6 Capacity tables
6 - 1 Cooling/Heating Capacity Tables
RZQG125L9V1
RZQG125L8Y1
Cooling Heating
Symbols
AFR: Airflowrate[m³/min]
BF: Bypassfactor
EWB: EnteringwetͲbulbtemperature(°CWB)
EDB: EnteringdryͲbulbtemperature(°CDB)
TC: Maximumtotalcooling/heatingcapacity[kW]
SHC: Sensibleheatcapacity[kW]
CPI: Coefficientofthepowerinput
PI: Powerinput[kW]
compressor+indoorandoutdoorfanmotors
Cooling Heating
Notes
1. Theratingsshownarenetcapacitieswhichincludeadeductionforindoorfanmotorheat.
2. = Maximumatstandardconditions
=Ratedcapacityandratedcoefficientofthepowerinput
Themaximumcapacityisnotguaranteedexceptatstandardconditions.
3. SHCisbasedonindoorunitsEWB&EDB.
SHCforotherdryͲbulbtemperatures=SHC+SHC*
SHC* = SHCcorrectionforotherdryͲbulbtemperatures
= 0.02xAFR(m³/min)x(1ͲBF)x(DB*ͲEDB)
4. Thecapacitiesarebasedonthefollowingconditions:
Outdoorair:85%RH
However,theoutdoorambientconditionoftheratedcapacityduringheatingoperationis7°CDB/6°CWB.
Correspondingrefrigerantpipinglength:5.0m
Leveldifference:0m
5. CPIisapercentagevaluecomparedtotheratedvaluewhichis1.00.
6. Theerrorrateforthisvalueislessthan5%anddependsontheindoorunittype.
7. Theheatingperformancetakesintoaccountthedropthatoccursduringdefrostoperation.
8. Theairflowrateandbypassfactorarementionedinthetable. 9. Theratedpowerinputforeachmodelismentionedinthetablebelow.
Pair Pair
FCQHG125F FCQG125F FBQ125C FHQG125C FDQ125C FVQ125C FHQ125CA FUQ125C FBQ125D FCQHG125F FCQG125F FBQ125C FHQG125C FDQ125C FVQ125C FHQ125CA FUQ125C FBQ125D
Cooling 3,003,223,153,583,203,743,583,443,63
Heating 3,073,723,533,483,533,653,483,863,46
Twin Twin
FCQG60FX2 FBQ60CX2 FHQ60CAX2 FFQ60CX2 FDXS60FX2 FBQ60DX2 FNQ60AX2 FCQG60FX2 FBQ60CX2 FHQ60CAX2 FFQ60CX2 FDXS60FX2 FBQ60DX2 FNQ60AX2
Cooling 3,143,283,673,613,754,103,75
Heating 3,643,744,114,104,203,854,20
Triple Triple
FCQG50FX3 FBQ50CX3 FHQ50CAX3 FFQ50CX3 FDXS50F9X3 FBQ50DX3 FNQ50AX3 FCQG50FX3 FBQ50CX3 FHQ50CAX3 FFQ50CX3 FDXS50F9X3 FBQ50DX3 FNQ50AX3
Cooling 3,173,283,663,233,453,973,45
Heating 3,663,744,103,553,613,813,61
Doubletwin Doubletwin
FCQG35FX4 FBQ35CX4 FHQ35CAX4 FFQ35CX4 FDXS35FX4 FBQ35DX4 FNQ35AX4 FCQG35FX4 FBQ35CX4 FHQ35CAX4 FFQ35CX4 FDXS35FX4 FBQ35DX4 FNQ35AX4
Cooling 3,233,283,643,013,943,743,94
