RZQSG100L9V1
RZQSG100L8Y1
Cooling Heating
Symbols
AFR: Airflowrate[m³/min]
BF: Bypassfactor
EWB: EnteringwetͲbulbtemperature(°CWB)
EDB: EnteringdryͲbulbtemperature(°CDB)
TC: Maximumtotalcooling/heatingcapacity[kW]
SHC: Sensibleheatcapacity[kW]
CPI: Coefficientofthepowerinput
PI: Powerinput[kW]
compressor+indoorandoutdoorfanmotors
Cooling Heating
Notes
1. Theratingsshownarenetcapacitieswhichincludeadeductionforindoorfanmotorheat.
2. = Maximumatstandardconditions
=Ratedcapacityandratedcoefficientofthepowerinput
Themaximumcapacityisnotguaranteedexceptatstandardconditions.
3. SHCisbasedonindoorunitsEWB&EDB.
SHCforotherdryͲbulbtemperatures=SHC+SHC*
SHC* = SHCcorrectionforotherdryͲbulbtemperatures
=0.02xAFR(m³/min)x(1ͲBF)x(DB*ͲEDB)
4. Thecapacitiesarebasedonthefollowingconditions:
Outdoorair:85%RH
However,theoutdoorambientconditionoftheratedcapacityduringheatingoperationis7°CDB/6°CWB.
Correspondingrefrigerantpipinglength:5.0m
Leveldifference:0m
5. CPIisapercentagevaluecomparedtotheratedvaluewhichis1.00.
6. Theerrorrateforthisvalueislessthan5%anddependsontheindoorunittype.
7. Theheatingperformancetakesintoaccountthedropthatoccursduringdefrostoperation.
8. Theairflowrateandbypassfactorarementionedinthetable. 9. Theratedpowerinputforeachmodelismentionedinthetablebelow.
Pair Pair
FCQGH100F FCQG100F FBQ100C FHQG100C FAQ100C FVQ100C FHQ100CA FBQ100D FCQGH100F FCQG100F FBQ100C FHQG100C FAQ100C FVQ100C FHQ100CA FBQ100D
Cooling 2,57 2,88 2,87 2,96 3,16 2,96 2,96 2,84
Heating 2,51 3,05 2,96 2,99 3,17 2,99 2,99 2,94
Twin Twin
FCQG50FX2FBQ50CX2 FHQ50CAX2 FFQ50CX2 FDXS50F9X2FBQ50DX2 FNQ50AX2FCQG50FX2FBQ50CX2 FHQ50CAX2 FFQ50CX2 FDXS50F9X2 FBQ50DX2 FNQ50AX2
Cooling 2,76 2,93 3,35 3,13 3,15 3,10 3,15
Heating 2,61 2,86 3,28 3,34 3,31 3,27 3,31
Triple Triple
FCQG35FX3FBQ35CX3 FHQ35CAX3 FFQ35CX3 FDXS35FX3FBQ35DX3 FNQ35AX3FCQG35FX3FBQ35C
X3 FHQ35CAX3 FFQ35CX3FDXS35FX3 FBQ35DX3 FNQ35AX3
Cooling 2,82 2,93 3,33 2,88 3,71 2,90 3,71
Heating 2,66 2,86 3,26 3,04 4,06 3,24 4,06
8.7x3
(0.17x3)
15x3
(0.08x3)
8.7x3
(0.17x3)
18x2
(0.15x2)
16x2
(0.11x2)
AFR
(BF)
12.5x3
(0.4x3)
16x3
(0.15x3)
14x3
(0.17x3)
10x3
(0.25x3)
AFR
(BF)
12.6x2
(0.22x2)
16x2
(0.16x2)
15x2
(0.18x2)
12x2
(0.16x2)
16x2
(0.11x2)
26.0
(0.10)
28.0
(0.20)
28.0
(0.09)
29.0
(0.03)
AFR
(BF)
32.3
(0.17)
32.0
(0.17)
32.0
(0.13)
20.0
(0.09)
Coefficientofthepowerinput
Coefficientofthepowerinput
Coolingcapacity[kW] Heatingcapacity[kW]
Capacityrange
Ratedpoint
Ratedpoint
Indoor
Indoor
Outdoortemperature[°CDB] Outdoortemperature[°CWB]
Capacityrange
3D076753E
RZQSG125L9V1
RZQSG125L8Y1
Cooling Heating
Symbols
AFR: Airflowrate[m³/min]
BF: Bypassfactor
EWB: EnteringwetͲbulbtemperature(°CWB)
EDB: EnteringdryͲbulbtemperature(°CDB)
TC: Maximumtotalcooling/heatingcapacity[kW]
SHC: Sensibleheatcapacity[kW]
CPI: Coefficientofthepowerinput
PI: Powerinput[kW]
compressor+indoorandoutdoorfanmotors
Cooling Heating
Notes
1. Theratingsshownarenetcapacitieswhichincludeadeductionforindoorfanmotorheat.
2. = Maximumatstandardconditions
=Ratedcapacityandratedcoefficientofthepowerinput
Themaximumcapacityisnotguaranteedexceptatstandardconditions.
