The compressor must only be used for its designed purpose(s) and wit-
hin its scope of application (refer to «operating limits»).
Consult Application guidelines and datasheet available from cc.danfoss.com
Under all circumstances, the EN378 (or other applicable local safety
regulation) requirements must be fulfilled.
The compressor is delivered under nitrogen gas pressure (between 0.3
and 0.7 bar) and hence cannot be connected as is; refer to the «assem-
bly» section for further details.
The compressor must be handled with caution in the vertical position (maxi-
mum offset from the vertical : 15°)
This Danfoss scroll compressor motor is protected by an external module protecting against phase loss/reversal, overheating and high current draw.
MPM
S
SSH
CCSS
LPS
UNIT
CONTROLLER
KM
Legend :
Fuses ............................................................................... F1
Compressor contactor...............................................KM
Control relay .................................................................KA
Safety lock out relay.................................................... KS
Optional short cycle timer (3 min) ..................... 180 s
External overload protection.................................... F2
Pump-down pressure switch .....................................LP
High pressure safety switch.......................................HP
Control device...............................................................TH
Liquid Line Solenoid valve..................................... LLSV
Discharge gas thermostat......................................DGT
Fused disconnect .........................................................Q1
Motor safety thermostat......................................... thM
Compressor motor ....................................................... M
Motor Protection Module ..................................... MPM
Thermistor chain.............................................................S
Safety pressure switch.............................................. LPS
Control circuit ..............................................................CC
Installation and servicing of the compressor by qualified personnel only. Follow
these instructions and sound refrigeration engineering practice relating to
installation, commissioning, maintenance and service.
A: Model number D: Supply voltage, Starting current & Maximum operating current
B: Serial number E: Housing service pressure
C: Refrigerant F: Factory charged lubricant
Map PCH065 R410A SH 5 K
Vapor Injection
Condensing temperature (°C)
Evaporating temperature (°C)
-40
5
10
15
20
25
30
35
40
45
50
55
60
65
70
-35 -30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35
Non Injection Area
1 – Introduction
This instruction pertain to the Danfoss PCH
scroll compressor used for heat pump systems.
It provides necessary information regarding
safety and proper usage of this product.
2 – Handling and storage
•Handle the compressor with care. Use the
dedicated handles in the packaging. Use the
compressor lifting lug and use appropriate and
safe lifting equipment.
•Store and transport the compressor in an
upright position.
•Store the compressor between Ts min and Ts
max values for LP side indicated on compressor
nameplate.
•Don’t expose the compressor and the packa-
ging to rain or corrosive atmosphere.
3 – Safety measures before assembly
Never use the compressor in a flammable
atmosphere.Check before assembly that the
compressor does not show any obvious signs of
deterioration that could have occurred during
inappropriate transportation, handling or sto-
rage
•The compressor ambient temperature shall
not exceed Ts max value for LP side indicated
on compressor nameplate during off-cycle.
•Mount the compressor on a horizontal flat
surface with less than 3° slope. The compres-
sor must be mounted with flexible grommet
(single applications). Refer to the PCH guide-
line to know the tightening torques that must
be applied.
•Verify that the power supply corresponds to
the compressor motor characteristics (see
nameplate).
•When installing PCH, use equipment specifi-
cally reserved for HFC refrigerants which was
never used for CFC or HCFC refrigerants.
•Use clean and dehydrated refrigeration-grade
copper tubes and silver alloy brazing material.
•Use clean and dehydrated system components.
•The piping connected to the compressor must be
flexible in 3 dimensions to dampen vibrations.
A
D
E
F
B
C

Danf
oss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order pro
vided that such alterations can be made without subsequential changes being necessary eady agreed.
All trademarks in this material are property of the respec
tive companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
2 | © Danfoss | DCS (CC) | 2018.04 8510287P01B - FRCC.PI.054.A2.02