Heating 3,723,744,003,304,453,784,45
15x4
(0.08x4)
8.7x4
(0.17x4)
AFR
(BF)
12.5x4
(0.4x4)
16x4
(0.15x4)
14x4
(0.17x4)
10x4
(0.25x4)
8.7x4
(0.17x4)
16x3
(0.11x3)
15x3
(0.13x3)
16x3
(0.11x3)
18x2
(0.18x2)
16x2
(0.12x2)
AFR
(BF)
12.6x3
(0.22x3)
16x3
(0.16x3)
15x3
(0.18x3)
12x3
(0.16x3)
AFR
(BF)
13.6x2
(0.2x2)
18x2
(0.15x2)
19.5x2
(0.20x2)
14.5x2
(0.11x2)
16x2
(0.12x2)
39.0
(0.16)
28.0
(0.16)
31.0
(0.14)
32.5
(0.19)
34.0
(0.06)
AFR
(BF)
33.5
(0.19)
33.0
(0.21)
39.0
(0.16)
31.0
(0.134)
TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
ԨWB ԨDB kW kW 㸫kW kW 㸫kW kW 㸫kW kW 㸫kW kW 㸫
16,0 22 14, 10 9,54 1, 00 13,60 9,30 1,10 13,10 9,12 1,20 12,60 8,78 1,31 9,80 6,95 0,91
18,0 25 14, 70 9,50 1, 00 14,20 9,32 1,10 13,70 9,09 1,21 13,20 8,83 1,32 10,27 6,97 0,92
19,0 27 15, 00 9,52 1, 01 14,50 9,34 1,11 14,00 9,06 1,21 13,50 8, 87 1,32 10,50 6,99 0,92
19,5 27 15, 21 9,52 1, 01 14,68 9,26 1,12 14,15 9,08 1,21 13,64 8,81 1,32 10,58 6,96 0,92
22,0 30 16, 00 9,39 1, 01 15,47 9,14 1,12 14,90 8,95 1,23 14,38 8,74 1,33 11,20 6,88 0,93
24,0 32 16, 70 9,31 1, 02 16,10 9,09 1,13 15,50 8,83 1,24 14,97 8,63 1,34 11,66 6,79 0,94
25 30 35 4
46
Coefficientofthepowerinput
Coefficientofthepowerinput
Coolingcapacity[kW] Heatingcapacity[kW]
Capacityrange
Ratedpoint
Capacityrange
Ratedpoint
Indoor
Outdoortemperature[°CWB]
3D076750F
Outdoortemperature[°CDB]
Indoor
RZQG140L9V1
RZQG140LY1
Cooling Heating
Symbols
AFR: Airflowrate[m³/min]
BF: Bypassfactor
EWB: EnteringwetͲbulbtemperature(°CWB)
EDB: EnteringdryͲbulbtemperature(°CDB)
TC: Maximumtotalcooling/heatingcapacity[kW]
SHC: Sensibleheatcapacity[kW]
CPI: Coefficientofthepowerinput
PI: Powerinput[kW]
compressor+indoorandoutdoorfanmotors
Cooling Heating
Notes
1. Theratingsshownarenetcapacitieswhichincludeadeductionforindoorfanmotorheat.
2. = Maximumatstandardconditions
=Ratedcapacityandratedcoefficientofthepowerinput
Themaximumcapacityisnotguaranteedexceptatstandardconditions.
3. SHCisbasedonindoorunitsEWB&EDB.
SHCforotherdryͲbulbtemperatures=SHC+SHC*
SHC* = SHCcorrectionforotherdryͲbulbtemperatures
= 0.02xAFR(m³/min)x(1ͲBF)x(DB*ͲEDB)
4. Thecapacitiesarebasedonthefollowingconditions:
Outdoorair:85%RH
However,theoutdoorambientconditionoftheratedcapacityduringheatingoperationis7°CDB/6°CWB.
