD2
ON
C.D.2
000s
ALMD3
Low
COMP3
030.0
D.B.3
03.0
EXMD3
ON
C.D.3
000s
ALMD4
Low
COMP4
020.0
D.B.4
03.0
EXMD4
ON
C.D.4
000s
UP UP
UP UP UP
UP UP
SHIFT SHIFT SHIFT SHIFT SHIFT SHIFT SHIFT
SHIFT SHIFT SHIFT SHIFT SHIFT
UP UP
UP UP UP
UP UP
UP UP UP
SHIFT SHIFT SHIFT SHIFT SHIFT
SHIFT SHIFT SHIFT SHIFT SHIFT
SHIFT SHIFT SHIFT SHIFT SHIFT
UP UP
UP UP UP
UP UP UP UP UP
2 contact
specification
3 contact
specification
4 contact specification
PREAL
OFF
UP
SHIFT
Move to the setting item you want to change by
the same operation method as display mode.

FSDLC-220-047
11
SHIFT
UP
UP
UP
UP
UP
UP
● Unit display (UNIT) setting.
● Minimum value scaling (MIN) setting.
Note(2) After set value changed, displays the change set value.
Note(3) The number of the top digit becomes "-"(minus) after 0 to 9.
Note(4) The number of digits other than the top digit becomes " ."(decimal point) after 0 to 9.
However, if decimal point is in other digits, decimal point does not display.
(2)
UNIT
%
(Middle omission)
UNIT
%
UNIT
m
UNIT
m
UNIT
kW
UNIT
kW
ENT
ENT
ENT
UP
UP
UP
After deciding set value change, a setting
item symbol is blinking.
(UNIT is blinking.)
UNIT
UP
UP With no unit
UNIT
%
ENT
(2)
(Middle omission)
MIN
000.0
MIN
100.0
MIN
010.0
MIN
-00.0
MIN
090.0
MIN
000.0
MIN
000.0
(Middle
omission)
MIN
010.0
(Middle omission)
(3) (4)
MIN
000.0
ENT
SHIFT
ENT
After deciding set value change, a setting item
symbol is blinking.
(Here, MIN is blinking.)

FSDLC-220-047
12
3.6 Calibration
Because this product is adjusted beforehand, there is no necessity for calibration.
However, if the operating point of an alarm output shifts, please adjust in the next way.
(1) After turning on the auxiliary power, perform preliminary energization for 15 minutes.
(2) When the input equivalent to the minimum display is applied, in order that it may become the minimum
display, set value CBIAS is set up.
Next, when the input equivalent to the maximum display is applied, in order that it may become the
maximum display, it sets up by set value CSPAN.
Calibration is finishing, if the above is checked again and the display is correct.
In addition, please refer to the 4.5 section "setting mode" about setting of set value CBIAS and CSPAN.
(3) Please perform the check of an operation value, a reset value, and a dead band.
4. Block-diagram and principle of operation
4.1 Block-diagram
4.2 Principle of operation
(1) The inputted voltage or current passes along a filter protection circuit, and becomes the DC voltage
below constant voltage. This voltage goes into an amplifier.
(2) The input is converted into the suitable voltage range in an amplifier.
This voltage constitutes an input of an A/D converter.
(3) The data converted into digital one by the A/D converter are sent to CPU.
A/D converter has 16-bit resolution and performs operation and conversion with 1MHz clock.
Based on the scaling range that had this data set up, it calculates within CPU.
And the measurement value scaling by the LCD is displayed.
(4) The operation value and measurement value, which was set up beforehand, are compared, and the relay
and LED are operated.
(5) The front key switch makes each setting change.
(6) The value set up by the switch is saved at non-volatile memory (E2PROM).
ROM has the capacity of 128×16 bits.
(
)
(+)
INPUT
(-)
Filter
protection
circuit
Key switch
AUX.
SUPPLY
1
2
Amplifier A/D
converter
Non-volatile
memory
E
2
PROM
CPU
(
)
Power supply
circuit
LCD
driver
100.0
%
AL1 AL2 AL3 AL4
LCD display
LED display
Relay output circuit
RY
RY
RY
RY
6
7
5
AL1
AL2
COM
6
7
5
AL3
AL4
COM
* In case of 4 contact output
[Normally open contact
ENT
UP
SHIFT
UNIT n
UNIT n+1
+
-
~
~
From mounting
base
MODE

