DALCNET CBU-DALI-GATEWAY Application guide

CBU-DALI-GATEWAY
Device Manual
Made in Italy
DALCNET S.r.l.
36077 Altavilla Vicentina (VI) –Italy
Via Lake Garda, 22
Tel. +39 0444 1836680
www.dalcnet.com –info@dalcnet.com
REv. 25/01/2023 - Pag. 1/11
FEATURES
CONVERTER+CASAMBI+DALI+GATEWAY
Input: DC 12-24-48 Vdc
Command: CASAMBI APP
Local Control programmable from CASAMBI APP: n°1 button Normally Open
Casambi signal to DALI protocol converter and vice versa
Possibility to control devices with DALI control via CASAMBI APP
Ability to Address DALI Devices
Extended temperature range
100% Function Test
PRODUCT DESCRIPTION
The device receives the command signal from the Casambi APP and depending on the fixture set sends the signal in a predetermined
sequence of DALI addresses.
See pag.7 for the DALI Addresses map.
With the "CBU DALI GATEWAY" profile, the device receives commands from an external DALI Master and sends control signals to
the Casambi lamps of the network to which it is associated. Each Casambi lamp has a DALI address.
In the case of Casambi Tunable White or RGB/RBGW devices, these will be recognized by the DALI Master as DALI DT8.
PRODUCT CODE
1
DALI bus power is required
2
Address management (DALI version) depends on the configuration of the Casambi module.
CODE
Power Supply
Command
incoming
Command
Outgoing
Type of Command
CBU-DALI-GATEWAY1
12-24-48V DC
APP CASAMBI
DALI2
N° 1 N.O. Push Button

CBU-DALI-GATEWAY
Device Manual
Made in Italy
DALCNET S.r.l.
36077 Altavilla Vicentina (VI) –Italy
Via Lake Garda, 22
Tel. +39 0444 1836680
www.dalcnet.com –info@dalcnet.com
REv. 25/01/2023 - Pag. 2/11
PROTECTIONS
TYPE IF PROFILES
PROFILE NAME
# PROFILE
DESCRIPTION
CBU DALI GATEWAY
24814
Control of Casambi devices from DALI network
DALI2 BROADCAST
24810
Basic DALI broadcast dimmer, no short address required.
W AUTOMATIC
25136
Fixture for checking 1 DALI address
WWWW AUTOMATIC
25139
Fixture for checking 4 DALI addresses
TW AUTOMATIC 2700-6000K
25140
Mixer hot/cold color with two channels.
RGB AUTOMATIC
25141
Fixture RGB DT6
RGB+W AUTOMATIC
25142
Fixture RGBW DT6
RGB+TW AUTOMATIC
25137
Fixture RGB+Tunable White DT6
WWWW GROUP
25138
Fixture for control of 4 DALI groups
8XW GROUP
25291
Fixture for control of 8 DALI groups
DALI DT8 BC RGB
11121
Fixture RGB DT8
DALI DT8 BC RGB+W
11545
Fixture RGB+W DT8
DALI DT8 BC TW
25143
Fixture Tunable White DT8
3
Protection on control logic
OVP
Over voltage protection 3
✓
UVP
Under voltage protection 3
✓
RVP
Reverse polarity protection 3
✓
VET
Protection with input fuse 3
✓

CBU-DALI-GATEWAY
Device Manual
Made in Italy
DALCNET S.r.l.
36077 Altavilla Vicentina (VI) –Italy
Via Lake Garda, 22
Tel. +39 0444 1836680
www.dalcnet.com –info@dalcnet.com
REv. 25/01/2023 - Pag. 3/11
REFERENCE STANDARDS
EN 61347-1
Lamp control gear –Part 1: General and safety requirements
EN 55015
Limits or methods of measurement of radio disturbance characteristics of electrical lighting and similar
equipment
EN 61547
Equipment for general lighting purpose –EMC immunity requirements
TECHNICAL SPECIFICATIONS
CBU-DALI-GATEWAY
Supply voltage
min: 10,8 Vdc .. max: 52,8 Vdc
Nominal Power4
Min
Max
@12V
61 mW
115 mW
@24V
120 mW
176 mW
@48V
230 mW
296 mW
Power loss in standby mode
<500mW
Operating frequency5
2402 –2480 MHz
Maximum output power5
7dBm
Storage temperature
min: -40 max: +60 °C
Ambient temperature4
min: -10 max: +40 °C
IP protection class
IP10
Wiring
2.5mm 2 solid –2.5mm2 stranded –30/12 AWG
Wire strip lenght
5.5 –6.5 mm
Mechanical dimensions
92 x 36 x 62 mm DIN RAIL 2M
Package dimensions
124 x 71 x 48 mm
Casing material
Plastic
Weight
88g
4
Maximum value, depending on ventilation conditions
5
The parameters are derived from the configuration of the Casambi module

