Danfoss REPI Series User manual

This manual suits for next models

4

Other Danfoss Thermostat manuals

Danfoss Icon Master Controller 24 V User manual

Danfoss

Danfoss Icon Master Controller 24 V User manual

Danfoss ECL Comfort 210 User manual

Danfoss

Danfoss ECL Comfort 210 User manual

Danfoss living connect User manual

Danfoss

Danfoss living connect User manual

Danfoss SET3M Assembly Instructions

Danfoss

Danfoss SET3M Assembly Instructions

Danfoss HP75-1 User manual

Danfoss

Danfoss HP75-1 User manual

Danfoss Icon Master User manual

Danfoss

Danfoss Icon Master User manual

Danfoss ECtemp 530 User manual

Danfoss

Danfoss ECtemp 530 User manual

Danfoss ECtemp 610 User manual

Danfoss

Danfoss ECtemp 610 User manual

Danfoss Eco User manual

Danfoss

Danfoss Eco User manual

Danfoss TP7000 Series User manual

Danfoss

Danfoss TP7000 Series User manual

Danfoss Link DBR User manual

Danfoss

Danfoss Link DBR User manual

Danfoss DEVIreg 330 User manual

Danfoss

Danfoss DEVIreg 330 User manual

Danfoss TP9000 Guide

Danfoss

Danfoss TP9000 Guide

Danfoss 088U0212 User manual

Danfoss

Danfoss 088U0212 User manual

Danfoss TPOne-M User manual

Danfoss

Danfoss TPOne-M User manual

Danfoss HCS6101-3 User instructions

Danfoss

Danfoss HCS6101-3 User instructions

Danfoss Link FT User manual

Danfoss

Danfoss Link FT User manual

Danfoss 140F1143 User manual

Danfoss

Danfoss 140F1143 User manual

Danfoss TRONE-RF User manual

Danfoss

Danfoss TRONE-RF User manual

Danfoss FH-CWP User manual

Danfoss

Danfoss FH-CWP User manual

Danfoss RT1-RF User manual

Danfoss

Danfoss RT1-RF User manual

Danfoss living connect Z User manual

Danfoss

Danfoss living connect Z User manual

Danfoss RTW-RA User manual

Danfoss

Danfoss RTW-RA User manual

Danfoss RET 230 User manual

Danfoss

Danfoss RET 230 User manual

Popular Thermostat manuals by other brands

EWELLY EW-181 manual

EWELLY

EWELLY EW-181 manual

Prolon T1100 Hardware guide

Prolon

Prolon T1100 Hardware guide

Computherm Q20 operating instructions

Computherm

Computherm Q20 operating instructions

Heatmiser neoStat user manual

Heatmiser

Heatmiser neoStat user manual

Mars HEAT CONTROLLER IR Wireless Thermostat user manual

Mars

Mars HEAT CONTROLLER IR Wireless Thermostat user manual

Saswell SAS920XWHB-7-S-RF User manual and warranty card

Saswell

Saswell SAS920XWHB-7-S-RF User manual and warranty card

Aircalo TFP1-ET85P2 operating manual

Aircalo

Aircalo TFP1-ET85P2 operating manual

Honeywell CM721 user manual

Honeywell

Honeywell CM721 user manual

Carrier DEBONAIR 33CS Installation and operating instructions

Carrier

Carrier DEBONAIR 33CS Installation and operating instructions

Lennox iHarmony Zone Thermostat Installation and setup guide

Lennox

Lennox iHarmony Zone Thermostat Installation and setup guide

Gemtech GT7000 Operation

Gemtech

Gemtech GT7000 Operation

Rollei Smartes 45000 manual

Rollei

Rollei Smartes 45000 manual

Sinope TH1300RF user guide

Sinope

Sinope TH1300RF user guide

Honeywell RLV4305 owner's guide

Honeywell

Honeywell RLV4305 owner's guide

Honeywell Prestige 2.0 THX9421 manual

Honeywell

Honeywell Prestige 2.0 THX9421 manual

NuTone NTBZ48 Installation & operation guide

NuTone

NuTone NTBZ48 Installation & operation guide

Stelpro MAESTRO ASMT402AD user guide

Stelpro

Stelpro MAESTRO ASMT402AD user guide

Honeywell T6811 quick guide

Honeywell

Honeywell T6811 quick guide

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2026 Manuals.Online. All Rights Reserved.