FSDLC-220-047
13
5. Specification and performance
5.1 Alarm output specifications
Item Specification
Output 2 contacts,3 contacts,4 contacts
Contact structure
2 contacts:Each change over contact (1c contact)
3 contacts:Each normally open contact (1a contact) or
each normally close contact (1b contact)
4 contacts:Each normally open contact (1a contact) [One side two points common] or
each normally close contact (1b contact) [One side two points common]
Contact capacity Maximum switching load AC120V 1A (COSφ=1) ,DC30V 1A (Resistance load)
Minimum switching load DC5V 10mA
Electrical life 500,000 times or more (Switching frequency 30 times/min)
Output mode
Setting in five kinds of modes as follows is possible for operation of detection.
① High limit detection (H), Detection operation, Relay excitation
② High limit detection (H), Detection operation, Relay non-excitation
③ Low limit detection (L) , Detection operation, Relay excitation
④ Low limit detection (L) , Detection operation, Relay non-excitation
⑤ OFF , Relay non-excitation always
Relay excitation
status display
MAX. 4 contacts. Monitor lamp lights when each relay is excited.
The monitor lamp blinks during the delay time when the pre-alarm setting is ON.
Relay and monitor
lamp operation
Auxiliary supply OFF, or
relay non-excitation. Relay normally close contact (b contact) ON, Monitor lamp OFF
Relay excitation Relay normally open contact (a contact) ON, Monitor lamp ON
Output mode Refer to the alarm output operation in section 5.2.
Relay contact status Refer to the alarm output operation in section 5.2.
5.2 Operation of alarm output
① At the auxiliary supply OFF, or at the relay non-excitation
:Relay normally close contact (b contact) ON, Monitor lamp OFF.
② At the relay excitation:Relay normally open contact (a contact) ON, Monitor lamp ON.
Output mode Relay and monitor lamp operating state
▽ Operation value setting. Input limit →
Excitation
H
Monitor lamp ●:Monitor lamp ON
Relay ○:Monitor lamp OFF
L
Monitor lamp
Relay
Non-excitation
H
Monitor lamp
Relay
L
Monitor lamp
Relay
OFF (Excitation・
Non-excitation)
Monitor lamp
Relay
Non-excitation Excitation
OFF ON
Non-excitation
Excitation
OFF
ON
Non-excitation
Excitation
OFF
ON
Non-excitation Non-excitation
OFF OFF
Non-excitation Excitation
OFF ON

FSDLC-220-047
14
● Relay contact status
Status 4 contacts
Each normally open contact (1a contact)
4 contacts
Each normally close contact (1b contact)
Auxiliary supply
OFF or relay
non-excitation
Relay excitation
Status 3 contacts
Each normally open contact (1a contact)
3 contacts
Each normally close contact (1b contact)
Auxiliary supply
OFF or relay
non-excitation
Relay excitation
Status 2 contacts
Each change over contact (1c contact)
Auxiliary supply
OFF or relay
non-excitation
Relay excitation
Terminal №
AL2 AL1 C1
6 5 7
AL4 AL3 C2
6 5 7
UNIT n UNIT n+1
Terminal №
AL2 AL1 C1
6 5 7
AL4 AL3 C2
6 5 7
UNIT n UNIT n+1
Terminal №
AL2 AL1 C1
6 5 7
AL4 AL3 C2
6 5 7
UNIT n UNIT n+1
Terminal №
AL2 AL1 C1
6 5 7
AL4 AL3 C2
6 5 7
UNIT n UNIT n+1
Terminal № 6 5 7
AL1 C1 AL3 C3 C2
5 8 6
UNIT n UNIT n+1
AL2
Terminal № 6 5 7
AL1 C1 AL3 C3 C2
5 8 6
UNIT n
AL2
UNIT n+1
Terminal № 6 5 7
AL1 C1 AL3 C3 C2
5 8 6
UNIT n UNIT n+1
AL2
Terminal № 6 5 7
AL1 C1 AL3 C3 C2
5 8 6
UNIT n
AL2
UNIT n+1
Terminal № 6 5 7 6 5 7
UNIT n UNIT n+1
AL1
c1 a1 b1
AL2
c2 a2 b2
Terminal № 6 5 7 6 5 7
UNIT n UNIT n+1
AL1
c1 a1 b1
AL2
c2 a2 b2

