Dinel CLS-23 User manual

Read carefully the instructions published in this manual before the rst use of the sensor. Keep the manual
at a safe place. The manufacturer reserves the right to implement changes without prior notice
INSTRUCTION MANUAL
průmyslová elektronika
CapaCitive level sensors Cls 23
Microlectra bv.
www.microlectra.nl
Microlectra bv.
Augustapolder 12. 2992 SR Barendrecht. The Netherlands.
www.microlectra.nl [email protected]

CONTNT
. afety.........................................................................................................................................4
. acing transportation and storage ..........................................................................................4
. rief............................................................................................................................................5
. eatures of variants ...................................................................................................................5
. imensional drawings................................................................................................................6
. ounting recommendation.........................................................................................................7
. lectrical connection ..................................................................................................................9
. ensor setting ............................................................................................................................11
. tatus signaliation ....................................................................................................................11
. ccessories..............................................................................................................................12
. rder code ...............................................................................................................................13
. orrect specication eamples ................................................................................................13
. afety protections compatibility and eplosion proof .............................................................14
. se manipulation and maintenance........................................................................................14
. eneral conditions and warranty .............................................................................................14
. aring of labels......................................................................................................................15
. pecications...........................................................................................................................16

CLS23 Dinel
4
All operations described in this instruction manual have to be carried out by trained
personnel or by an accredited person only. Installation, commissioning, operation and
maintenance of the capacitive level sensors has to be carried out in accordance with this
instruction manual; the provisions of regulations in force regarding the installation of
electrical equipment have to be adhered to.
Improper use, installation or set-up of the sensor can lead to crashes in the application,
(overlling of the tank or damage of system components).
The manufacturer is not responsible for improper use, loss of work caused by either
direct or indirect damage, and for expenses incurred at the time of installation or during
the period of use of the level sensors.
1 .
saet
Used symbols
To ensure maimum safety of control processes we have dened the following safety instructions
and information. ach instruction is labeled with the appropriate pictogram.
A
This symbol informs you about particularly important instructions for installation and op-
eration of euipment or dangerous situations that may occur during the installation and
operation. ot observing these instructions may cause disturbance damage or destruction
of euipment or may cause inury.
I
This symbol indicates particularly important characteristics of the device.
N
This symbol indicates helpful additional information.
2 .
Packing,transPortation and storage
uipment is paced in a polythene bag and the whole consignment is placed in a card-
board bo. The cardboard bo is suitably lled to prevent mechanical damage during transport. et
the device paced up till the use to prevent possible damage.
Transport to the customer is realied by forwarding company. pon receipt please chec whether
the shipment is complete and corresponds to the etent of the order or whether during the transport
did not occurred the damage of the pacaging or the euipment. The device apparently damaged
during transport do not use and contact the manufacturer to resolve the situation.
f the device is transported further then only wrapped in the original pacaging and protected
against shocs and weather. tore the device in its original pacaging in a dry place sheltered from
the weather with humidity up to without the effects of chemically active substances. torage
temperature range is from to .
Sensor variants CLS–23_–20 a 21 with the electrodes longer than 100 mm are tted with
protective caps at the ends of the electrodes to prevent damage of the electrodes, box
rupture or injury of handling persons. Before commissioning, remove the caps.

5
Dinel CLS23
4 .
FeatUres oF variants
3 .
brieF
Capacitive level sensors (switches) CLS23 are designed for limit level detection of electrically
conductive and nonconductive uids in vessels reservoirs sumps pipes tans etc. The sensitiv-
ity of the sensor can be easily set by placing magnetic pen on sensitive spot.
The process coupling at the housing can be with metric thread . . pipe thread
or sealing thread T . utput performances transistor output with open
collector two wire electronic switch and R output.
There are net performances available N ormal for noneplosive areas E tended tem-
perature range for noneplosives areas Xi plosion proof intrinsically safe for eplosive ar-
eas NT igh temperature variant for noneplosives areas and XiT igh temperature variant
for eplosive areas.
CLS23_10 Uncoated short bar electrode for sensing of electrically nonconductive
liuids mineral and plant oilsresins etc.. ounting in horiontal position.
lectrode length mm.
CLS23_11 Insulated (coated) short bar electrode for nonaggressive electrically
conductive liuid sensing water water solutions. The insulation is made
from olypropylene.
lectrode length mm.
CLS23_12 Insulated (coated) short bar electrode for moderately aggressive electri
cally conductive liuid sensing chemicals water moderately aggressive
water solutions. igher temperature resistance than variant . The insula
tion is made from Tetrauoroethyleneeruororopylene.
lectrode length mm
CLS23_20 Partly insulated rod electrode for level detection of conductive and non
conductive liuids partially resistant to vapours water condensation in the
sensing area. The insulation is made from . ertical mounting horiontal
mounting from the side is possible for shorter electrodes up to mm
lectrode length from mm to m.
CLS23_21 Fully insulated rod electrode for universal use for level detection of con
ductive liuids water water solutions. Resistant to vapours water conden
sation in the sensing area and partially resistant to medium
spraying. The insulation is made from . ertical mounting horiontal
mounting from the side is possible for shorter electrodes up to mm.
lectrode length from mm to m.
CLS23_30 Uncoated removable rod electrode for level detection of conductive and
nonconductive liuids. ertical mounting horiontal mounting from the
side is possible for shorter electrodes up to mm.
lectrode length from mm to m.