CBU-DALI-GATEWAY
Device Manual
Made in Italy
DALCNET S.r.l.
36077 Altavilla Vicentina (VI) –Italy
Via Lake Garda, 22
Tel. +39 0444 1836680
www.dalcnet.com –info@dalcnet.com
REv. 25/01/2023 - Pag. 4/11
WIRING DIAGRAM
As shown in the connection diagram, perform the following steps to install the product
Connect the normally open button to the INPUT terminals with the " " symbol.
Be sure not to connect live parts to the INPUT terminals.
Connect the constant voltage SELV power supply to the DC IN terminal with the "+" and "-" symbols.
Make sure you are not using a power supply with a constant current output and check that the polarity of the cables is
correct.
Connect the DALI BUS on the "DALI OUT" terminals.
Like any other product with Bluetooth control, be sure not to place the product inside a metal case or placed near large metal
structures. The metal will greatly block the radio signal important for the operation of the device.

CBU-DALI-GATEWAY
Device Manual
Made in Italy
DALCNET S.r.l.
36077 Altavilla Vicentina (VI) –Italy
Via Lake Garda, 22
Tel. +39 0444 1836680
www.dalcnet.com –info@dalcnet.com
REv. 25/01/2023 - Pag. 5/11
LOCAL COMMANDS FUNCTIONALITY
N.O. PUSH BUTTON
6
The Casambi app allows you to program the local command with some prearranged functions.
Button No.
Function
1
Controls a luminaire
Click
Long press (>1s)
Tap to turn a luminaire on or off –hold to adjust
luminaire brightness
Controls an element
Click
Long press (>1s)
Tap to turn a device element on or off –hold to adjust
the element value
Control a group
Click
Long press (>1s)
Tap to turn a group on or off –hold to adjust
brightness
Control scene
Click
Long press (>1s)
Tap to turn a scene on or off –hold to adjust scene
brightness
Control all luminaires
Click
Long press (>1s)
Tap to turn all luminaires on or off –hold to adjust
brightness
Cycles scenes
Click
Long press (>1s)
Tap to cycle through the list of scenes –hold to adjust
current scene brightness
Active/Standby
Click
Long press (>1s)
Tap to switch between two scenes –hold to adjust
current scene brightness
Controls a luminaire
Click
Long press (>1s)
Tap to turn a luminaire on or off –hold to adjust
luminaire brightness
Controls an element
Click
Long press (>1s)
Tap to turn a device element on or off –hold to adjust
the element value
Control a group
Click
Long press (>1s)
Tap to turn a group on or off –hold to adjust
brightness
For all other functions, consult the CASAMBI APP documentation at:
https://support.casambi.com/support/home
UNPAIRING THE DEVICE FROM THE CASAMBI NETWORK
If the device is associated with a network to which you do not have the credentials and you want to associate it with a new one,
follow the settings specified in the Casambi APP in the "Nearby Devices" section. Once the decoupling function has started and the
procedure has begun, remove the mains power supply (230Vac/110Vac) of the power supply connected to the CBU-DALI-GATEWAY
and turn it back on within 1 –2 seconds.
If you turn the power supply off and on quickly, decoupling may not occur correctly. Repeat the decoupling sequence by escalating
1 or 2 seconds more between the instant you turn off and turn the mains power to the power supply back on
7
.
If you are unable to unpair the device, associate an N.A. button to the "INPUT" input of the CBU-DALI-GATEWAY and during the
unpairing procedure, press the button.
6
By default, the button is set as "Control a lamp".
7
The discharge time of the secondary power supply depends on the construction characteristics of the power supply used.

