Daikin Altherma EKRTCTRL1 User manual

EKRTCTRL1
EKRTCTRL2
EKWHCTRL0
EKWHCTRL1
EKPCBO
INSTALLATION MANUAL
Daikin Altherma
heat pump convector options

2
DAIKIN EUROPE N.V.
We would first of all like to thank you for having chosen one of our products.
We are sure you will be happy with it because it represents the state of the art in the technology of
home air conditioning.
By following the suggestions contained in this manual, the product you have purchased will operate
without problems, giving you optimum room temperatures with minimum energy costs.
The pictograms in the next chapter provide the necessary
information for correct, safe use of the appliance in a rapid,
unmistakable way.
Symbols
U
User
Refers to pages containing instructions or information for
the user.
I
Installer
Refers to pages containing instructions or information for
the installer.
S
Service
Refers to pages containing instructions or information for
the CUSTOMER TECHNICAL ASSISTANCE SERVICE
installer.
Editorial pictograms
Safety pictograms
Warning
The operation described may cause physical harm if not
carried out in accordance with safety regulations.
Dangerous electrical current
Make personnel aware that the operation described may
lead to electrical shocks if not carried out in accordance
with safety regulations.
High temperature danger
Of safety regulations, the risk of burns caused by contact
with components with high temperatures.
Prohibition
Refers to prohibited actions.

3
EN
1 GENERAL
1.1 General warnings ............................................................................4
2 EKRTCTRL1
2.1 Assembly, set-up and connection of on-board control panels ...........................................5
2.2 Assembly ..................................................................................5
2.3 Set-up of auxiliary dip-switch functions B and C ......................................................6
2.4 CP presence contact input connection (only for EKRTCTRL1)............................................6
2.5 Air temperature probe assembly (only for model EKRTCTRL1)............................................7
2.6 EKRTCTRL1 connections ......................................................................8
3 EKWHCTRL0
3.1 Continuous modulation circuit board for connecting remote thermostat .....................................9
3.2 LED Indications (Ref. A) ........................................................................9
3.3 EKWHCTRL0 connections ....................................................................10
4 EKWHCTRL1
4.1 Wall-mounted remote control panel assembly EKWHCTRL1 ............................................11
4.2 Spring-loaded terminal connections -AB+ and CP ...................................................12
4.3 CP occupancy contact input connection ..........................................................12
4.4 EKWHCTRL1 Connections ....................................................................13
5 EKRTCTRL2
5.1 Assembly and connections for on-board control panel EKRTCTRL2 ......................................14
5.2 Assembly .................................................................................14
5.3 Air temperature probe assembly ................................................................15
5.4 EKRTCTRL2 Connections .....................................................................15
6 SETUP MENU FOR EKRTCTRL1 - EKWHCTRL1 - EKRTCTRL2
6.1 Setup menu ...............................................................................16
7 EKPCBO
7.1 Assembly and connections for on-board control panel EKPCBO.........................................19
7.2 Assembly .................................................................................19
7.3 EKPCBO Connections .......................................................................20
7.4 Warnings table .............................................................................20
8 VERSIONS WITH CONNECTIONS ON THE RIGH
8.1 Motor connection in versions with hydraulic connections on the right EKREPLH..............................21

4
S
I
U
1.1 General warnings
- This instruction is an integral part of the booklet of
the appliance on which the kit is installed. Please consult
this booklet for general warnings and fundamental safety
rules.
- This manual is designed only for the qualified
and authorised installation technician, who must be
sufficiently trained and in possession of all psycho-
physical requirements as per the law.
- All operations must be carried out with care and
according to best practices, and in compliance with
workplace safety regulations.
- After unpacking, check that the contents are intact
and that all parts are included. If not, contact the agent
who sold the appliance to you.
- It is forbidden to modify the safety or adjustment
devices without authorisation from and indications of the
manufacturer.
- It is forbidden to dispose of, or leave in the reach of
children, the packaging materials which could become
a source of danger.
- Repairs or maintenance must be performed by the
Technical Assistance Service or by qualified personnel
in accordance with this manual. Do not modify or tamper
with the appliance as this could create dangerous
situations and the manufacturer will not be liable for any
damage caused.
GENERAL