© Danfoss | 2022.05 AI097986404620en-010102 | 1
REPI Series Digital Thermostat Manual
Data sheet
Description REPI series thermostats are used to control
room temperature in industrial, commercial and
residential environment via controlling electric
modulating valve with 0-10VDC (4-20mA) control
signal or floating control as well as damper
actuator of VAV system.
Electronic control technology is adopted, with
green backlit LCD display of: working mode
(cooling “ ”, heating “ ”, ventilating “ ”, auto
“ ” ); fan speed (low “ ”, med “ ”, high “ ”, auto
“”); room temperature; setting temperature
etc. push button: On/Off “ ”; mode changeover
“ ”; fan speed choose “ ” and temperature
adjustment “ ” and “ ”.
Shell: PC + ABS retardant material.
Function
Detect and Display room temperature
Room temperature setting
Fahrenheit or Celsius degree display
Timing sleep
Control On/Off of cooling and heating
equipment
Selectable single speed or three speed fan
control
Order Guide
Model Output signal Fan
(Single/3-speed)
RS485
Network
Input
Control
Remote
Sensor
Floating Modulation
REPI-2 Cooling/Heating   
REPI-2N Cooling/Heating    
REPI-4 Cooling/Heating   
REPI-4N Cooling/Heating    
Fan: thermostat with fan functions, can be selected with single speed fan or three speed fan by setting parameter.
Remote Control: input signal can be selected by setting parameter.
Specification
Set temperature range: 0 - 99.5 °C adjustable
Accuracy displayed: 0.1 °C
Accuracy: ±0.5 °C
Rated Power: < 1 W
Sensor type: NTC
Display: LCD
Power: AC 24V±10%, 50Hz/60Hz
Output signal: AC 24V×2 (0.5A resistive) ,
0 - 10VDC(5mA) / 4 - 20mA (600Ω)
Relay load: 2A (resistive load), 1A (inductive
load)
Input signal: dry contact (NO)
Dimensions: 86×86×23mm (W×H×D)
Fixing screw width : 60mm (Standard)
2 | AI097986404620en-010102 © Danfoss | 2022.05
Data sheet REPI Series Digital Thermostat Manual
Operations
On/Off: Press “ ” buttons to turn on;
press “ ” again to turn off.
Setpoint: With thermostat on, press “ ” to
reduce the setpoint, press “ ” to increase the
setpoint, the setpoint step is
0.5 °C, the setpoint will be confirmed
automatically after 5 seconds, and then return to
dispay status, press “ ” or “ ” to check setpoint.
Mode: With thermostat on, press “ ” to
change the working mode – Cooling “ ”,
Heating “ ”, Vent “ “, Auto “ ”
( Auto is available REPI-4/ REPI-4N).
Fan Speed: With thermostat on, press “ ” to
select the desired speed – low speed “ ”, Med
speed “ ”, High speed “ ”, auto “ ”. If single
speed fan available, there’s only med speed “ ”.
Under auto speed fan, the fan speed will be
changed automatically as below: in low speed
when room temperature
is 1 °C difference with setpoint;in med speed
when room temperature is 2 °C difference with
setpoint; in High speed when
room temperature is 3 °C difference with
setpoint.
Sleep: Thermostat will get into sleep function
after programming.The set Temperature should
to be.
To set: Press “ ” button for 3 seconds till
“ ” display, there’s a number of count down
in the center of LCD, Use “ ” or “ ” to adjust
the desired sleep time: the max. = 48 hours;
thermostat will return to the working status after
5 seconds, “ ” is flashing to start counting down.
The setpoint should be replaced by the sleep
setpoint.
To quit: When thermostat get into Sleep
function, “ ” will flash, press “ ” or “ ” to quit.
Keypad lock: press “ ” and “ ” for 10
seconds till to “ ” display to activate, under this
function, any keypad is locked.
Press “ ” and “ ” for 10 seconds till “ ”
