2 Specifications
Standard Accessories : Clamps;
Standard Accessories : Accessory pipe;
Standard Accessories : Insulation;
Standard Accessories : Installation manual;
Notes
(1) In case of connecting with a 15-50 type indoor unit, use the accessory pipe to match the size of the field pipe. Be sure to braze the connection between the accessory pipe and the
field pipe.
(2) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(3) Maximum allowable voltage range variation between phases is 2%.
(4) MCA/MFA: MCA = 1.25 x FLA
(5) MFA ≤4 x FLA
(6) Next lower standard fuse rating minimum 15A
(7) Select wire size based on the value of MCA
(8) Instead of a fuse, use a circuit breaker
(9) In case of connecting to a 150-160 type indoor unit, use the accessory pipe to match the size of the field pipe. Be sure to braze the connection between the accessory pipe and
the field pipe.
(10) In case of connecting to a 160-200 type indoor unit, use the accessory pipe to match the size of the field pipe. Be sure to braze the connection between the accessory pipe and
the field pipe.
2-1 Technical Specifications BS1Q10A BS1Q16A BS1Q25A
Power input Cooling Nom. kW 0.005
Heating Nom. kW 0.005
Maximum number of connectable indoor units 5 8
Maximum capacity index of connectable indoor units 15 \< x ≤100 100\<x≤160 160\<x≤250
Casing Material Galvanised steel plate
Dimensions Unit HeightxWidthxDe
pth
mm 207x388x326
Weight Unit kg 12 15
Piping connections Outdoor unit Liquid Type Brazing connection
OD mm 9.5
Gas Type Brazing connection
OD mm 15.9 22.2
Dischar
ge gas
Type Brazing connection
OD mm 12.7 19.1
Indoor unit Liquid Type Brazing connection
OD mm 9.5
Gas Type Brazing connection
OD mm 15.9 22.2
Sound absorbing thermal insulation Foamed polyurethane Flame-resistant needle felt
2-2 Electrical Specifications BS1Q10A BS1Q16A BS1Q25A
Power supply Phase 1~
Frequency Hz 50
Voltage V 220-240
Voltage range Min. % -10
Max. % 10
Total circuit Minimum circuit amps (MCA) A 0.1
Maximum fuse amps (MFA) A 15
Notes Instead of a fuse, use a circuit breaker