FSDLC-220-047
15
5.3 Relay action
■ Contact delay function
Relay operation in over-input detection. (Output mode:Excitation, H (5))
Relay operation in shortage-input detection. (Output mode:Excitation, L (5))
Note(5) In case of non-excitation for relay excitation operation setting, action of relay becomes reverse.
■ Starting delay function
After an auxiliary supply apply, detection action is performed after a starting delay time.
Operation value
setting
Relay action ON
OFF
Setting value
Input
Contact delay
setting time
Contact delay
setting time
Contact delay
setting time
Dead band
Operation value
setting
Relay action ON
OFF
Input
Contact delay
setting time
Contact delay
setting time
Contact delay
setting time
Dead band
Setting value
Auxiliary supply
Detect action
Closing
Starting delay setting time

FSDLC-220-047
16
5.4 Pre-alarm function
A monitor lamp is blinked among contact delay time until excitation of a relay after operation value
detection. Blinking of a monitor lamp will be gradually fast, and when the point of contact delay time
passes, a monitor lamp is lights up.
If contact delay time setting is made into 0 second, a pre-alarm function constitutes OFF.
・Relay action and pre-alarm in over-input detection.
(Output mode setting:Excitation H, Pre-alarm setting:ON)
・Action of the pre-alarm in contact delay time (blinking)
Operation value
setting
Relay
action
ON
OFF
Dead band
Setting value
Input
Monitor
lamp
ON
OFF
Blinking
Lights up
Blinking
Contact delay
setting time
Contact delay
setting time
Contact delay
setting time
Lights up
180s
3s
Blinking cycle
6s
Blinking cycle
4s
Blinking cycle
2s Blinking becomes
gradually fast.
3s
120s
3s
3s
2s
2s
1
1s
2s
2s
60s 10s 0s

