INSTALLTION:
1. Remove the diffuser
2. Open the PCB by pushing the latch
3. Pull power cord through gasket and seal it to prevent water ingress
4. Fix the base to surface with screws provided
5. Connect supply cable to the terminal block
6. Close PCB
7. Replace the diffuser
MAINTENANCE:
The supply must be isolated before opening or accessing the luminaire. Product maintenance is critical to the product designed
performance. The product is to be maintained in accordance with the manufacturer’s instructions. For the latest product
maintenance guides please go to www.davislighting.com. Davis Lighting is not responsible for any product not maintained in
accordance with the recommended procedure or intervals. For recommended LAMP / LED maintenance guides, please refer to
the lamp installation guidelines supplied with the lamp product or the nominated lamp manufacturer’s website. Products
supplied with visors or covers must not be operate with a damaged visor or cover; it is recommended damaged visors or covers
be replaced by a competent person immediately.
Warning: Maximum loading of earth leakage and circuit protection device.
Note
•The maximum number of ballasts/drivers connected to earth leakage circuit protection device shall not be greater than 60
units for fixed output on MCB 16A or that as recommended by the protective device supplier/manufacturer whichever is the
smaller number.
•The maximum loading of automatic circuit breakers shall not be greater than those shown in the table supplied by the con-
trol gear manufacturer or that as recommended by the protective device supplied/manufacturer whichever is the smaller
number.