5
S
I
U
A
D
E
C
H
I
L
B
G
M
2.1
2.2
EN
Assembly, set-up and connection of on-board control panels
Assembly
The controllers have two independent clean contacts for
controlling a refrigerator unit, a boiler and a presence input.
The 2 tube versions have a 230V output to power the
summer and winter solenoid valve.
The 10 kΩ water temperature probe positioned in the
compartment on the battery regulations the minimum level
when heating (30°C) and the maximum level when cooling
(20°C).
The board also has a function when there is no water
probe, in such cases the fan stop thresholds are ignored.
Slide the control panel into its housing in the upper part
of the device and fix it with the two fixing screws (ref. A).
To install the connection box:
- open the box (ref. B);
- lock the lower tooth into its hole (ref. C) on the side of
the device;
- hook the upper part of the box to the side (ref. D);
- fix it with the two fixing screws (ref. E);
- connect the grounding cable to the fan coil body (ref. M)
using the fixing screws (the minimum force that must be
applied for tightening screws must be around 2N);
- connect the fast connector of the MOTOR to the other
on the board (ref. I) *;
- on the two GRID block terminals (ref. L) there is a
bridge that allows the FWXM-series to work without a
microswitch.
- For other versions, remove the bridge and connect the
two terminals originating on the grill safety microswitch*;
- connect the water probe to the H2 connector on the
device.
The water temperature probe controls the temperature
inside the batteries and determines when the fan starts
according to pre-set parameters (minimum operation
in winder and maximum in summer).** Check that
they are correctly inserted into the compartment on
the battery.
- Connect the electrics, tidy cables and fix them with
the three clevises supplied (ref. G);
- close the box with the 4 screws (ref. H);
- refit the vanity plate on the side of the unit;
- tighten the upper screws on the control panel;
- place the screw head covers in their housing on the
control panel;
* For versions with hydraulic connections on the right,
refer to the relevant paragraph
** The regulation also works without a water probe
connected
EKRTCTRL1

6
S
I
U
A
C
B
N
EV1
N
EV2
BA
ON
D
C
H4 H2 AIR
COMM
ASCII
RTU
MOTOR
LN
GRIDGRIDCP
CHILLER BOILER
LED
2.3
2.4
There are two dip switches on the controller circuit board
for configuring unit operation as per requirements.
- The night-time heating operation logic is modified by
using dip switch C:
- in the ON position, the fan is always off, and heats the
room using radiation and natural convection, as with
traditional radiators; in the off position it operates as a
normal fan.
- By positioning dip switch B to ON, when cooling, the
fan operates at the minimum speed even after having
reached the set point, to allow for more uniform
operation of the temperature probe and to avoid
layering in the air. With the cursor in the OFF position,
the functions are cycled (4 minutes ON, 10 minutes
OFF).
On closing the contact connected to the CP input (ref. A)
the panel is placed in stand-by mode.
If the contact is open the unit is active, if the contact is
closed it is deactivated when a key is pressed the
symbol flashes.
The input cannot be connected in parallel to that of other
electronic boards (use separate contacts).
Set-up of auxiliary dip-switch functions B and C
CP presence contact input connection (only for EKRTCTRL1)

7
S
I
U
B
C
D
A
2.5
EN
- To position the temperature probe (ref. A):
- pass the probe through the hole on the shoulder (ref. B)
- insert the probe into the lower hole (ref. C)
- fix the probe on the relevant hook (ref. D)
Air temperature probe assembly (only for EKRTCTRL1)

8
S
I
U
EKRTCTRL1
2.6 EKRTCTRL1 connections
H2* water temperature probe (10 kΩ)
AIR air temperature probe (10 kΩ)
M1 DC inverter fan motor
S1 grill safety micro-switch
Y1 water solenoid valve (230V/ 50Hz 1A output
voltage)
Y2 mobile flap connection
230V/ 50Hz 1A output voltage.
L-N
230V/50Hz electrical power supply
BO boiler consent output (free contact max 1A)
CH chiller consent output (free contact max 1A)
CP presence input sensor (if closed, the fan coil unit
is placed in standby).
*If after switching the power on the board
detects the H2 probe, start-up occurs in normal
conditions with the minimum water temperature
when heating (30°C) and maximum when
cooling (20°C).
The board also has a function when there is no
probe, in such cases the fan stop minimum and
maximum thresholds are ignored.