CLS23 Dinel
6
5 .
dimensions drawings
CLS 23_ 10 CLS 23_ 11
CLS 23_ 30
Variant A
with cable outlet
Variant C with connector
(except CLS–23N, NT, Xi, XiT)
Magnetic pen MP8
Electrode type according
to specic variants
CLS 23_ 12 CLS 23_ 21
High temperature variants
(CLS–23_T–10; 12; 20; 21; 30)
CLS 23_ 20
Thread
Types of threads:
G 3/8''
M18x1,5
M20x1,5
1/214 NPT
LED *
* Variant E without LED state indicator

7
Dinel CLS23
6 .
moUnting recommendation
level sensors can be ed in a vertical horiontal or bevelled position into the shell of the
vessel the storage tan for the ation console in the pit by screwing into the welding ange using
a ing nut or T process connection.
asic application recommendations are mentioned below.
During assembly into the metal tank or the storage tank, it is not necessary to separately ground the
base of the level sensor. In the case of installation in concrete tanks or silos, it is recommended to
install a level sensor on the auxiliary metal construction (console, cap, etc.) and to then connect it
using a permanently dipped metal item or with steel reinforcement in the concrete (armouring).
In the case of the reading of an aggressive medium, we recommend that the producer be consulted.
If the sensors are tted with protective caps at the ends of the electrodes, remove the
caps before commissioning.
or top mounting vertical position it is necessary to eep the
distances from walls and from other sensors.
All vertically mounted sensors
E Electrode length in mm
E
k
c
d20
E
20k +≥=
40
E
40d +≥=
50
E
10c +≥=
20
E
40b +≥=
ounting in a bypass measuring tube. e recommend to
eep the tube diameter.
Applies to: CLS23_20, 21, 30
E Electrode length in mm
b
E
Fig. 1: Vertical mounting
Fig. 2: Bypass measuring tube

CLS23 Dinel
8
hen installing the sensor into the pipe it
is necessary to choose properly internal di-
ameter of the tube to ensure the inner walls
distances from the electrode to min. 5 mm.
n some cases sticy liuids liuids with low
dielectric constant is suitable to mount the
sensor in the knee tube.
Applies to: CLS23_10, 11, 12, 20, 21
hen installing the sensor in vertical position it can be used
for 2-state (LO-HI) level control between the min. and ma.
level. The position of the minimum and maimum level can be
changed by setting the sensor. luid changes reuire new set-
tings of the sensor
E Electrode length in mm
Applies to: CLS23_20, 30 (only for electrically non-conductive liquids)
Applies to: CLS23_21 (for electrically conductive liquids)
max.
min.
E
>5
>5
>5
ensor installation close to inlet hole in a narrow
nec or using improper welding ange may result in
malfunction of the sensor.
uitable welding anges can be found in the inel
assortment types see ccessories.
Applies to: All variants
WRONG CORRECT
WRONG
CORRECT
WRONG CORRECT
Fig. 3: Mounting in the pipe
Fig. 4: Two state regulation by hysteresis setting
Fig. 5: Long tting tubes in side wall mounting

