
20
faulty limit, or a failed circulator blower can cause this
power during a heating cycle may also cause the auxil-
iary limit to open. The automatic reset secondary limit is
located on top of the circulator blower assembly.
passages, blocked or cracked heat exchanger, a failed
rollout protection device is a manual reset limit located
must be determined and corrected before resetting the
limit.
Check wiring for opens/shorts and miswiring.
A pressure switch stuck open can be caused by a faulty
pressure switch, faulty wiring, a disconnected or damaged
a faulty induced draft blower.
If the control senses an open pressure switch during the
pre-purge cycle, the induced draft blower only will be ener-
gized. If the pressure switch opens after ignition has begun
the gas valve is de-energized, the circulator blower heat
A stuck closed pressure switch can be caused by a faulty
pressure switch or faulty wiring. If the control encounters
a pressure switch stuck closed, the induced draft blower
A primary limit will open due to excessive supply air tem-
total external duct static, blower motor, blower motor speed
-
ly reset once the temperature falls below a preset level.
If a limit switch opens, the gas valve is immediately de-en-
ergized, the induced draft and air circulating blowers are
energized. The induced draft and air circulator blowers
remain energized until the limit switch re-closes. The diag-
combustion and air circulator blowers are energized. The
times to indicate this condition. The control can be reset by
removing the power supply to the unit or it will automatically
reset after one hour. Miswiring is the probable cause for this
fault.
Under some conditions, the fuel or air supply can create a
amber diagnostic LED. The unit will continue to operate
The automatic ignition control has a built-in feature that
prevents damage to the compressor in short cycling situ-
ations. In the event of intermittent power losses or inter-
mittent thermostat operation, the ignition control will delay
output to the compressor contactor for three minutes from
the time power is restored or thermostat call for cooling is
compressor contactor output is being delayed.
Some models include a high pressure cutout switch and/
or a loss of charge cutout switch. The high pressure cutout
switch protects the refrigeration system from excessive
operating pressures. The loss of charge cutout switch
protects the refrigeration system from very low operating
pressures due to a loss of refrigerant. Compressor oper-
ation will be disabled if either of these devices opens. If
times to indicate that a refrigeration system pressure switch
is open.