1.3 Voltage Ratings
FC 102/FC 202 FC 302
[V] [HP] [HP: NO] [HP: HO]
208-230 1.5-5 — 1/4-5
460-480 1.5-10 — 1/2-10
575-600 1.5-10 — 1-10
Table 1.7 Frames A1 - A3
FC 102/FC 202 FC 302
[V] [HP] [HP: NO] [HP: HO]
208-230 7.5-15 10-15 7.5-10
460-480 15-25 20-25 15-20
575-600 15-25 15-25 15-20
Table 1.8 Frame B1
FC 102/FC 202 FC 302
[V] [HP] [HP: NO] [HP: HO]
208-230 20 20 15
460-480 30-40 30-40 25-30
575-600 30-40 30-40 25-30
Table 1.9 Frame B2
FC 102/FC 202 FC 302
[V] [HP] [HP: NO] [HP: HO]
208-230 25-30 25-30 20-25
460-480 50-75 50-75 40-60
575-600 50-75 50-75 40-60
Table 1.10 Frame C1
FC 102/FC 202 FC 302
[V] [HP] [HP: NO] [HP: HO]
208-230 40-60 40-60 30-50
460-480 100-125 100-125 75-100
575-600 100-125 100-125 75-100
Table 1.11 Frame C2
1.4 Fuse Replacement Table
Drive Rating FC 102/FC 202 FC 302
[HP] [kW] 208-230 V 460-480 V 575-600 V 208-230 V 460-480 V 575-600 V
0.5 0.37 n/a n/a n/a LP-CC-5 5 A, 600 V,
Class CC
LP-CC-6 6 A,
600 V, Class CC
n/a
0.75 0.55 n/a n/a n/a LP-CC-10 10 A,
600 V, Class CC
LP-CC-6 6 A,
600 V, Class CC
n/a
1 0.75 n/a n/a n/a LP-CC-10 10 A,
600 V, Class CC
LP-CC-6 6 A,
600 V, Class CC
LP-CC-5 5 A, 600 V,
Class CC
1.5 1.1 LP-CC-10 10 A,
600 V, Class CC
LP-CC-6 6 A, 600 V,
Class CC
LP-CC-5 5 A, 600 V,
Class CC
LP-CC-10 10 A,
600 V, Class CC
LP-CC-6 6 A,
600 V, Class CC
LP-CC-5 5 A, 600 V,
Class CC
2 1.5 LP-CC-15 15 A,
600 V, Class CC
LP-CC-10 10 A,
600 V, Class CC
LP-CC-10 10 A,
600 V, Class CC
LP-CC-15 15 A,
600 V, Class CC
LP-CC-10 10 A,
600 V, Class CC
LP-CC-10 10 A,
600 V, Class CC
3 2.2 LP-CC-20 20 A,
600 V, Class CC
LP-CC-10 10 A,
600 V, Class CC
LP-CC-10 10 A,
600 V, Class CC
LP-CC-20 20 A,
600 V, Class CC
LP-CC-10 10 A,
600 V, Class CC
LP-CC-10 10 A,
600 V, Class CC
4 3 LP-CC-25 25 A,
600 V, Class CC
LP-CC-15 15 A,
600 V, Class CC
LP-CC-15 15 A,
600 V, Class CC
LP-CC-25 25 A,
600 V, Class CC
LP-CC-15 15 A,
600 V, Class CC
LP-CC-15 15 A,
600 V, Class CC
5 3.7/4 LP-CC-30 30 A,
600 V, Class CC
LP-CC-20 20 A,
600 V, Class CC
LP-CC-20 20 A,
600 V, Class CC
LP-CC-30 30 A,
600 V, Class CC
LP-CC-20 20 A,
600 V, Class CC
LP-CC-20 20 A,
600 V, Class CC
7.5 5.5 JJN-50 50 A, 300 V,
Class T
LP-CC-25 25 A,
600 V, Class CC
LP-CC-25 25 A,
600 V, Class CC
LP-CC-50 50 A,
600 V, Class CC
LP-CC-25 25 A,
600 V, Class CC
LP-CC-25 25 A,
600 V, Class CC
10 7.5 JJN-50 50 A, 300 V,
Class T
LP-CC-30 30 A,
600 V, Class CC
LP-CC-30 30 A,
600 V, Class CC
JJN-60 60 A, 300 V,
Class T
LP-CC-30 30 A,
600 V, Class CC
LP-CC-30 30 A,
600 V, Class CC
15 11 JJN-60 60 A, 300 V,
Class T
JJS-40 40 A, 600 V,
Class T
JJS-35 35 A, 600 V,
Class T
JJN-80 80 A, 300 V,
Class T
JJS-40 40 A, 600 V,
Class T
JJS-35 35 A, 600 V,
Class T
20 15 JJN-80 80 A, 300 V,
Class T
JJS-40 40 A, 600 V,
Class T
JJS-35 35 A, 600 V,
Class T
JJN-125 125 A,
300 V, Class T
JJS-50 50 A, 600 V,
Class T
JJS-45 45 A, 600 V,
Class T
25 18.5 JJN-125 125 A,
300 V, Class T
JJS-50 50 A, 600 V,
Class T
JJS-45 45 A, 600 V,
Class T
JJN-125 125 A,
300 V, Class T
JJS-60 60 A, 600 V,
Class T
JJS-50 50 A, 600 V,
Class T
Installation Instructions VLT® FC Series Internal Fuse Replacement
4
MI92D102 - VLT®is a registered Danfoss trademark