9
Dinel CLS23
Applies to: CLS23_20, 21, 30 (for electrode length up to 300 mm)
or electrodes with a length over 300 mm for the detection in nonconductive containers sensors
in vertical position must be used the auiliary electrode e.g. conductivity probe. The auxiliary
electrode is connected to the sensor housing. Recommended length of the auiliary electrode
and the distance from the sensor are shown in the picture.
uitable types of auiliary electrode probes are e.g. inel with thread.
E
a
Ep
Electrical connection to
the sensor housing
Conductive probe
CNP18F30
Non-conductive tank
EEp >
E Electrode length in mm
30
E
30a +≈
Auxiliary electrode PDE18
7 .
electrical connection
or variant with the ed cable the individual colour cores of the connecting cable are con-
nected to the respective terminals of the related euipment supply unit.
or variant with the connector the cable can be supplied with the sensor length or m tted
with the pressed connector socet or dismountable connector socet without the cable see acces-
sories. n this case the cable is connected to the inside pins of the socet according to ig. .
The sensor with related euipment is interconnected by a suitable threecore variation or two
core and R variations cable. The length of the cable for the i and iT variations must be
selected with respect to the maimum permitted parameters usually inductance and capacity of
the outside intrinsically safe circuit of supply units . f using a dismountable
connector socet the outside diameter of the cable is a maimum of mm
Sensors CLS23 are equipped with protection against over-voltages and current overload. The capacity
loads and low resistance (bulb) are evaluated by sensors with output type P and S as short circuit.
Sensors with output type R are designed for interconnect to intrinsically safe supply units.
In case of strong ambient electromagnetic interference, paralleling of conductors with power distribu-
tion, or for the distribution to distance over 30 m, we recommend to use shielded cable.
Fig. 6: Auxiliary electrode in non-conductive tanks

CLS23 Dinel
10
CLS23___S_
ositive pole of power supply
is connected through a load relay to
brown blue wire or pin connector o.
negative pole is connected to white
wire or pin connector o. .
Typ CLS23___P_
ositive pole of power supply is
connected to brown wire or pin connec-
tor o. negative pole is connected to
blue wire or pin connector o. . oad
relay is connected to blac wire or pin
connector o. .
+U
0V
BN (1)
WH, BU (3)
+U
0V
BN (1)
BU (3)
BK (4)
Typ CLS23___R_
rown wire or pin connector o. is
connected to positive pole of n-
trinsically safe supply unit. lue wire or
pin.connector o. is connected to
negative pole of ntrinsically safe sup-
ply unit.
Electrical connection must be done in de-energized state! For switching supply sources,
it is necessary to check that the input is galvanically separated from the network side
and that they are tted with a lter suppressing the conforming interference (terminals
+ and – oscillate together towards the ground potential), or the interference is removed
in another manner.
Fig. 7: S type sensors connection
(2 - wire electronic switch)
Fig. 8: P (PNP) type sensors connection
Fig. 9: R (NAMUR) type sensors connection
Legend:
(1...3) – Terminals number for variants with connector
BN Brown
WH White
BK – Black
BU Blue
Fig. 10: Inside of the connector socket
Output (BK)
0V (BU)
+U (BN)

11
Dinel CLS23
8 .
sensor settings
The setting is done by placing magnetic pen to sensitive
spot located on the front of the sensor. hort time attaching
up to sec. of the magnetic pen to the sensitive spot
maes the sensor open. ong time attaching at least sec. of
the pen when the level is changed denes closed state of the
sensor. n this way is set the sensitivity for the measured medi-
um and switching modes normally open or normally
closed.
Sensitive spot
ACTOR AULT STTINS
Types CLS23_10; 20; 30 are set to detect mineral oil CLS23_11; 12; 21 to detect water.
The mode is set sensor closes when immersed.
hen the level is low the container is empty attach the magnetic pen
to the sensitive spot
for long time min. sec.. hen the level
is high the container is full attach the magnetic pen to the sensitive
spot
for short time ma. sec..
.
hen the level is low the container is empty attach the magnetic pen
to the sensitive spot for short time ma. sec.. hen the
level is high the container is full attach the magnetic pen to the
sensitive spot for long time min. sec..
mode O
normally open
mode C
normally close
9 .
statUs signalization
(only with LED state indicator variant)
ndicator unction
range
Continuous light ensor is closed switched
Dark ensor is open switched
Rapid ashing (period 0.2 s) nrecognied upper and lower limits or setting mistae
Slow ashing (period 0.8 s) hort circuit at sensor output
ensors of type CLS23E are produced without signaling indicator LED. or control of correct
settings it is necessary to interconnect the sensor to related evaluation unit or load.
n the case of the vertical mounting for detection of non-conductive liuids by sensors CLS23_20;
30 and for detection of conductive and non-conductive liuids by sensors CLS23_21 it neces-
sary to set limits and when electrode of the sensor is immersed to medium.