9
S
I
U
A
3.1
3.2
EN
Continuous modulation circuit board for connecting remote thermostat
LED Indications (Ref. A)
EKWHCTRL0
The circuit board for remote control is for all functions of
the fan coil system from the wall-mounted remote control
EKWHCTRL0.
A remote control can be connected to a maximum of
30 fan coils that will be controlled in broadcast mode
(simultaneous commands to all fan coils).
It can be installed on all versions, the board has a green
LED that indicates the operational state and any anomalies.
The main operational parameters, the set point and the
room temperature are transmitted from the wall-mounted
remote control EKWHCTRL0 to all terminals connected to
the network, allowing unified operation.
Refer to the instructions for this control for use of the fan
coils.
The 10 kΩ water temperature probe positioned in the
device battery regulations the minimum level when heating
(30°C) and the maximum level when cooling (20°C).
Green LED: Indicates that the unit is
operational. Flashing indicates an anomaly. LED off: unit is off or has no power.
Error signals
Error Display
Communication error. The circuit board expects continuous information exchange on the serial line
with the wall-mounted control EKWHCTRL1. If this exchange is lost for more than 5 minutes, an
error warning is displayed and the unit deactivated.
6 flashes + pause
Problem with fan motor (e.g. blockage caused by foreign objects, faulty rotation sensor). 2 flashes + pause
Water temperature probe fault (H2).
In this case, ensure that the probe installed is 10 kΩ. 3 flashes + pause
Engaging of grille microswitch S1 due to filter cleaning operation. Continuous rapid
flashing
Water demand detected by probe H2 insufficient (above 20°C when cooling, below 30°C when
heating). Stops the fan until the temperature returns to a suitable level to satisfy the demand*. 1 flashes + pause
* If after having powered the board the water probe is
detected, start-up takes place with the minimum and
maximum water temperature thresholds.
The board also has a function when there is no probe, in
such cases the fan stop thresholds are ignored.

10
S
I
U
H4
8mm0.2-1.5mm2
EKWHCTRL0
A
3.3 EKWHCTRL0 connections
-AB+ serial connection for wall-mounted remote
control EKWHCTRL1 (respect AB polarity)
H2** hot water temperature probe (10 kΩ)
M1 DC inverter fan motor
S1 grill safety micro-switch
Y1 hot water solenoid valve (230V/ 50Hz 1A output
voltage)
Y2 mobile flap
(230V/ 50Hz 1A output voltage)
L-N
230V/50Hz electrical power supply
BO boiler consent output (free contact max 1A)
CH chiller consent output (free contact max 1A)
CP not used in this version
AIR Air probe optional (*)
*Alternatively, connect the wall-mounted
controller EKWHCTRL1 to the air probe
** If after switching the power on the board
detects the H2 probe, start-up occurs in normal
conditions with the minimum water temperature
when heating (30°C) and maximum when
cooling (20°C).
The board also has a function when there is no
probe, in such cases the fan stop minimum and
maximum thresholds are ignored.
Rigid or flexible wires with a 0.2 to 1.5 mm² cross-section
(0.75 mm² if two wires are connected to the same terminal
block) can be inserted in the 4 spring-loaded terminal
blocks (ref. A) for connection of the wall-mounted controller
EKWHCTRL1. If the wires have wire end ferrules with a
plastic collar, the maximum cross-section is 0.75 mm².
Strip 8 mm of the wire, then if the wire is rigid, you can
insert it easily whereas, if it is flexible, it is advisable to use
long nose pliers.
Push the wire completely in and check that it is anchored
by pulling it gently.
To disconnect the cables, press the
corresponding white indent (ref. A) with a
screwdriver and remove the conductor.