FSDLC-220-047
17
5.5 Setting value
№ Contents Mark
Default setting value
Setting range
2 contact
outputs
3 contact
outputs
4 contact
outputs
1 Unit display UNIT %
%
,m ,℃ ,m 3/h,ppm,pH,TPm,×10kg,
Ω,kW,No unit
2 Minimum value scaling MIN 0.0 -9999 to 9999 -9.99 to 99.99
-99.9 to 999.9 0.000 to 9.999
3 Maximum value scaling MAX 100.0
4
AL1
Output mode ALMD1 High High High High:H operation,Low:L operation,
OFF :With no operation
5 Operation value COMP1 70.0 80.0 80.0 Measurement display range -25 to
+125% (Real scale)
6 Dead band D.B.1 3.0 0.5 to 50.0%
7 Excitation mode EXMD1 0N ON:Excitation,OFF:Non-excitation
8 Contact delay time (CD) C.D.1 0 0 to 180s
9
AL2
Output mode ALMD2 Low High High High:H operation,Low:L operation,
OFF :With no operation
10 Operation value COMP2 30.0 70.0 70.0 Measurement display range -25 to
+125% (Real scale)
11 Dead band D.B.2 3.0 0.5 to 50.0%
12 Excitation mode EXMD2 0N ON:Excitation,OFF:Non-excitation
13 Contact delay time (CD) C.D.2 0 0 to 180s
14
AL3
Output mode ALMD3 - Low Low High:H operation,Low:L operation,
OFF :With no operation
15 Operation value COMP3 - 30.0 30.0 Measurement display range -25 to
+125% (Real scale)
16 Dead band D.B.3 - 3.0 0.5 to 50.0%
17 Excitation mode EXMD3 - ON ON:Excitation,OFF:Non-excitation
18 Contact delay time (CD) C.D.3 - 0 0 to 180s
19
AL4
Output mode ALMD4 - Low High:H operation,Low:L operation,
OFF :With no operation
20 Operation value COMP4 - 20.0 Measurement display range -25 to
+125% (Real scale)
21 Dead band D.B.4 - 3.0 0.5 to 50.0%
22 Excitation mode EXMD4 - ON ON:Excitation,OFF:Non-excitation
23 Contact delay time (CD) C.D.4 - 0 0 to 180s
24 Starting delay time (SD) S.D. 5 1 to 180s
25 Bias point calibration CBIAS 0.00 -9.99 to 9.99% (% of input span)
26 Span point calibration CSPAN 0.00 -9.99 to 9.99% (% of input span)
27 Average number AVE 1 1,4,8,16,32
28 Pre-alarm PREAL OFF ON:Pre-alarm ON, OFF:Pre-alarm OFF
< Notes of setting >
・The decimal point position change of scaling is made by the minimum value scaling.
If the decimal point position is changed, the decimal point position of maximum value scaling and operation
values 1 to 4 will also change. If the decimal point position is changed, please be sure to check the set
value of a maximum value scaling and an operation value.
・When changing the scaling, set the operation values 1 to 4 within the measurement display range (see below).
Even if the output mode is set to OFF, keep it within the measurement display range.
・An operation value can be set up in -25 to +125% of the measurement display range (minimum value scaling
to maximum value scaling).
(Example) Input 4 to 20mA,
Operation value -25.0,
Output mode is "Low" setting.
Becomes the L detected at the input 0mA,
can also be used as a disconnection
detection.
・After setting change, in case a set value combination error occurs, it becomes a setting error display.
Please push the key and set up the right set value (in set value change mode).
125%
100%
50%
0%
-25%
24mA
20mA
12mA
4mA
0mA

FSDLC-220-047
18
5.6 Performance
Item Specification
Setting accuracy (6) ±0.1% (% of input span)
Display accuracy (7)(8) ±0.1% (% of input span) ±1digit
Reproducibility of the
operating point (6) ±0.1% (% of input span)
Operating time ±0.25 seconds of set value (Setting value 0 seconds = 0.5 ± 0.25 seconds)
Set value is contact delay time (9)
Reset time 0.5 seconds or less (9)
Starting delay time ±0.25 seconds of set value
Influence of temperature 0.2% (For input span) / 23±10℃
Influence of auxiliary
supply voltage variation 0.1% (For input span) / Within variation range
Operation period About 0.1 second
Response time About 0.5 second (9)
When a step change of 90% to 110% of the operating value setting is given (at CD = 0 seconds)
Overload
capacity
Voltage input 2 times 10 seconds and 1.5 times continuation of rated voltage.
Current input 10 times 5 seconds and 1.5 times continuation of rated current.
Aux. supply 1.5 times 10 seconds of rated voltage. Variable range upper limit continuous.
Insulation resistance
Between electric circuit and case.
Above 50MΩ at DC500V
Between input, output terminals and auxiliary supply
terminals.
Between input terminals and output terminals.
Between
output
terminals
2 contacts Between AL1 and AL2
3 contacts Between AL1 and AL2 and AL3
4 contacts Between AL1・AL2 and AL3・AL4 (10)
Power frequency
withstand voltage
Between electric circuit and case.
AC2000V (50/60Hz) 1 minute.
There must not be malfunction.
Between input, output terminals and auxiliary supply
terminals.
Between input terminals and output terminals.
Between
output
terminals
2 contacts Between AL1 and AL2
3 contacts Between AL1 and AL2 AC1000V (50/60Hz) 1 minute.
There must not be malfunction.
Between AL1・AL2 and AL3 AC2000V (50/60Hz) 1 minute.
There must not be malfunction.
4 contacts Between AL1・AL2 and AL3・AL4 (10)
Impulse withstand
voltage Between electric circuit and case. 5kV 1.2/50
μ
s. Both positive and negative polarity
for 3 times each. There must not be malfunction.
Vibration Vibration of vibration frequency 16.7Hz,Double amplitude 1mm.
In the direction of X Y Z for each 10 minutes. There must not be malfunction.
Shock Error:98m/s2, X, Y, Z direction for each 3 times.
Duration:294m/s2, X, Y, Z direction for each 3 times.
Power failure guarantee Each set value is data-saved by non-volatilized memory.
Material of case Case:Flame resisting ABS resin , Name plate:Polyester film
Color Munsell N1.5 (Black)
Operating temperature
and humidity limits -10 to +55℃ , 5 to 90%RH (Non condensing)
Storage temperature limits -25 to +70℃
Mass Approx. 180g
Accessories Unit symbol sheet,Instruction manual
Note(6) Input is DC60mV to less than 1V, DC±60mV to less than ±1V. ±0.2% (% of input span)
Note(7) Input is DC60mV to less than 1V, DC±60mV to less than ±1V. ±0.2% (% of input span) ±1digit.
Note(8) If the scaling span is 10,000 or more (5 digits excluding the decimal point), it is ±0.1% (for input
span) ±2 digits. If the scaling span is 10,000 or more and the input is less than 1V, it is ±0.2% (for
input span) ±2 digits.
Note(9) When the average number is once. If the average number is 4, 8, 16, or 32, the operating time and
reset time will vary depending on the conditions.
Note(10) In case of 4-contact output, there is no insulation between AL1 and AL2 and between AL3 and AL4.
● About transition of a contact
In DC load switching, transition of a contact may start and a contact may not return by uneven connection.
A contact evaporates locally with arc heat, what carried out contact evaporation to + polarity → - polarity
carries out the adhesion deposition of this, and a single-sided convex opposite side serves as a concave.
〈Measure〉Be sure to use each relay within a rated load.

