4 Manual RS8EL402 © Danfoss 03-2010 AK-PC 420
Capacity regulation
Three-way valve + step-by-step coupling of fans (applications 1 and 3)
Capacity regulation takes place via a P or PI regulation, which con-
trols the three-way valve and subsequent step-by-step coupling of
the fans.
First of all regulation takes place on the three-way valve via the an-
alogue output. The output can be set at 0-10 V or 10-0 V, depend-
ing on which valve function is desired. Only when the three-way
valve is fully open do the fans start up.
The capacity of the three-way valve is 50% of the total capacity.
The P/PI controller has separate regulation settings (proportional
band and integration time) for the three-way valve and the fans
respectively.
Capacity overlap – start of fans
As mentioned above, the three-way valve comprises a xed 50% of
the total capacity. In some systems it may be necessary to start the
fans slightly before (or slightly after) the three-way valve has been
fully opened. An overlap is created here between the three-way
valve and the start of the fans. This is done by changing the setting
“FanCap OFF%” from 50% to, for example, 40% (the setting denes
the capacity at which the last fan stops). In this case the fans are
started before the three-way valve is fully open.
Three-way valve + speed control of fans (applications 2 and 4)
Capacity regulation takes place via a P or PI regulator, which
controls the three-way valve and subsequent speed control of
the fans. Here the analogue output signal is divided between the
three-way valve and the frequency converter (50% of the ana-
logue output signal is always used for the three-way valve), i.e.
if the analogue output signal is set at 0-10V, 0-5 V is used for the
three-way valve.
The frequency converter/fans are controlled via the relay output
for fan 1 on the basis of the setting“FanCapOFF%”.
In the event of falling capacity, the relay output for fan 1 will be
disabled when the actual capacity has fallen to “FanCap OFF%”.
To achieve hysteresis when starting/stopping the frequency con-
verter, the relay output for fan 1 will, when capacity is increasing,
be enabled when the desired capacity is “FanCap OFF%” + “10%
fan capacity”.
If “FanCapOFF%” is set at above or below 50%, the frequency
converter can be started after or before the three-way valve is fully
opened.
The P/PI controller has separate regulation settings (proportional
band and integration time) for the three-way valve and the fans
respectively.
Fan control only (applications 5 and 6)
Capacity regulation takes place via a P or PI regulator, which con-
trols the fans either with step-by-step coupling or speed control.
The analogue output and a frequency converter are used for
speed control. The relay output for fan 1 is used to start/stop the
frequency converter.
In the event of falling capacity, the relay output for fan 1 will be
disabled when the actual capacity has fallen to “FanCap OFF%”.
To achieve hysteresis when starting/stopping the frequency con-
verter, the relay will become enabled when the desired capacity
is the fan capacity above “FanCap OFF%” (The 10% fan capacity
will correspond to hysteresis of 1 V in the analogue output signal,
when the signal is 0-10 V.)
The P/PI controller only uses regulation settings (proportional
band and integration time) for the fans.