CLS23 Dinel
12
For security reasons, we recommend to set the mode O (normally open, sensor closes when immersed)
for minimum level detection. Any failure of the sensor or wiring is equally apparent as the emergency
level state. Analogously for the maximum level detection is recommended to set the mode C (normally
closed, sensor opens when immersed).
10 .
accessories
Standard
(included in the level sensors price)
pc of agnetic pen
pc of eal nonasbestos
Optional
(for extra charge)
tra cables over the standard length m
onrewirable connector plug
N and NT variants
Rewirable connector plug
N and NT variants
teel or tainless steel welding ange
tainless steal ing nut
ther seals T l etc.
Level state Mode Type of sensor Output state LED indicator *
Minimum level sensing
O
P
S
hine
i R
iT R
R
RRT
O
P
S
ar
i R
iT R
R
RRT
Maximum level sensing
C
P
S
svt
i R
iT R
R
RRT
C
P
S
nesvt
i R
iT R
R
RRT
* Variant E without LED state indicator
Sensor for each ash of the LED switches its output on for approx. 3 ms. This period is sufciently
short to avoid unwanted switching of relay contacts. For binary inputs, we recommend to set the
lter so as not to respond to pulses shorter than 3 ms.
Units Dinel NSSU, NDSU a NLCU with transistor switch (T) detects and transmitts these pulses
to the output.

13
Dinel CLS23
11 .
order code
CLS 23 E Cable
Performance:
N – Normal for non-explosive areas
E – Extended temperature range variants for non-explosive
areas (without LED)
NT – High temperature variants for non-explosive areas
Xi (intrinsically safe) for hazardous areas
XiT (intrinsically safe), high temperature variants
Process connection:
G3/8 Pipe thread G3/8
G1/2 Pipe thread G1/2
M18 Metric thread M 18x1,5
M20 Metric thread M20x1,5
NPT Sealing thread 1/214 NPT
Output type:
P– PNP (Open collector)
S 2-wire electronic switch
R– NAMUR (For Xi variants only)
Electric connection:
A– Cable outlet (+ Spec. the length of the cable)
C– Connector – (+ Spec. type of the socket)
except variant A
Type and electrode performance:
10 Uncoated short bar, length 30mm
11 Insulated (coated) short bar (PP), length 30 mm
12 Insulated (coated) short bar (FEP), length 30 mm
20 Partly insulated rod (FEP), length 50 ...1000 mm
21 Fully insulated rod (FEP), length 50 ...1000 mm
30 Uncoated removable rod, length 50 ...1000 mm
Length of cable in meters
(variant “A“)
Electrode length in mm
12 .
correct sPeciFication examPles
cable m
(N) For non-explosive areas; (10) Uncoated short bar electrode 30 mm, (A) Cable outlet with 5 m xed cable; (S) 2-wire electronic
switch; (G3/8) Process connection with pipe thread G3/8”
cable m
(E) Extended temperature range performance for non-explosive areas; (30) Uncoated removable rod electrode; (A) Cable outlet with
10 m xed cable; (S) 2-wire electronic switch; (G1/2) Process connection with pipe thread G1/2”; (E450) Electrode length 450 mm.
T
(NT) High temperature variants for non-explosive areas; (20) Partly insulated rod electrode (FEP); (C) Electrically connection with
connector; (S) 2-wire electronic switch; (M18) Process connection with metric thread M18x1.5; (E320) Electrode length 320 mm.
iRT
(Xi) Intrinsically safe for hazardous areas; (11) Insulated (coated) short bar (PP) electrode 30 mm (C) Electrically connection with
connector; (R) NAMUR output type; (NPT) Process connection with sealing thread 1/2 – 14 NPT.