FSDLC-220-047
19
6. Trouble shooting
Abnormal phenomenon Cause of estimated Method of settlement
Not output
Power supply input is not applied Please power supply-input-check and apply.
Alarm setter trouble Repair of alarm setter
Input is not connected Please confirm connection of input.
Abnormal of input Please confirm measurement value.
Error of setting Please confirm set value.
Output is not connected. Please confirm connection of output.
Power-supply voltage is low. Please confirm power-supply voltage.
Display is abnormal
(Large error)
Power-supply voltage is not
regulation range.
Please check power-supply voltage and give as
regulation range.
Input is abnormal. Please give a measurement value as a check and a
normal input.
Error of set value Please confirm set value.
Alarm setter trouble Repair of alarm setter
Display error
(Small error) Secular change of input measurement Display is proofread again.
(Reference of instruction manual 3.6 section)
Set value cannot be
changed.
Error of the setting method Please check setting method.
(Reference of instruction manual 3.5 section.)
Alarm setter trouble Repair of alarm setter
An error is
displayed.
ROM SUM value error
Repair of alarm setter
In case of EEP error, press ENT key to enter
setting mode. Check the setting value.
RAM READ/WRITE error
EEP Saving value error
A/D A/D conversion error
This manual suits for next models
1
Table of contents
Popular Security System manuals by other brands

Sphere
Sphere 400-03520 Installation & operation manual

Dahua
Dahua DHI-ARA12-W2 user manual

KP Electronic Systems
KP Electronic Systems ATC100 installation manual

Motorola
Motorola HMEZ2000 - Homesight Wireless Home Security... quick start guide

DSC
DSC MAXSYS PC4020 installation manual

Blue point
Blue point BP04-101P Installation and maintenance instructions

Aiphone
Aiphone GF-MK Installation & operation manual

Velleman
Velleman CAMSET31 user manual

Soundoff Signal
Soundoff Signal Armada A200 manual

System Sensor
System Sensor SpectrAlert S1224MCW Installation and maintenance instructions

DMP Electronics
DMP Electronics Thinline 7063 user guide

QOLSYS
QOLSYS IQ PANEL 2 quick guide