11
S
I
U
B
A
A
4.1
EN
The wall-mounted remote control EKWHCTRL1 is an
electronic thermostat (fitted with an optional temperature
probe which can be remotely installed in one of the fan
coils connected to it) with the possibility to control one
or more units (up to max. 30) fitted with an electronic
controller for remote control EKWHCTRL0.
- Install the wall-mounted remote control EKWHCTRL1
away from doors and/or windows and from heat
sources (radiators, fan coils, hobs, direct sunlight), on
internal walls and around 1.5m from the floor.
The wall-mounted remote control is inside the pre-
assembled package, therefore prior to affixing to the wall,
the two parts should be separated by unhooking the two
protruding teeth on the rear (A).
Use the base of the controller (ref. B in diagram) to trace
the fixing points on to the wall (use two opposing holes).
Then proceed with the following operations:
- drill holes in the wall;
- pass the cables through the window on the base;
- fix the base of the controller to the wall using suitable
screws and wall plugs;
- make the electrical connections then close the
controller taking care not to crush the conducting
wires.
EKWHCTRL1
Wall-mounted remote control panel assembly EKWHCTRL1

12
S
I
U
8mm0.2-1.5mm2
C
A
A
B
4.2
4.3
Rigid or flexible wires with a 0.2 to 1.5 mm² cross-section
can be inserted in the spring-loaded terminal blocks for
the serial connection. If the wires have wire end ferrules
with a plastic collar, the maximum cross-section reduced
to 0.75 mm².
For correct and safe connection, carry out the following
operations:
- Strip back the wires by 8mm as shown below;
- if the cable is rigid the end of the wire can be inserted
easily, whereas with flexible cable it may be easier to
use a long pointed pair of pliers to insert correctly.
- Push the wire completely in and check that it is
anchored by pulling it gently.
- To disconnect the cables, press the corresponding
white indent (ref. C) with a screwdriver and remove
the conductor.
Spring-loaded terminal connections -AB+ and CP
CP occupancy contact input connection
On closing the contact connected to the CP input (ref.
A) the panels are placed into stand-by. If the contact is
open the units are active, if the contact is closed they are
deactivated when a key is pressed the symbol flashes.
- To connect the CP input in more than one PCB,
observe the polarity between external relay contact
and CP contacts as shown in the figure.
contact CP
- contact -
Aremote control terminal block
Bauxiliary relay

13
S
I
U
4.4
CP
L
N
MOTOR
+A B -A A B B -
LED
AB CD AB CD
H4 H2 AIR H4 H2 AIR
ON
MOTOR
LED
ON
N EV1 N EV2
COMM
GRID CP
COMM
GRID CP
N EV1 N EV2
EN
Connect the RS485 line of the wall-mounted remote control
to one or more (up to a maximum of 30) devices fitted with
electronics for remote control EKWHCTRL0 using a suitable
two-core cable for serial connections RS485 keeping the
power supply cables separate.
- Chase out the wall in order to minimise the length of
the leads;
- complete the line with the supplied 120 Ω heating
element;
- do not make "star" connections;
- The RS485 cable connection is polarised, respect the
"A" and "B" indications on every periphery connected
(for connecting, it is preferable to use a shielded two-
core cable with a minimum thickness of 0.35 mm2);
- connect the + and - power terminals on the wall
mounted terminal block, 5V DC, to one of the boards
EKWHCTRL0, respecting polarity.
EKWHCTRL1 Connections

14
S
I
U
A
D
E
C
H
B
G
M
5.1
5.2
F
L
I
Slide the control panel into its housing in the upper part
of the device and fix it with the two fixing screws (ref. A).
To install the connection box:
- open the box (ref. B);
- lock the lower tooth into its hole (ref. C) on the side of
the device;
- hook the upper part of the box to the side (ref. D);
- fix it with the two fixing screws (ref. E);
- connect the grounding cable to the unit structure (ref.
M) using the fixing screws (the minimum force that
must be applied for tightening screws must be around
2N);
- connect the fast connector of the MOTOR to the other
on the board (ref. I) *;
- on the two GRID block terminals (ref. L) there is a
bridge that allows FWXM-series to work without a
microswitch.
For versions in-built into the formwork, follow the
microswitch connection instructions on the instruction
sheet of the vanity panel.
For other versions, remove the bridge and connect
the two terminals originating on the grill safety
microswitch*;
- connect the water probe connector (ref. F) on the unit.
The water temperature probe controls the temperature
inside the batteries and determines when the fan starts
according to pre-set parameters (minimum operation
in winter and maximum in summer).**
Check that they are correctly inserted into the
compartment on the battery.
- Connect the electrics, tidy cables and fix them with
the three clevises supplied (ref. G);
- close the box with the 4 screws (ref. H);
- refit the vanity plate on the side of the unit;
- tighten the upper screws on the control panel;
- place the screw head covers in their housing on the
control panel;
*N.B.: * For versions with hydraulic connections on the
right, refer to the relevant paragraph
** If after switching the power on the board detects the
H2 probe, start-up occurs in normal conditions with the
minimum and maximum functions.
The board also has a function when there is no H2 probe,
in such cases the fan stop thresholds are ignored.
The on-board controller is a panel with 8 capacitative keys
and amber display that contains the AUTO function (step
ventilation adjustment).
The EKRTCTRL2 thermostat can be set from 5 to 40°C,
has a winter and summer selector and the 10 kΩ water
temperature probe positioned in the compartment on the
battery regulations the minimum level when heating (30°C)
and the maximum level when cooling (20°C). It is suitable
for installing on board and has a 230V output for controlling
a solenoid valve.
The board also has a function when there is no H2 probe,
in such cases the fan stop thresholds are ignored.
EKRTCTRL2
Assembly and connections for on-board control panel EKRTCTRL2
Assembly