Correspondingrefrigerantpipinglength:5.0m
Leveldifference:0m
5. CPIisapercentagevaluecomparedtotheratedvaluewhichis1.00.
6. Theerrorrateforthisvalueislessthan5%anddependsontheindoorunittype.
7. Theheatingperformancetakesintoaccountthedropthatoccursduringdefrostoperation.
8. Theairflowrateandbypassfactorarementionedinthetable. 9. Theratedpowerinputforeachmodelismentionedinthetablebelow.
Pair Pair
FCQHG140F FCQG140F FBQ140C FHQG140C FVQ140C FHQ140CA FBQ140D FCQHG140F FCQG140F FBQ140C FHQG140C FVQ140C FHQ140CA FBQ140D
Cooling 4,004,174,024,054,174,054,00
Heating 3,774,304,304,274,304,274,31
Twin Twin
FCQHG71FX2 FCQG71FX2 FBQ71CX2 FHQG71CX2 FAQ71CX2 FHQ71CAX2 FUQ71CX2 FBQ71DX2 FCQHG71FX2 FCQG71FX2 FBQ71CX2 FHQG71CX2 FAQ71CX2 FHQ71CAX2 FUQ71CX2 FBQ71DX2
Cooling 3,944,113,753,593,813,593,353,75
Heating 3,714,244,704,474,684,474,364,70
Triple Triple
FCQG50FX3 FBQ50CX3 FHQ50CAX3 FFQ50CX3 FDXS50F9X3 FBQ50DX3 FNQ50AX3 FCQG50FX3 FBQ50CX3 FHQ50CAX3 FFQ50CX3 FDXS50F9X3 FBQ50DX3 FNQ50AX3
Cooling 4,123,754,254,154,263,754,26
Heating 4,244,705,434,154,374,704,37
Doubletwin Doubletwin
FCQG35FX4 FBQ35CX4 FHQ35CAX4 FFQ35CX4 FDXS35FX4 FBQ35DX4 FNQ35AX4 FCQG35FX4 FBQ35CX4 FHQ35CAX4 FFQ35CX4 FDXS35FX4 FBQ35DX4 FNQ35AX4
Cooling 4,183,754,233,835,383,755,38
Heating 4,304,705,333,815,854,705,85
15x4
(0.08x4)
8.7x4
(0.17x4)
AFR
(BF)
12.5x4
(0.4x4)
16x4
(0.15x4)
14x4
(0.20x4)
10x4
(0.25x4)
8.7x4
(0.17x4)
16x3
(0.11x3)
15x3
(0.13x3)
16x3
(0.11x3)
20.5x2
(0.13x2)
23.0x2
(0.24x2)
18.0x2
(0.13x2)
AFR
(BF)
12.6x3
(0.22x3)
16x3
(0.16x3)
15x3
(0.18x3)
12x3
(0.16x3)
AFR
(BF)
21.2x2
(0.2x2)
21.5x2
(0.14x2)
18.0x2
(0.08x2)
20.5x2
(0.13x2)
18.0x2
(0.16x2)
30.0
(0.18)
34.0
(0.17)
34.0
(0.06)
AFR
(BF)
33.5
(0.15)
33.0
(0.23)
39:C/41:H
(0.14)
34.0
(0.17)
TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI
ԨWB ԨDB kW kW
㸫
kW kW
㸫
kW kW
㸫
kW kW
㸫
kW kW
㸫
16,0 22 15,50 10,47 0,98 14,93 10,25 1,08 14,44 10,03 1,18 13,86 9,69 1,28 11,27 8,02 0,92
18,0 25 16,17 10,55 0,98 15,62 10,21 1,09 15,11 10,01 1,19 14,52 9,71 1,30 11,76 7,95 0,93
19,0 27 16,56 10,43 0,99 15,96 10,18 1,09 15,40 9,98 1,19 14,83 9,76 1,30 12,00 8,03 0,93
19,5 27 16,74 10,49 0,99 16,14 10,16 1,10 15,57 10,00 1,19 14,98 9,66 1,30 12,16 7,93 0,93
22,0 30 17,61 10,37 0,99 17,01 10,16 1,10 16,36 9,83 1,21 15,76 9,60 1,31 12,81 7,91 0,94
24,0 32 18,38 10,20 1,00 17,72 10,00 1,11 17,04 9,67 1,22 16,43 9,47 1,32 13,30 7,74 0,95
25 30 35 40 46
Coefficientofthepowerinput
Coefficientofthepowerinput
Coolingcapacity[kW] Heatingcapacity[kW]
Capacityrange
Ratedpoint
Capacityrange
Ratedpoint
Indoor
Outdoortemperature[°CWB]
Outdoortemperature[°CDB]
Indoor