CLS23 Dinel
14
It is forbidden to make any changes or interventions to the CLS–23 sensor without the
consent of the producer. Any repairs must only be carried out by the producer or author-
ized service organisations.
Assembly, installation, commissioning, service and maintenance of the CLS23 level
sensor must be carried out in accordance with this manual and the provisions of valid
standards for the installation of electrical equipment must be complied with.
14 .
Use,maniPUlation and maintenance
The level meter does not reuire any personnel for its operation.
13 .
saFety,Protections,comPatibility and exPlosion ProoF
The level sensor is euipped with a protection against electric shoc on electrode polarity overvoltage
and shortterm current overload on the output.
lectromagnetic compatibility is provided by conformity with standards
m a .
plosion proof i and iT is eamined T strava Radvanice certicate o.
T T .
upplied electrical euipment matches the reuirements of valid uropean directives for safety and
electromagnetic compatibility. The declaration of onformity for the above mentioned product was
issued.
S
f the apparatus is used as device of roup and with using of an approved power supply device
which output parameters comply with reuired input parameters it is necessary to have an galvanic
separation or in case of apparatus without galvanic separation ener barriers it is necessary to
provide euipotential eualiing between sensor and barrier earthing point.
esign i can be used in one . ther design i can be used in
one only electrode part and head with electronics can be used only in one .
mbient temperature Tamb ...
Temperature of measured medium according to design variant
i typ to
i typ to
i typ iT to
15 .
general conditions and warranty
inel s.r.o. guarantees for the period of three years that the product has the characteristic as in
technical specication is mentioned. The guarantee can be invoed only when the product is com-
pleted by original invoice and guarantee list. This guarantee does not cover the damages resulting
from misuse improper installation or incorrect maintenance.

CLS23 Dinel
16
17 .
sPeciFications
technical sPeciFications
upply voltage ...
upply current utput type
utput type
ma. m state
ma. m state
witched current in. a. utput type
utput type
ma. m
m m min. ma.
Remanent voltage state utput type
utput type
utput time delay s
rotection class a
able
for cable outlet performance
T i iT
mm mm2 vstup type
ilicone mm2
eight
with m cable and mm electrode
i
T iT
ppro. g
ppro. g
electrical Parameters
– T
upply voltage ...
urrent supply state R m m
a. internal values i i m i m i n i
oupling capacity lectric strength n
able parameters Typical pm
Typical m
Process connection
Type Size Marking
etric thread M18
etric thread M20
ipe thread G3/8
ipe thread G1/2
ealing thread NPT
oUtPUt tyPe
Output Variants
T
T
R R i iT
material PerFormance
Sensor part Variants Material
ousing ll variants lastic
rocess coupling ll variants tainless steel .r. .
lectrode ll variants tainless steel .r. .
lectrode insulation lastic
lectrode insulation lastic

17
Dinel CLS23
working areas
(EN 60079-101)
erformance for noneplosive areas
tended temperature performance for noneplosive areas
T
igh temperature performance for noneplosive areas
iiT
iiT
erformance for eplosive areas iThigh temperature ia T a
b
with intrinsically safe supply units electrode part one housing
one
i erformance for eplosive areas ia T a with intrinsically safe
supply units whole sensor one
iT
igh temperature performance for eplosive areas
ia T ab
with intrinsically safe supply units electrode part one housing one .
temPeratUre and PressUre resistance
variants N, E, NT
Variant
(Performance) Temperature tpTemperature tmTemperature taMax. operating pressure for temperature tp
to 30°C to 85°C to 105°C to 130°C do 150°C
CLS23N10 -25°C ... +105°C -25°C ... +105°C -20°C ... +80°C 8 MPa 6 MPa 5 MPa
CLS23E10 -25°C ... +120°C -25°C ... +120°C -25°C ... +105°C 8 MPa 6 MPa 5 MPa
CLS23NT10 -30°C ... +150°C -30°C ... +150°C -20°C ... +80°C 8 MPa 6 MPa 5 MPa 4 MPa 3 MPa
CLS23N11 -10°C ... +105°C -10°C ... +105°C -10°C ... +80°C 7 MPa 5 MPa 4 MPa
CLS23E11 -10°C ... +105°C -10°C ... +105°C -10°C ... +105°C 7 MPa 5 MPa 4 MPa
CLS23N12 -25°C ... +105°C -25°C ... +105°C -20°C ... +80°C 8 MPa 6 MPa 5 MPa
CLS23E12 -25°C ... +120°C -25°C ... +120°C -25°C ... +105°C 8 MPa 6 MPa 5 MPa
CLS23NT12 -30°C ... +150°C -30°C ... +150°C -20°C ... +80°C 8 MPa 6 MPa 5 MPa 4 MPa 3 MPa
CLS23N20 -25°C ... +105°C -30°C ... +150°C * -20°C ... +80°C 3 MPa 2,5 MPa 2 MPa
CLS23E20 -25°C ... +120°C -30°C ... +150°C * -25°C ... +105°C 3 MPa 2,5 MPa 2 MPa
CLS23NT20 -30°C ... +150°C -30°C ... +150°C -20°C ... +80°C 3 MPa 2,5 MPa 2 MPa 1,5 MPa 1 MPa
CLS23N21 -25°C ... +105°C -30°C ... +150°C * -20°C ... +80°C 3 MPa 2,5 MPa 2 MPa
CLS23E21 -25°C ... +120°C -30°C ... +150°C * -25°C ... +105°C 3 MPa 2,5 MPa 2 MPa
CLS23NT21 -30°C ... +150°C -30°C ... +150°C -20°C ... +80°C 3 MPa 2,5 MPa 2 MPa 1,5 MPa 1 MPa
CLS23N30 -25°C ... +105°C -30°C ... +150°C * -20°C ... +80°C 8 MPa 6 MPa 5 MPa
CLS23E30 -25°C ... +120°C -30°C ... +150°C * -25°C ... +105°C 8 MPa 6 MPa 5 MPa
CLS23NT30 -30°C ... +150°C -30°C ... +150°C -20°C ... +80°C 8 MPa 6 MPa 5 MPa 4 MPa 3 MPa
* Valid for top mounting (in vertical position)

