DALEMANS U-V6 User manual

U•V6
ALARM CONTROL UNIT FOR
TOXIC & FLAMMABLE GASES
INSTRUCTION
MANUAL

Copyright ©2021 DALEMANS S.A.
Revision V1R0 • 01/2022
Any reproduction, partial or full, of this document by means
of any process whatsoever without prior written consent
from DALEMANS s.a. is strictly prohibited.
Warning
All information contained in this document is non-
contractual
and subject to change without notice.
We also encourage you to regularly check the availability
of a new version on our website: http://www.dalemans.com
Please contact your distributor in case of doubt,
DALEMANS sa/nv
Rue Jules Mélotte, 27A • B-4350 Remicourt (Belgique)
Tél. +32 19 33 99 43 • Email: sales@dalemans.com

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
2 |65
Certified
ISO9001 • VCA
www.dalemans.com
TABLE OF CONTENT
1 General remarks ................................................................................5
1.1 Responsibilities - guarantees...................................................................... 5
1.2 Safety information........................................................................................ 6
1.3 Environment ................................................................................................. 7
1.4 Operating Principle ...................................................................................... 7
1.5 Display interface........................................................................................... 8
LED ............................................................................................................. 8
Keypad........................................................................................................ 9
Display........................................................................................................ 9
2 Installation........................................................................................11
2.1 Precautions for Use.................................................................................... 11
2.2 Placing the U•V6 unit ................................................................................. 11
2.3 Connecting the control unit....................................................................... 12
2.4 Connecting the Detectors.......................................................................... 13
General ..................................................................................................... 13
Two-Wire Current-Loop Detectors.......................................................... 13
Three-Wire Current-Loop Detectors ....................................................... 14
2.5 Connecting the Relays............................................................................... 14
2.6 Connecting the Siren ................................................................................. 14
2.7 Connecting the Analogue Output ............................................................. 15
2.8 Connecting the Power Supply................................................................... 16
2.9 Connecting a Battery ................................................................................. 16
2.10 First Start-Up ............................................................................................ 17
3 Configuration...................................................................................18
3.1 Unit-Configuration Principle...................................................................... 18
3.2 Addressing the Relays............................................................................... 18
Standard Factory Settings....................................................................... 19
3.3 Target Gases and Alarm Thresholds........................................................ 20
Target gases for car parks ...................................................................... 20
Target Gases for Laboratories................................................................ 22
4 User menus......................................................................................24
4.1 Main menu................................................................................................... 24

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
3 |65
Certified
ISO9001 • VCA
www.dalemans.com
4.2 Info Menu .................................................................................................... 24
History ...................................................................................................... 25
Calibration Age ........................................................................................ 25
Outputs test.............................................................................................. 25
Simulating a Detector.............................................................................. 26
Analogue Output Test.............................................................................. 27
Switching to the Battery.......................................................................... 27
Date and Time .......................................................................................... 28
Battery Age............................................................................................... 29
Firmware Version..................................................................................... 29
4.3 Configuration Information......................................................................... 29
Base standard configuration................................................................... 29
Measurement Channels........................................................................... 30
Target Gases............................................................................................ 31
Relay Configuration................................................................................. 33
Fault Menu................................................................................................ 34
External Alarm Menu ............................................................................... 36
Analogue Output...................................................................................... 38
Network Info............................................................................................. 40
4.4 Statuses Menu............................................................................................ 41
4.5 Test Menu.................................................................................................... 41
5 Service menu ...................................................................................42
5.1 Protected Access ....................................................................................... 42
5.1 Advanced System Tests............................................................................ 43
Outputs Tests........................................................................................... 43
Simulating a Detector.............................................................................. 44
Analogue Output Test.............................................................................. 45
Switching to the Battery.......................................................................... 45
5.2 Configuration Menu.................................................................................... 46
Configuring the Measurement Channels................................................ 46
Network Configuration ............................................................................ 48
5.3 Maintenance Management......................................................................... 49
Maintenance Interval................................................................................ 50
Renewing the Validity of the Calibration................................................ 51
Detecting the Detectors........................................................................... 51
6 Spare Parts and Options.................................................................53

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
4 |65
Certified
ISO9001 • VCA
www.dalemans.com
7 Target gases.....................................................................................54
8 Product specifications ....................................................................55
A. Event messages.............................................................................56
B. Error messages..............................................................................59
C. Predefined locations......................................................................61
D. Characters available for text edition.............................................62
E. User menu diagram........................................................................63
F. Service menu diagram ...................................................................65