Danfoss A/S
6430 Nordborg
Denmark
4 – Assembly
•Slowly release the nitrogen holding charge
through the schrader port.
•Remove the gaskets when brazing rotolock
connectors.
•Always use new gaskets for assembly.
•Connect the compressor to the system as soon
as possible to avoid oil contamination from am-
bient moisture.
•The PCH065 is dedicated for heat pump system
and has been designed to work with an econo-
mizer system. The compressor injection port
must be connected to the outlet of the interme-
diated exchanger. A solenoid must be installed
on the injection line: this injection port must be
closed when the compressor is stopped, while it
is running in the non-injection area of the appli-
cation map and during inversed cycle (cooling
mode and defrost).
•Avoid material entering into the system while
cutting tubes. Never drill holes where burrs can-
not be removed.
•Braze with great care using state-of-the-art tech-
nique and vent piping with nitrogen gas flow.
•Connect the required safety and control devices.
When the schrader port is used for this, remove
the internal valve. Do not exceed the maximum
tightening torque for rotolock connections:
Rotolock connections Tightening torque
1" rotolock 80 Nm
1 1/4" rotolock 90 Nm
1 3/4" rotolock 110 Nm
2 1/4" rotolock 130 Nm
5 – Leak detection
Never pressurize the circuit with oxygen or dry
air. This could cause fire or explosion.
•Do not use dye for leak detection.
•Perform a leak detection test on the complete
system.
•The test pressure must not exceed 1.1 x Ps value for
LP side and PS value for HP side indicated on com-
pressor nameplate
•When a leak is discovered, repair the leak and
repeat the leak detection.
6 – Vacuum dehydration
•Never use the compressor to evacuate the sys-
tem.
•Connect a vacuum pump to both the LP & HP
sides.
•Pull down the system under a vacuum of 500
µm Hg (0.67 mbar) absolute.
•Do not use a megohmmeter nor apply power to
the compressor while it is under vacuum as this
may cause internal damage.
7 – Electrical connections
•Switch off and isolate the main power supply.
See overleaf for wiring details.
•All electrical components must be selected as
per local standards and compressor require-
ments.
•Refer to page for electrical connections details.
•The Danfoss scroll compressor only works cor-
rectly in one rotation direction. Line phases L1,
L2, L3 must absolutely be connected to com-
pressor terminals T1, T2, T3 to avoid reverse
rotation.
•Use ø 4.8 mm (3/16») screws and ¼» ring termi-
nals for the power connection. Fasten with 3 Nm
torque.
•The compressor must be connected to earth
with the 5 mm earth terminal screw.
8 – Filling the system
•Keep the compressor switched off.
•Fill the refrigerant in liquid phase into the conden-
ser or liquid receiver. The charge must be as close
as possible to the nominal system charge to avoid
low pressure operation and excessive superheat.
Never let the pressure on LP side exceed the pres-
sure on HP side with more than 5 bar. Such pres-
sure difference could cause internal compressor
damage.
•Keep the refrigerant charge below the indicated
charge limits if possible. Above this limit; protect
the compressor against liquid flood-back with a
pump-down cycle or suction line accumulator.
•Never leave the filling cylinder connected to the
circuit.
Compressor models Refrigerant charge limit (kg)
PCH065 13.5
9 – Verification before commissioning
Use safety devices such as safety pressure
switch and mechanical relief valve in compliance
with both generally and locally applicable regu-
lations and safety standards. Ensure that they are
operational and properly set.
Check that the settings of high-pressure swit-
ches and relief valves don’t exceed the maximum
service pressure of any system component.
•A low-pressure switch is recommended to
avoid vacuum operation. Minimum setting for
PCH065 is 1.7 bar g.
•Verify that all electrical connections are properly
fastened and in compliance with local regula-
tions.
•When a crankcase heater is required, it must be
energized at least 12 hours before initial start-
up and start-up after prolonged shutdown for
belt type crankcase heaters (6 hours for surface
sump heaters).
10 – Start-up
•Never start the compressor when no refrigerant
is charged.
•All service valves must be in the open position.
•Balance the HP/LP pressure.
•Energize the compressor. It must start promptly.
If the compressor does not start, check wiring
conformity and voltage on terminals.
•Eventual reverse rotation can be detected by
following phenomena; the compressor doesn’t
build up pressure, it has abnormally high sound
level and abnormally low power consumption.
In such case, shut down the compressor imme-
diately and connect the phases to their proper
terminals. Danfoss scroll compressor PCH065 is
protected against reverse rotation by the exter-
nal electronic protection module. They will shut
off automatically.
11 – Check with running compressor
•Check current draw and voltage.
•Check suction superheat to reduce risk of slug-
ging.
•Observe the oil level in the sight glass for about
60 minutes to ensure proper oil return to the
compressor.
•Respect the operating limits.
•Check all tubes for abnormal vibration. Move-
ments in excess of 1.5 mm require corrective
measures such as tube brackets.
•When needed, additional refrigerant in liquid
phase may be added in the low-pressure side as
far as possible from the compressor. The compres-
sor must be operating during this process.
•A minimum injection superheat of 5 K must be
respected.
•Do not overcharge the system.
•Never release refrigerant to atmosphere.
•Before leaving the installation site, carry out a
general installation inspection regarding clean-
liness, noise and leak detection.
•Record type and amount of refrigerant charge
as well as operating conditions as a reference for
future inspections.
12 – Maintenance
Internal pressure and surface temperature
are dangerous and may cause permanent injury.
Maintenance operators and installers require
appropriate skills and tools. Tubing temperature
may exceed 100°C and can cause severe burns.
Ensure that periodic service inspections to
ensure system reliability and as required by local
regulations are performed.
To prevent system related compressor problems,
following periodic maintenance is recommended:
•Verify that safety devices are operational and
properly set.
•Ensure that the system is leak tight.
•Check the compressor current draw.
•Confirm that the system is operating in a way
consistent with previous maintenance records
and ambient conditions.
•Check that all electrical connections are still
adequately fastened.
•Keep the compressor clean and verify the ab-
sence of rust and oxidation on the compressor
shell, tubes and electrical connections.
13 - Warranty
Always transmit the model number and serial number
with any claim filed regarding this product.
The product warranty may be void in following cases:
•Absence of nameplate.
•External modifications; in particular, drilling,
welding, broken feet and shock marks.
•Compressor opened or returned unsealed.
•Rust, water or leak detection dye inside the
compressor.
•Use of a refrigerant or lubricant not approved by
Danfoss.
•Any deviation from recommended instructions
pertaining to installation, application or mainte-
nance.
•Use in mobile applications.
•Use in explosive atmospheric environment.
•No model number or serial number transmitted
with the warranty claim. The compressor is not
designed to withstand natural disasters such
as earthquakes, cyclones, floods…. or extreme
events such as fires, terrorist attacks, military
bombardments, or explosions of any kind.
Danfoss Commercial Compressor is not liable
for any malfunction of its product resulting from
such events
14 – Disposal
Danfoss recommends that compressors
and compressor oil should be recycled
by a suitable company at its site.