CLS23 Dinel
18
temPeratUre and PressUre resistance
variants Xi, XiT
Variant
(Performance) Temperature tpTemperature tmTemperature taMax. operating pressure for temperature tp
to 30°C to 85°C to 105°C to 130°C to 150°C
CLS23Xi10 -25°C ... +105°C -25°C ... +105°C -20°C ... +75°C 8 MPa 6 MPa 5 MPa
CLS23XiT10 -30°C ... +150°C -30°C ... +150°C -20°C ... +75°C 8 MPa 6 MPa 5 MPa 4 MPa 3 MPa
CLS23Xi11 -10°C ... +105°C -10°C ... +105°C -10°C ... +75°C 7 MPa 5 MPa 4 MPa
CLS23Xi12 -25°C ... +105°C -25°C ... +105°C -20°C ... +75°C 8 MPa 6 MPa 5 MPa
CLS23XiT12 -30°C ... +150°C -30°C ... +150°C -20°C ... +75°C 8 MPa 6 MPa 5 MPa 4 MPa 3 MPa
CLS23Xi20 -25°C ... +105°C -30°C ... +150°C * -20°C ... +75°C 3 MPa 2,5 MPa 2 MPa
CLS23XiT20 -30°C ... +150°C -30°C ... +150°C -20°C ... +75°C 3 MPa 2,5 MPa 2 MPa 1,5 MPa 1 MPa
CLS23Xi21 -25°C ... +105°C -30°C ... +150°C * -20°C ... +75°C 3 MPa 2,5 MPa 2 MPa
CLS23XiT21 -30°C ... +150°C -30°C ... +150°C -20°C ... +75°C 3 MPa 2,5 MPa 2 MPa 1,5 MPa 1 MPa
CLS23Xi30 -25°C ... +105°C -30°C ... +150°C * -20°C ... +75°C 8 MPa 6 MPa 5 MPa
CLS23XiT30 -30°C ... +150°C -30°C ... +150°C -20°C ... +75°C 8 MPa 6 MPa 5 MPa 4 MPa 3 MPa
* Valid for top mounting (in vertical position)
tm Medium
operating temp
tp Temp. in process
connection place
ta
Ambient temperature
range (on housing)
ariants
N; E; Xi;
ariants
NT; XiT;

Version:
industrial electronics
Microlectra bv.
www.microlectra.nl
Microlectra bv.
Augustapolder 12. 2992 SR Barendrecht. The Netherlands.
www.microlectra.nl [email protected]
Other manuals for CLS-23
2
Table of contents
Other Dinel Accessories manuals
Popular Accessories manuals by other brands

SELT
SELT BORA installation manual

PCB Piezotronics
PCB Piezotronics PCB-320C04 Installation and operating manual

ESI
ESI MAYA44 USB user manual

Elk
Elk 319HRR quick start guide

Hubbell
Hubbell Direct Drive Electric Cable Reels S-21 Installation and maintenance instructions

CS Instruments
CS Instruments Vortex VX 570 instruction manual