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
5 |65
Certified
ISO9001 • VCA
www.dalemans.com
1GENERAL REMARKS
1.1 Responsibilities - guarantees
The installer is required to respect standards and installation provisions.
The installation must be carried out by qualified personnel.
All our equipment is tested and inspected in our workshops before shipping.
This manual must be read carefully by anyone who is or will be responsible for the installation,
use and/or maintenance of this equipment. The guarantee offered by DALEMANS sa/nv will
be void if this equipment is not installed, used and maintained in compliance with these
instructions, warnings and limits of use.
By following these instructions, you guarantee the proper working of the equipment. Please
contact DALEMANS sa/nv for any information about the use or maintenance of this product.
ONLY use original DALEMANS sa/nv parts when performing maintenance on the equipment
Any repair or maintenance performed without respecting the procedures described in this
manual or without help from our after-sales service may prevent the equipment from working
correctly and, as a result, prevent guaranteeing the safety of the occupants of the building and
installations.
This equipment must be installed indoor, in a clean and dry area. Please use a screen (box)
DALEMANS
sa/nv for any additional information concerning the use of maintenance of this product.
DALEMANS sa/nv cannot be held responsible for any direct or indirect damage as well as
any direct and indirect monetary damages resulting from the failure to comply with these
guidelines.
DALEMANS sa/nv guarantees that this product is free from manufacturing defects and
agrees, at its sole discretion, to repair or replace any component which is defective or likely to
become so in the context of normal use during the warranty period specified in the general
terms of sale.
This guarantee does not cover elements such as batteries, fuses or any other component
provided by a third party.
Claims concerning the DALEMANS sa/nv product guarantee must be made in the guarantee
period specified above and within 5 calendar days of the discovery of the problem. Please
contact your DALEMANS sa/nv after-sales service to register your claim.
For any additional information, please refer to DALEMANS sa/nv generalconditions available
on request.

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
6 |65
Certified
ISO9001 • VCA
www.dalemans.com
1.2 Safety information
Symbol
Description
Protective ground terminal
Warning : risk of electric shock
Warning : refer to instruction manual
V6 control unit must be performed by qualified
personnel only. This qualified personnel is trained and accredited by DALEMANS sa/nv
During installation, refer to the standards in application.
Should the equipment be installed or used in a manner not specified by DALEMANS sa/nv,
the protection provided by the equipment may be impaired.
Modification, disassembling and total or partial destruction of this equipment may invalidate
the essential safety requirements of the whole plant.
For commissioning, please contact DALEMANS sa/nv to arrange an appointment.
Do not open the equipment without disconnecting mains power supply first

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
7 |65
Certified
ISO9001 • VCA
www.dalemans.com
1.3 Environment
The presence of the crossed-out wheelie bin logo on this product means
that you are required to respect the regulations in force concerning the
collection and recycling of waste electrical and electronic waste.
These provisions aim to preserve the natural resources used to produce this
product and to avoid the dispersal of substances which are potentially
harmful to the environment and human health.
Once this product reaches the end of its life, you MUST discard it by taking it to an approved
collection centre for the recycling of electrical and electronic equipment.
For more information on collection and recycling centres in your region, please contact your
local or regional administration.
1.4 Operating Principle
control unit for detecting toxic and/or inflammable gases in a commercial or
light industrial building (e.g. underground car parks), so that action can be taken. It allows
ventilation to be actively regulated, in particular. It has six detection inputs and up to four
alarm thresholds that can be configured independently for each input.
ctors. A gas detector is a
concentration of gas detected in the air.
The unit can send commands to one or more pieces of connected safety equipment when
the configured alarm thresholds are reached, e.g., to do the following:
▪control the ventilation (air blowers or extractors)
▪cause a siren to sound
▪cause a LED warning panel to light up
▪send a command to a CTM (Centralised Technical Management) system
also has internal fault management. Notification is sent via a relay signalling a
technical fault once any unusual use of the unit or a detector is detected. This function thus
ensures the reliability of the gas-detection system installed.
The status of t
viewed via the front panel of the unit at any point in time:

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
8 |65
Certified
ISO9001 • VCA
www.dalemans.com
▪
unit and shows a message explaining the status.
▪There is a set of colour LEDs.
▪There is a resettable buzzer which is triggered when the fault or alarm functions are
triggered.
1.5 Display interface
LED
LED indicators
» LED
The control unit is powered on
Battery LED
A battery is installed and correctly detected
« LED
There is at least one active fault condition.
» LED
The control unit is in a special state: gas
concentration measurements and alarm management
are still running; the alarm statuses are not updated.
This mode automatically exits after 15min without any
user interaction.
Clavier
Indicateurs LED
Afficheur rétro-éclairé