Other Danfoss Air Compressor manuals

Danfoss BOCK HGX22e/125-4 A User manual

Danfoss

Danfoss BOCK HGX22e/125-4 A User manual

Danfoss SH485 Instruction Manual

Danfoss

Danfoss SH485 Instruction Manual

Danfoss VZL028 User manual

Danfoss

Danfoss VZL028 User manual

Danfoss VCH115 User guide

Danfoss

Danfoss VCH115 User guide

Danfoss VZH028 User manual

Danfoss

Danfoss VZH028 User manual

Danfoss VLZ065 Instruction Manual

Danfoss

Danfoss VLZ065 Instruction Manual

Danfoss CXH User manual

Danfoss

Danfoss CXH User manual

Danfoss Performer SM Series User manual

Danfoss

Danfoss Performer SM Series User manual

Danfoss VLZ065 User manual

Danfoss

Danfoss VLZ065 User manual

Danfoss Maneurop NTZ Instruction Manual

Danfoss

Danfoss Maneurop NTZ Instruction Manual

Danfoss MLZ/MLM090-116-130-160-200-240 Instruction Manual

Danfoss

Danfoss MLZ/MLM090-116-130-160-200-240 Instruction Manual

Danfoss MT User manual

Danfoss

Danfoss MT User manual

Danfoss PSH Series User manual

Danfoss

Danfoss PSH Series User manual

Danfoss Turbocor TTS Series User guide

Danfoss

Danfoss Turbocor TTS Series User guide

Danfoss Turbocor TT-300 User manual

Danfoss

Danfoss Turbocor TT-300 User manual

Danfoss CH290 User guide

Danfoss

Danfoss CH290 User guide

Danfoss MLZ Instruction Manual

Danfoss

Danfoss MLZ Instruction Manual

Danfoss H Series User manual

Danfoss

Danfoss H Series User manual

Danfoss MT User manual

Danfoss

Danfoss MT User manual

Danfoss MT User manual

Danfoss

Danfoss MT User manual

Danfoss VZH088-G single Instruction Manual

Danfoss

Danfoss VZH088-G single Instruction Manual

Danfoss LLZ User manual

Danfoss

Danfoss LLZ User manual

Danfoss MLZ Series User manual

Danfoss

Danfoss MLZ Series User manual

Danfoss Vitrifrigo BD50F User manual

Danfoss

Danfoss Vitrifrigo BD50F User manual

Popular Air Compressor manuals by other brands

JBL 7110 manual

JBL

JBL 7110 manual

Draper Stormforce DA50/207/BK instructions

Draper

Draper Stormforce DA50/207/BK instructions

SAEVO 40L owner's manual

SAEVO

SAEVO 40L owner's manual

EINHELL TC-AC 400/50/8 Original operating instructions

EINHELL

EINHELL TC-AC 400/50/8 Original operating instructions

Porter-Cable PCFP02040 instruction manual

Porter-Cable

Porter-Cable PCFP02040 instruction manual

WORKZONE TITANIUM PREMIUM HC520 user manual

WORKZONE TITANIUM

WORKZONE TITANIUM PREMIUM HC520 user manual

HOTO QWCQB001 user manual

HOTO

HOTO QWCQB001 user manual

IKH XT0901 Original instruction manual

IKH

IKH XT0901 Original instruction manual

Porter-Cable CF1540 instruction manual

Porter-Cable

Porter-Cable CF1540 instruction manual

Campbell Hausfeld HU3501 operating instructions

Campbell Hausfeld

Campbell Hausfeld HU3501 operating instructions

Graco 25A931 Operation manual

Graco

Graco 25A931 Operation manual

Gardner Denver AirSmart VS135A Operating and service manual

Gardner Denver

Gardner Denver AirSmart VS135A Operating and service manual

Black Diamond Equipment C151BD owner's manual

Black Diamond Equipment

Black Diamond Equipment C151BD owner's manual

Sullair SRL-7.5MB user manual

Sullair

Sullair SRL-7.5MB user manual

MARMON Campbell Hausfeld VX4002 Operating instructions and parts manual

MARMON

MARMON Campbell Hausfeld VX4002 Operating instructions and parts manual

Bitzer ESH7 Series operating instructions

Bitzer

Bitzer ESH7 Series operating instructions

Craftsman 921.153620 owner's manual

Craftsman

Craftsman 921.153620 owner's manual

Sakura SS3604 user guide

Sakura

Sakura SS3604 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.