CBU-DALI-GATEWAY
Device Manual
Made in Italy
DALCNET S.r.l.
36077 Altavilla Vicentina (VI) –Italy
Via Lake Garda, 22
Tel. +39 0444 1836680
www.dalcnet.com –info@dalcnet.com
REv. 25/01/2023 - Pag. 7/11
DALI MAP ADDRESSES OF THE CBU-DALI-GATEWAY
"AUTOMATIC" FIXTURE CONFIGURATION:
The "AUTOMATIC" fixtures of the CBU-DALI-GATEWAY automatically direct the UNADDRESSED devices connected to the DALI BUS.
CBU DALI GATEWAY
Casambi Slider
None
The device appears in the Gateway section of the
Casambi app
DALI2BROADCAST
Casambi Slider
Dimmer 0
Address
Command
BROADCAST
Dimmer ALL
WAUTOMATIC
Casambi Slider
Dimmer 0
Address
Command
A0
Dimmer 0
WWWW AUTOMATIC
Casambi Slider
Dimmer 0
Dimmer 1
Dimmer 2
Dimmer 3
Address
Command
A0
Dimmer 0
A1
Dimmer 1
A2
Dimmer 2
A3
Dimmer 3

CBU-DALI-GATEWAY
Device Manual
Made in Italy
DALCNET S.r.l.
36077 Altavilla Vicentina (VI) –Italy
Via Lake Garda, 22
Tel. +39 0444 1836680
www.dalcnet.com –info@dalcnet.com
REv. 25/01/2023 - Pag. 8/11
TW AUTOMATIC 2700 -6000K
Casambi Slider
Dimmer
Color temperature
Address
Command
A0
Warm white
A1
Cold white
RGB AUTOMATIC
Casambi Slider
Dimmer
Color
Saturation
Map
Address
Command
A0
R –Red
A1
G –Green
A2
B –Blue
RGBW AUTOMATIC
Casambi Slider
Dimmer
White / Color
Color
Saturation
Map
Address
Command
A0
R –Red
A1
G –Green
A2
B –Blue
A3
W –White
RGB TW AUTOMATIC
Casambi Slider
Dimmer
Color temperature
White / Color
Color
Saturation
Map
Address
Command
A0
R –Red
A1
G –Green
A2
B –Blue
A3
WW –Warm White
A4
CW –Could White

CBU-DALI-GATEWAY
Device Manual
Made in Italy
DALCNET S.r.l.
36077 Altavilla Vicentina (VI) –Italy
Via Lake Garda, 22
Tel. +39 0444 1836680
www.dalcnet.com –info@dalcnet.com
REv. 25/01/2023 - Pag. 9/11
FIXTURE "GROUP" CONFIGURATION:
The "GROUP" fixtures of the CBU-DALI-GATEWAY send group commands. The DALI devices must be previously addressed and
assigned to the desired group through an external DALI master.
WWWW GROUP
Casambi Slider
Group 0
Group 1
Group 2
Group 3
Address
Command
G0
Group 0
G1
Group 1
G2
Group 2
G3
Group 3
8W GROUP
Casambi Slider
Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7
Address
Command
G0
Group 0
G1
Group 1
G2
Group 2
G3
Group 3
G4
Group 4
G5
Group 5
G6
Group 6
G7
Group 7

CBU-DALI-GATEWAY
Device Manual
Made in Italy
DALCNET S.r.l.
36077 Altavilla Vicentina (VI) –Italy
Via Lake Garda, 22
Tel. +39 0444 1836680
www.dalcnet.com –info@dalcnet.com
REv. 25/01/2023 - Pag. 10/11
FIXTURE CONFIGURATION "DT8 BC":
The "DT8 BC" fixtures of the CBU-DALI-GATEWAY send broadcast commands to devices compliant withIEC 62386-209 - "Device
Type 8".
DALI DT8 BC TW
Sliderr Casambi
Dimmer
Color temperature
Address
Command
Broadcast
DT8 Dimming + CCT
DALI DT8 BC RGB
Casambi Slider
Dimmer
Color
Saturation
Map
Address
Command
Broadcast
DT8 Dimming + RGB
DALI DT8 BC RGBW
Casambi Slider
Dimmer
White / Color
Color
Saturation
Map
Address
Command
Broadcast
DT8 Dimming + RGBW