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
9 |65
Certified
ISO9001 • VCA
www.dalemans.com
Keypad
Allows the user to move around a menu or a selection
Allows the user to enter a sub-menu or launch the action associated with the menu
item selected
Allows the user to exit a sub-menu and return to the parent menu
ENTER
Allows the user to enter configuration mode, to confirm a change of settings or to
launch the action associated with the menu item selected
ESC
Allows the user to exit the configuration menus entirely or cancel the modification of the
settings in progress and return to the parent menu
RESET 1 x
Allows the user to turn off the buzzer and the siren output
RESET 2 x
Allows the user to do the following:
--reset an alarm, on the condition that the alarm is no longer active
--reset the faults for which there are still notifications, but which are no longer valid.
Display
messages on the display and the
colour of the backlighting.
Backlighting
Off
Green
Yellow
Red
Mode
Standby
No Alarm
Maintenance
Alarm
Message
Looped Display:
• No Alarm indicates that
there are no active alarms.
•Maintenance Date:
Next Maintenance
•Gas Concentration
Values for each of the
detectors.
Maintenance interval
exceeded:
Maintenance required .
Looped display of the alarms
that have been triggered. The
highest alarm level per type of
gas monitored is displayed.
The ID of the detector, the
alarm level and the gas
concentration measured is
shown for each of the alarms
displayed.
Technical Fault
Looped Display:
•List of faults and
technical faults
Only alarm messages are displayed when an alarm has been triggered, so any messages
associated with technical faults are no longer shown.

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
10 |65
Certified
ISO9001 • VCA
www.dalemans.com
a) Alarm mode (gas detected)
The unit enters into alarm mode when one or more alarm conditions have been met. The
screen turns RED, indicating the alarm level of the highest active alarm.
2.Detector 2
CO A3 155 ppm
The system can only exit alarm mode when all the alarm conditions have been reset.
b) Fault mode
The system can enter back-up mode when no alarm conditions have been met, but one or
several fault conditions have been.
2.Detector 2
Sensor error
c) Normal mode
Normal mode is reached if, and only if, the following conditions have been met:
▪No alarm conditions have been met
▪There are no faults
In such a case, the screen is GREEN and states 'No alarm':
No alarm
d) Standby mode
When there are no gas alarms or fault messages, the backlighting of the display enters into
standby mode after 60 seconds.
The system automatically exits standby mode when one of the following occurs:
▪keyboard action
▪detection of an alarm
▪appearance of a technical fault
Concentration & unité
Numéro de canal
Gaz cible
Localisation

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
11 |65
Certified
ISO9001 • VCA
www.dalemans.com
2INSTALLATION
2.1 Precautions for Use
For your safety, ensure that you are working on a device that is powered off before you do
anything!
cables can be inserted from the top, or in such a way that they can be inserted from the
bottom. However, in order to guarantee optimal sealing, it is recommended that you always
insert the cables from the bottom.
The housing of the device is IP65-certified and is therefore protected against the presence of
dust and water, provided that the installation instructions are followed.
The housing has a number of machined apertures. You will need to clear these machined
apertures with a flat screwdriver and hammer in order to insert the cable glands.
2.2 Placing the U•V6 unit
and a quick installation guide are supplied with the device. You can choose to fix the unit
using the housing or the four feet provided.
not have an explosive atmosphere and
must always be easy to access.
ohigh-voltage cables or power cables
otransmitters or coaxial cables
owelding stations or frequency regulators.

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
12 |65
Certified
ISO9001 • VCA
www.dalemans.com
DALEMANS representative for more information.
If you choose to fix the device without using the feet, attach the housing via the four holes
provided for this purpose to the four corners of the housing using a PZ2 screwdriver that is at
least 150 mm long.
See the quick installation guide provided for the different steps.
2.3 Connecting the control unit
The unit must be installed and the electrical connections hooked up by a qualified technician,
in accordance with the instructions given in this manual and on the diagram on the back of
It is recommended that you place the circuit breaker in the vicinity of the equipment.
Any installation must comply with the applicable local standards and regulations, in particular
as they pertain to the type of cable and the cross-sectional area of the wires to be used.
Ensure that the wires are securely connected to the connectors when connecting the
electrical terminals. Use a maximum torque of 0.60 Nm. To ensure electrical safety, the
wires that go from the cable glands on the housing to the terminals on the board must not be
longer than 70 mm.
It is recommended that you always use wires with crimp ends, in order to avoid any risk of
bad electrical contacts.
Exam
A circuit breaker (2 pins, 6A, 250V (AC)) must be placed on the live and the neutral. See
the wiring example below.

