14 Manual RS8EL402 © Danfoss 03-2010 AK-PC 420
Menu survey
SW: 1.2x
To be continued
Conguration parameters can only be set when the regulation is
stopped, r12=0.
Function Para-
meter
Min. Max. Fac.
sett.
Normal display
A display of the regulated temperature
can be seen in EKA 164. (display with
buttons)
- °C
Shows Pc in EKA 163 - °C
Reference
Select unit (0=bar and °C, 1=Psig and
°F) r05 0 1 0
Start/Stop of regulation r12 OFF ON OFF
Set regulation setpoint r28 -25°C 75°C 30°C
Shows the total reference r29 °C
Limitation: reference max. value r30 -99.9°C 99.9°C 55.0°C
Limitation: reference min. value r31 -99.9°C 99.9°C -99.9°C
Correction of signal from Pc-sensor r32 -50 K 50 K 0.0
Pc reference variation.1 and 2 are PI-
regulation
1: Fixed reference.“r28”is used
2: Variable reference. Outdoor tempera-
ture (Sc3) included in the reference
3: As 1, but with P-regulation (Xp-band)
4: As 2, but with P-regulation (Xp-band)
5: As 1, but with min.-reference acc. to
outdoor temperature
6: As 3, but with min.-reference acc. to
outdoor temperature
r33 1 6 1
The mean temperature dierence
across the condenser at the lowest
relevant capacity (min tm K)
r56 3.0 50.0 8.0
This is where you can see the actual
temperature that is part of the regula-
tion.
r58 °C
Set point settings for heat recovery r64 -25°C 75°C 35°C
Average period for reference changes. r65 0.1 K/
min.
50
K/min.
10
K/min.
Displacement of reference at external
signal = 10 V r68 -50 K 50 K 0.0
Displacement of reference at external
signal = 0 V r69 -50 K 50 K 0.0
Correction of signal from S7-sensor r72 -50 K 50 K 0.0
Correction of signal from S8-sensor r73 -50 K 50 K 0.0
Capacity
Denition of fan relay
1-6: Total number of fan relays in
sequential operation.
7-10: Not used
11- 16: Total number of fan relays in
cyclic operation.
c29 0/OFF 16 0
Denition of the analoge output volt-
age 0-10 V
1: 0-10 V, linear
2: 10-0 V, linear
3: 0-10 V, unlinear
4: 10-0 V, unlinear
c34 1 4 1
Proportional band Xp for (P= 100/Xp)
valve regulation n04 0.2 K 40.0 K 10.0 K
I: Integration time Tn for valve regula-
tion n05 30 s 600 s 120
Cutin condenser capacity with manual
control. See also“n53” n52 0 % 100 % 0
Manual control of condenser capacity
(when ON, the value in “n52”will be
used)
n53 OFF ON OFF
Proportional band Xp for (P= 100/Xp)
fan regulation n60 0.2 K 40.0 K 20.0 K
I: Integration time Tn for fan regulation n61 30 s 600 s 240
Denition of where the rst fan is
connected. Set as a % of the total
refrigeration capacity. Ex. 50%, if a
three-way valve is also used.
n62 0 % 70 % 50 %
Alarm
Delay time for a DI1 alarm A27 0 min.
(-1=OFF)
999
min. OFF
Delay time for a DI2 alarm A28 0 min.
(-1=OFF)
999
min. OFF
Delay time for a DI3 alarm A29 0 min.
(-1=OFF)
999
min. OFF
Upper alarm and safety limit for Pc A30 -10 °C 200°C 60.0°C
Pump alarm delay A63 1 s 600 s 15 s
Miscellaneous
Controllers address o03* 1 990
On/o switch (service-pin message) o04* - -
Access code o05 1
(0=OFF) 100 OFF
Used sensor type for Sc3, S7 and S8
0=Pt1000, 1=PTC1000 o06 0 1 0
Set supply voltage frequency o12 50 Hz 60 H 0
Manual control of outputs:
0: No override
1-10: 1 will cut in relay 1, 2 relay 2, etc.
11-18: Gives voltage signal on the
analog output. (11 gives 1.25 V, and so
on in steps of 1.25 V
o18 0 18 0
Use of DI4-input
0=not used. 1=Safety signal from high
pressure pressostat
o22 0 1 0
Setting of refrigerant
1=R12. 2=R22. 3=R134a. 4=R502.
5=R717. 6=R13. 7=R13b1. 8=R23.
9=R500. 10=R503. 11=R114.
12=R142b. 13=User dened. 14=R32.
15=R227. 16=R401A. 17=R507.
18=R402A. 19=R404A. 20=R407C.
21=R407A. 22=R407B. 23=R410A.
24=R170. 25=R290. 26=R600.
27=R600a. 28=R744. 29=R1270.
30=R417A. 31=R422A. 32=R413A.
33=R422D. 34=R427A. 35=R438A.
o30 0 35 0
Pc pressure transmitter’s working range
- min. value o47 -1 bar 0 bar -1.0
Pc pressure transmitter’s working range
- max. value o48 1 bar 200
bar 34.0
Operating hours of relay 7 (value time
1000) o52 0.0 h 99.9 h 0.0
Operating hours of relay 8 (value time
1000) o53 0.0 h 99.9 h 0.0
* this setting is only possible if data communication module is mounted in
the controller