15
S
I
U
B
C
D
A
A
INN-FR-B20
H4
COMM
Y2Y1
H2
DISPLAY INN-DU4
H2
NEV1 NEV2
ASCII
GRID
S1
D
AIR
RTU
M1
AIR
BC
ZOT
MOTOR
6V DC
230V AC
HRS
RS
L N
NL
EKRTCTRL2
5.3
5.4
EN
To position the temperature probe (ref. A):
- pass the probe through the hole on the shoulder (ref. B)
- insert the probe into the lower hole (ref. C)
- fix the probe on the relevant hook (ref. D)
Air temperature probe assembly
EKRTCTRL2 Connections
H2* water temperature probe (10 kΩ)
AIR air temperature probe (10 kΩ)
M1 DC inverter fan motor
S1 grill safety micro-switch
Y1 water solenoid valve (230V/ 50Hz 1A output
voltage)
Y2 Mobile flap connection.
230V/ 50Hz 1A output voltage.
L-N
230V/50Hz electrical power supply
*If after switching the power on the board
detects the H2 probe, start-up occurs in normal
conditions with the minimum water temperature
when heating (30°C) and maximum when
cooling (20°C).
The board also has a function when there is no
probe, in such cases the fan stop minimum and
maximum thresholds are ignored.

16
S
I
U
6.1
Ad
Ub
SETUP MENU FOR EKRTCTRL1 - EKWHCTRL1 - EKRTCTRL2SETUP MENU FOR EKRTCTRL1 - EKWHCTRL1 - EKRTCTRL2
Through the remote control, the access to Setup menu will
be available from display off:
Use the icons to move inside the menu.
Use the icon to select menu items and to confirm changes
made.
Pressing and confirming the change will switch to the next
item.
To exit from menu:
- press the icon for 10 sec.
- or wait 30 sec. for automatic shutdown
After 30 seconds from the last action, the control goes
off and the settings is memorised.
Setup menu
Key Operation Display
- press the key "ON" for 10 sec.
- the device turns on and the temperature appears
- continue to press until "Ad" appears
Ad Reserved ("01" default)
uu Reserved ("no" default)
Ub Adjust buzzer volume
br Adjust the brightness
di Digital input
rZ Reserved ("no" default)
rb Reserved ("no" default)
Fr Factory reset
ot Offset probe T
oh Offset probe HR
Sc Scale
rE Reserved ("no" default)
Menu items
To change the volume:
The volume changes after you confirm the modification.
Display Operation
- the volume setting range is from 00 (min) to 03 (max)
- Increase or decrease the volume with the icons
Adjusting buzzer volume

17
S
I
U
br
di
Fr
ot
EN
To adjust the brightness:
The brightness changes after confirming the modification.
You can also reduce the brightness of the display through
the control's key. From the display off, press the icon for
20 sec. The message "01" will appear. Press to decrease
brightness "00". Wait 30 sec. for the correct settings to be
verified.
Display Operation
- the brightness adjustment range is from 00 to 01
- increase and decrease the brightness with the icons
Adjusting the brightness of the display
To change the digital input, select "di" menu:
By default, digital input is set to CP.
By selecting one of the other inputs (CO,CC) the
seasonality is locked. It is not possible to modify it through
the key of the control.
For return to the default settings, set the digital input to
"CP".
Display Operation
- CP / clean contact (default)
- CO / cooling open
- CC / cooling close
Settings of the digital input
To reset the control to factory settings:
Display Operation
- select "YS" to reset the settings
- select "no" to keep the current settings
Factory reset
Use this adjustment carefully.
Use this adjustment only after having actually detected
a discrepancy compared with the actual room temperature
using a reliable device.
Adjust the value in a range of - 9 °C to + 12 °C, at
variations of 0,1 °C.
After 30 seconds from the last action, the control goes
off and the settings is memorised.
Display Operation
- the adjustment range is from -9 to 12
Probe T regulation offset (room temperature probe)