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
13 |65
Certified
ISO9001 • VCA
www.dalemans.com
2.4 Connecting the Detectors
General
following order:
Bornes
CA/IR/SC (3 fils)
Bornes
EC (2 fils)
Bornes central
+
+
V+
-
V-
S
-
S
EC: Électrochimique (2 fils) - IR: Infrarouge (3 fils) - SC: Semi-conducteur (3 fils) - CA: Catalytique (3 fils)
(see Paragraphs 2.4.2 and 2.4.3 below for more details)
Two-Wire Current-Loop Detectors
Use a dual-conductor flex cable with a cross-sectional area of between 0.75 and 1.5 mm2to
e.g., CO and NO2. See the diagram below).
300 m
long.
sources of
strong electromagnetic interference (transmitters, welding stations, switching relays, HF
transmitters, cable runs or computer networks, etc.), it is preferable to use shielded cables
to connect the detectors.
Never use two or more wires to increase the cross-sectional area of the wire. The cable
must be one length of cable (without connections) and properly connected to the
appropriate terminals. Use a maximum torque of 0.60 Nm.
Never place a detector cable next to a coaxial cable or a power cable and definitely never
in the same bundle or cable run.

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
14 |65
Certified
ISO9001 • VCA
www.dalemans.com
Three-Wire Current-Loop Detectors
Use a triple-conductor flex cable with a cross-sectional area of between 0.75 and 1.5 mm2to
e.g., LPG and
CNG. See the diagram below).
2.5 Connecting the Relays
addressed by the alarms and a technical-fault
relay. Different types of devices can be connected to these relays, such as air blowers or
extractors, sirens, LED warning signs or flashing lights, etc.
2.6 Connecting the Siren
Connect the Sand V
respectively). Respect the polarity to avoid damaging the siren.
The cables used to connect the siren must meet the same requirements as the detector
cable (see Connecting the Detectors).

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
15 |65
Certified
ISO9001 • VCA
www.dalemans.com
See the operation manual for the siren for instructions on how to connect the siren and
configure its tone.
2.7 Connecting the Analogue Output
Connect the Sand Vterminals on the analogue output to close the circuit. In current-loop
mode, the current leaves via terminal Sand returns via terminal V-.
The analogue output is configured as follows before leaving the factory:
▪In 4-20 mA current-loop mode
▪The output signal corresponds to the maximum value of the 6 input channels
▪The output gain ratio is 1:1 of the detectors' measurement range. A full-scale
measurement of the detector is shown as 20 mA on the analogue output signal
The user can change the unit from a current-loop signal mode to a voltage-signal mode by
toggling the RL Enable switch:
▪The ON position of the RL Enable switch transforms the output signal to a voltage

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
16 |65
Certified
ISO9001 • VCA
www.dalemans.com
▪The other position (the OFF position) of the RL Enable load-resistor switch leaves
the analogue output in current-loop mode.
2.8 Connecting the Power Supply
Connect the earth to terminal 3 and then the 230V mains voltage to terminals 1 and 2 on
the terminal; see the box below.
It must be possible to electrically isolate the unit for maintenance (protection via a
circuit breaker or double pole switch).
different devices must be connected to the
same circuit. Ensure that the power conductors are always attached together and kept
separate from the low-voltage conductors.
The power cables for the 230 V part must have a minimum cross-sectional area of 1.5 mm2.
2.9 Connecting a Battery
early wear and tear or damage of the battery connected.
A compatible battery
Please contact your DALEMANS representative to order a battery.
The operation of the current-loop mode might be impaired if the piece of equipment
The operation of the voltage mode might be impaired if the piece of equipment connected
has a low input impedance (less t
-I device. always be connected to the earth,
in accordance with the instructions given in this manual.