CBU-DALI-GATEWAY
Device Manual
Made in Italy
DALCNET S.r.l.
36077 Altavilla Vicentina (VI) –Italy
Via Lake Garda, 22
Tel. +39 0444 1836680
www.dalcnet.com –info@dalcnet.com
REv. 25/01/2023 - Pag. 11/11
TECHNICAL NOTE
INSTALLATION
•CAUTION: The product may only be connected and installed by a qualified electrician. All applicable regulations, legislation, and
building codes must be observed. Incorrect installation of the product can cause irreparable damage to the product and the
connected LEDs.
•Maintenance must be performed only by a qualified electrician in compliance with current regulations.
Pay attention when connecting the LEDs: polarity reversal results in no light output and often damages the LEDs.
•The product is designed and intended to operate LED loads only. Powering non-LED loads may push the product outside its
specified design limits and is, therefore, not covered by any warranty.
Operating conditions of the product may never exceed the specifications as per the product datasheet.
•The product must be installed inside a switchgear/controlgear cabinet and/or junction box protection against overvoltage.
•The product must be installed in a vertical or horizontal position with the label/top cover facing upwards or vertically. Other
positions are not permitted. The bottom position is not permitted (label/top cover facing down).
•Keep separated 230Vac (LV) circuits and not SELV circuit from safety extra low voltage (SELV) circuit and from any connection
with this product. It is absolutely forbitten to connect, for any reason whatsoever, directly or indirectly, the 230Vac mains voltage
to the product (terminal block of BUS included).
•The product must be dissipated correctly.
•The use of the product in harsh environments could limit the output power.
•For built-in components inside luminaires, the ta ambient temperature range is a guideline given for the optimum operating
environment. However, integrator must always ensure proper thermal management (i.e. correct mounting of the device, air flow
etc.) so that the tc point temperature does not exceed the tc maximum limit in any circumstance. Reliable operation and lifetime
is only guaranteed if the maximum tc point temperature is not exceeded under the conditions of use.
POWER SUPPLY
•Only use SELV power supplies with limited current for device power supply, short circuit protection and the power must be
dimensioned correctly.
In the case of power supplies equipped with ground terminals, it is mandatory to connect ALL protective ground points (PE=
Protection Earth) to a properly and certified protection earth.
•The connection cables between the very low voltage power source and the product must be properly dimensioned and must be
insulated from any wiring or part at non-SELV voltage. Use double insulated cables.
•Dimension the power of the power supply in relation to the load connected to the device. In case the power supply is oversized
compared to the maximum absorbed current, insert a protection against over-current between the power supply and the device.
COMMAND
•The length of the cables connecting between the local commands (N.O. Push button or other) and the product must be less than
10m. The cables must be properly dimensioned and must be insulated from any non-SELV wiring or voltage. It is recommended
to use double insulated cables, if deemed appropriate also shielded.
•ALL device and control signal connected to the local command “N.O. Push button” with symbol, they must not supply
any type of voltage.
OUTPUTS
•It is recommended a length of the connecting cables between the product and the LED module less than 10m. The cables must
be properly dimensioned and must be insulated from any wiring or circuits at voltage not SELV. It is recommended to use double
insulated cables. In case you want to use connecting cables between the product and the LED module greater than 10m, the
installer must guarantee the correct operation of the system. In any case, the connection between the product and the LED
module must not exceed 30m.
ONLY CASAMBI/BLUETTOTH PRODUCT
•WARNING: For optimal functionality of the Casambi signal, do not put the device into metal or aluminium boxes and do not shield
the device. As any other Casambi product, should not be placed in a metal enclosure or next to large metal structures. Metal will
effectively block all radio signals which are crucial to the operation of the product.
WARNINGS
•To guarantee the best performances and the full use of functions, make sure to download on your device the last release of
CASAMBI APP.
•Whenever CASAMBI APP requires an upgrade of the profile installed in the LED Dimmers, follow the instruction to do it. This allows
you to stay always up to date and benefit of new functions released.
•Functionality test are done on all dimmers to ensure the right working. In case the device is still paired to “Dalcnet network”, you
are asked to unpair it by following the instructions on CASAMBI APP and in paragraph “UNPAIR DEVICE FROM THE CASAMBI
NETWORK”.
Other manuals for CBU-DALI-GATEWAY
1
Table of contents
Other DALCNET Gateway manuals