disappear to quit the function.
Set Parameters: With thermostat off, press
“ ” for 10 seconds to enter menu to set the
parameters.
Parameter table
Parameter Description Default Range Step
1 Power on status (0: Off; 1: On; 2: Hold) 2 0 - 2
2Fan speed (0: Single Speed; 1: Three Speed) 1 0 - 1
3 Fan mode (DA; DB) 0
4 Sensor selection (0: Internal; 1: Remote) 1 0 - 1
5 Temperature format (0: Celsius; 1: Fahrenheit) 0 0 - 1 0.1
6Temperature calibration 0 -20.0 - +20.0 0.1
7Minimum setpoint 5 °C/41 °F 0 - 99.5 0.5
8Maximum setpoint 35 °C/96 0 - 99.5 0.5
9 Dead band (REPI-4) 2 0 - 10 0.5
10 Heating & Auto sleep setpoint 7 °C/45 °F 0 - 99.5 0.5
11 Cooling sleep setpoint 28 °C/82 0 - 99.5 0.5
12 Comms# (REPI-2N;REPI-4N) 1 1 - 32 1
13
Input Signal Mode 0: Invalid
1: Changeover(REPI-2)
2: thermostat will be sleep without input signal
3: thermostat will be Off without input signal
0 0 - 3
14 Heating reset time 90 sec. 10 - 300 sec. 10 sec.
15 Cooling reset time 90 sec. 10 - 300 sec. 10 sec.
16 Ports mode (0: Modulation & Floating; 1: On/Off) 0 0 - 1
17 Valve status as turn off (0: Close; 1:Hold; 2: Open ) 0 0 - 2
18 Port1 Modulation direction (0:10V Open; 1:10V Close) 0 0 - 1
19 Port1 Modulation minimum signal 0Bit 0-128Bit(5V/10mA) 0.04V/Bit(0.08mA/Bit)
20 Port1 Modulation proportional 2 1 - 20 0.5
21 Port2 Modulation direction (0:10V Open; 1:10V Close) 0 0 - 1
22 Port2 Modulation minimum Signal 0 Bit 0-128Bit(5V/10mA) 0.04V/Bit(0.08mA/Bit)
23 Port2 Modulation proportional 2 1 - 20 0.5
24 Port1 Floating minimum time 1 sec. 1 - 9 sec. 1 sec.
25 Port1 Floating maximum time 30 sec. 10 - 300 sec. 10 sec.
26 Port1 Floating minimum time 1 sec. 1-9 sec. 1 sec.
27 Port1 Floating maximum time 30 sec. 10 - 300 sec. 10 sec.
28 Disable / Enable bypass PID control
(0: Disable; 1: Enable) 00-1
29 Override output value when bypass PID control
Display output value when enable PID control 0 - 255
AI097986404620en-010102 | 3© Danfoss | 2022.05
Data sheet REPI Series Digital Thermostat Manual
30 Override output value when bypass PID control
Display output value when enable PID control 0 - 255
31
Input signal management: 0: Input valid
1: Override Input: open
2: Override Input: close
00-2
32 Display room temperature or set-point
0: Room temperature 1: Set-Point 00-1
33
Configuration external sensor
0: B = 3950; 1: B = 3450; 2: B = 3900
3: User define (via network. default B = 3950)
00-3
34-38 N/A
39 Start temperature of Low temperature protection 5 °C/42 °F 0-15 °C/42-62 °F 1 °C/2 °F
40 Stop temperature of Low temperature protection 7 °C/46 °F 2-17 °C/46-66 °F 1 °C/2 °F
It will confirm itself 20 seconds later after setting and return to Off state.
Parameter table (continuous)
Specification
There is a 5 poles switch on PCB. The meaning is below:
Location ON OFF
1 120 ohm Resistance between AB wires No Resistance between AB wires
2 Port 1 Modulation 0 - 20mA Off
3 Port 1 Modulation 0 - 10VDC Off
4 Port 2 Modulation 0 - 20mA Off
5 Port 3 Modulation 0 - 10VDC Off
40 Stop temperature of Low temperature protection 7 °C/46 °F
Mounting
1. Open the back panel with screwdriver. 2. Connect the wires follow the diagram.
3. Fix the base with screw. 4. Fix the front panel and finish the installation.
© Danfoss | DCS-SGDPT/SI | 2022.054 | AI097986404620en-010102
Data sheet REPI Series Digital Thermostat Manual
Wiring diagram
Note: Be sure to connect all the wires as per the wiring diagrams and keep it away from water, mud and other material so as to
prevent the unit being spoiled!