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
17 |65
Certified
ISO9001 • VCA
www.dalemans.com
Clear the front panel by unscrewing the four corners and disconnecting the flat connection
cable.
Then, place the battery in the housing provided for this purpose, before following the steps
below:
1. Connect the battery, respecting the polarity.
6 unit turns on.
The "Power Failure" message appears and the FaultLED lights up.
The Battery LED
This detection operation may take a few sections.
2. Reconnect the flat connection cable.
3.
4. The fault message disappears after a few seconds.
light up.
5. The fault message disappears after a few seconds.
light up.
2.10 First Start-Up
the terminals have been tightened
properly and the power voltage is in the acceptable operating range
The LEDs on the motherboard must light up when the device is powered on. It is important
that the user checks that these are all green and not flashing, except for the yellow LED on
the right-hand side of the motherboard, which should flash on and off at one-second
intervals.
Immediately after the unit is powered on, the LCD screen on the unit must turn blue and the
buzzer should sound a short, uninterrupted sound.
All activated detection channels -when the unit is turned on. The
measurements on a channel in a warm-up state are ignored. The warm-up state has a finite
duration which depends on the target gas configured.
The useful lifespan of a standard battery is estimated at four years. It is essential to replace
it after that. If a battery is defective, its charge is inhibited to avoid damaging it.
The unit may place itself in an unknown status during this operation. As a result, it
may be necessary to restart it correctly by pressing the Reset button on the motherboard.
Please contact DALEMANS to set up a commissioning appointment.

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
18 |65
Certified
ISO9001 • VCA
www.dalemans.com
3CONFIGURATION
to be configured. The user can access these menus, regardless of the s
unit, by pressing ENTERon the keyboard (if the display is in standby, the user should first
exit standby mode by pressing any key). Once in this mode, the display backlighting turns
blue.
ode after an idle period of 60 seconds (a
period in which no action is performed using the keyboard) and returns to the appropriate
mode: normal mode, if no faults or alarms have been signalled; fault mode, if a fault, but no
alarms, have been signalled; or alarm mode if an alarm has been signalled.
3.1 Unit-Configuration Principle
changed depending on the intended use.
All the channels are deactivated in the factory. A detector-detection script must be run, so
that all the channels to which detectors have been connected can be activated (see
Paragraph 5.4.3 Spotting the Detectors ).
A gas-
1. Detect the detectors and activate the input channels
2. Select the appropriate "standard config."
3. [Optional] Select the target gases and alarm thresholds for each input channel
4. [Optional] Adjust the settings specific to the installation.
3.2 Addressing the Relays
Relay addressing involves connecting the alarm conditions configured with actions to open
or close contacts on the alarm relays. Depending on the requirements of the installation, a
standard configuration can be selected and, as a result, the appropriate devices can be
activated in the event of a gas detection.
These standard configurations come as presets, which are stored in the unit's memory. A
technician, who has been trained and certified by Dalemans, can activate the most
appropriate standard configuration for the installation during commissioning.
These operations require the intervention of qualified technicians. Contact DALEMANS
for more information.
The PENxx standard configurations have been designed in accordance with EN 50545-1.
However, any subsequent modification may impact compliance with this standard. Please
contact your DALEMANS representative for more information.

DALEMANS sa/nv
Rue Jules Mélotte 27A
B-4350 Remicourt
+32 19 33 99 43
U•V6 Instruction Manual
19 |65
Certified
ISO9001 • VCA
www.dalemans.com
Standard Factory Settings
The PEN01 configuration
delivered:
PEN01
F
R1
R2
R3
R4
R5
FAULT
Channel #
Target gas
& range
Power
Failure
Channel 1
CO 300ppm
A1
A2
A3
-
Channel 2
CO 300ppm
A1
A2
A3
-
Channel 3
CO 300ppm
A1
A2
A3
-
Channel 4
CO 300ppm
A1
A2
A3
-
Channel 5
CO 300ppm
A1
A2
A3
-
Channel 6
CO 300ppm
A1
A2
A3
-
A1, A2 and A3 represent the respective alarm conditions for each input channel.
F, R1, R2, R3, R4 and R5 represent the fault relay and the five alarm relays that can be
addressed.
A symbol with an intersecting row and column indicates that the alarm condition in the
row, if met, will activate the relay in the corresponding column.
Configuration description:
▪The six detector input channels are configured to detect CO with a range of
measurement of 300 ppm
▪Single zone: identical alarm conditions all address the same relay
▪The five programmable relays are addressed as follows:
oRelays 1 & 2 are addressed to level-one alarms on the six input channels
oRelays 3 & 4 are addressed to level-two alarms on the six input channels
oRelay 5 is addressed to level-three alarms on the six input channels
▪The fault relay works in failsafe mode
▪The alarm relays are configured in non-failsafe mode
Table of contents