3. SHCisbasedonindoorunitsEWB&EDB.
SHCforotherdryͲbulbtemperatures=SHC+SHC*
SHC* = SHCcorrectionforotherdryͲbulbtemperatures
= 0.02xAFR(m³/min)x(1ͲBF)x(DB*ͲEDB)
4. Thecapacitiesarebasedonthefollowingconditions:
Outdoorair:85%RH
However,theoutdoorambientconditionoftheratedcapacityduringheatingoperationis7°CDB/6°CWB.
Correspondingrefrigerantpipinglength:5.0m
Leveldifference:0m
5. CPIisapercentagevaluecomparedtotheratedvaluewhichis1.00.
6. Theerrorrateforthisvalueislessthan5%anddependsontheindoorunittype.
7. Theheatingperformancetakesintoaccountthedropthatoccursduringdefrostoperation.
8. Theairflowrateandbypassfactorarementionedinthetable. 9. Theratedpowerinputforeachmodelismentionedinthetablebelow.
Pair Pair
FCQHG125F FCQG125F FBQ125C FHQG125C FAQ125C FVQ125C FHQ125CA FBQ125D FCQHG125F FCQG125F FBQ125C FHQG125C FAQ125C FVQ125C FHQ125CA FBQ125D
Cooling 3,71 3,74 3,74 4,15 3,74 4,27 4,15 3,72
Heating 3,60 3,96 3,85 3,73 3,85 3,96 3,73 3,72
Twin Twin
FCQG60FX2 FBQ60CX2 FHQ60CAX2 FFQ60CX2 FDXS60FX2 FBQ60DX2 FNQ60AX2 FCQG60FX2 FBQ60CX2 FHQ60CAX2 FFQ60CX2 FDXS60FX2 FBQ60DX2 FNQ60AX2
Cooling 3,66 3,95 4,34 4,75 4,88 4,24 4,88
Heating 3,88 4,06 4,43 4,33 4,38 4,14 4,38
Triple Triple
FCQG50FX3 FBQ50CX3 FHQ50CAX3 FFQ50CX3 FDXS50F9X3 FBQ50DX3 FNQ50AX3 FCQG50FX3 FBQ50CX3 FHQ50CAX3 FFQ50CX3 FDXS50F9X3 FBQ50DX3 FNQ50AX3
Cooling 3,69 3,95 4,33 4,14 4,07 4,08 4,07
Heating 3,90 4,06 4,42 3,87 3,92 4,09 3,92
Doubletwin Doubletwin
FCQG35FX4 FBQ35CX4 FHQ35CAX4 FFQ35CX4 FDXS35FX4 FBQ35DX4 FNQ35AX4 FCQG35FX4 FBQ35CX4 FHQ35CAX4 FFQ35CX4 FDXS35FX4 FBQ35DX4 FNQ35AX4
Cooling 3,75 3,95 4,31 3,99 4,67 3,95 4,67
Heating 3,96 4,06 4,32 3,59 4,66 4,03 4,66
15x4
(0.08x4)
8.7x4
(0.17x4)
AFR
(BF)
12.5x4
(0.4x4)
16x4
(0.15x4)
14x4
(0.17x4)
10x4
(0.25x4)
8.7x4
(0.17x4)
16x3
(0.11x3)
15x3
(0.13x3)
16x3
(0.11x3)
18x2
(0.15x2)
16x2
(0.12x2)
AFR
(BF)
12.6x3
(0.22x3)
16x3
(0.16x3)
15x3
(0.18x3)
12x3
(0.16x3)
AFR
(BF)
13.6x2
(0.2x2)
18x2
(0.15x2)
19.5x2
(0.20x2)
14.5x2
(0.11x2)
16x2
(0.12x2)
39.0
(0.16)
28.0
(0.16)
31.0
(0.14)
34.0
(0.06)
AFR
(BF)
33.5
(0.19)
33.0
(0.21)
39.0
(0.16)
31.0
(0.134)
Coefficientofthepowerinput
Coefficientofthepowerinput
Coolingcapacity[kW] Heatingcapacity[kW]
Capacityrange
Ratedpoint
Capacityrange
Ratedpoint
Indoor
Indoor
Outdoortemperature[°CDB] Outdoortemperature[°CWB]
3D076754F