18
S
I
U
oh
Sc
Use this adjustment carefully.
Use this adjustment only after having actually detected a
discrepancy compared with the actual room humidity using
a reliable device.
Adjust the value in a range of - 9 °C to + 9 °C, at
variations of 1 °C.
After 30 seconds from the last action, the control goes
off and the settings is memorised.
Display Operation
- the adjustment range is from -9 to 9
Sensor offset settings (humidity probe)
To change the temperature unit:
Display Operation
- select °C o °F
Scale

19
S
I
U
A
MLF
7.1
7.2
EN
Slide the control panel into its housing in the upper part
of the device and fix it with the two fixing screws (ref. A).
To install the board on the fan coil:
- connect the grounding cable to the unit structure (ref.
M) using the fixing screws (the minimum force that
must be applied for tightening screws must be around
2N);
- connect the fast connector of the MOTOR to the other
on the board (ref. I) *;
N.B.: should the board not be fitted in the factory, the
fan motor must be rotated 180° due to the length of
the standard fan coil cable.
- on the two GRID block terminals (ref. L) there is a
bridge that allows FWXM-series to work without a
microswitch.
- For other versions, remove the bridge and connect
the two terminals originating on the grill safety
microswitch*.
-N.B.: should the two brown terminals on the unit be
too short, replace them with those included in the kit
packaging.
- make the electrical connections, tidy the cabling;
- refit the vanity plate on the side of the unit;
- tighten the upper screws on the control panel;
- place the screw head covers in their housing on the
control panel;
* For versions with hydraulic connections on the
right, refer to the relevant paragraph
The on-board controller with speed selector and ON/OFF key
and TERM room thermostat is suitable for fitting on board the
unit and has a 230V output for controlling a solenoid valve.
EKPCBO
Assembly and connections for on-board control panel EKPCBO
Assembly

20
S
I
U
TA
M1
S1
Y1
L-N
FF
EKPCBO
7.3
7.4
230V connection permission from room
thermostat
DC inverter fan motor
grill safety micro-switch
water solenoid valve (230V/ 50Hz 1A output
voltage)
230V/50Hz electrical power supply
output for mobile suction panel servo (power
output 230V/ 50Hz 1A)
EKPCBO Connections
Warnings table
The board provides diagnostics in the event of anomalies,
which can be interpreted from combinations of LEDs.
The following table summarises the warnings.
• Flashing LED : TA contact open
• Flashing LED : TA contact closed;
• 4 flashing LEDs: S1 contact open;
• LED on: supersilent speed active (400 rpm).
• LED on: minimum speed active (680 rpm).
• LED on: medium speed active (1,100 rpm).
• LED on: maximum speed active (1,500 rpm).
This manual suits for next models
4
Table of contents
Other Daikin Heater manuals

Daikin
Daikin DRC User manual

Daikin
Daikin Altherma 3 H F User manual

Daikin
Daikin FWXV15AVEB User manual

Daikin
Daikin AHKD 20 User manual

Daikin
Daikin KEH041A43 User manual

Daikin
Daikin KEH094A41E User manual

Daikin
Daikin KEH041A42 User manual

Daikin
Daikin Altherma 3 H HT F User manual

Daikin
Daikin REYQ8-48PY1B User manual

Daikin
Daikin REYQ8-48PY1B User manual
Popular Heater manuals by other brands

KUTON
KUTON YD-PHB-1 Operation instructions

Jaga
Jaga Eyecatchers Aristocrat Mounting instructions

EUROM
EUROM RK2009N instruction manual

Commercial Electric Heat
Commercial Electric Heat RDH 6000 installation instructions

ThermoTec
ThermoTec AeroFlow instructions

Glen
Glen 2570 Installation and operating instructions