Digital Monitoring Products CellCom Installation Guide
4
CellCom System Messages
ThefollowingmessagesarecommunicatedtotheDMPSCS-1RreceivertoindicateCellComstatus:
130WARNING:CellCommunicatorBusFailed
COMMUNICATIONSECURITYFEATURE
The communication on the bus between the panel and the cellular communicator has failed while no areas of
the system were armed. This message may originate from both the panel and the cellular communicator as both
monitorthebus.TherestoralmessageisS132.
131ALARM:CellCommunicatorBusFailed
SERVICENOTIFICATIONFEATURE
The communication on the bus between the panel and the cellular communicator has failed while any area of the
system was armed. This message may originate from both the panel and the cellular communicator as both monitor
thebus.TherestoralmessageisS132.
132CellCommunicatorBusRestored
SERVICENOTIFICATIONFEATURE
The communication on the bus between the panel and the cellular communicator has restored. Message is sent
fromthepaneltothereceiverandisarestoralforS130andS131.
133WARNING:CellCommunicatorDCFailed
SERVICENOTIFICATIONFEATURE
The panel has received a message from the cellular communicator that its input DC voltage is missing or low. The
cellularcommunicatorisoperatingfromitsinternalbattery.TherestoralmessageisS134.
134CellCommunicatorDCRestored
SERVICENOTIFICATIONFEATURE
The panel has received a message from the cellular communicator that its input DC voltage has restored. This
messageisarestoralforS133.
135WARNING:CellCommunicatorLowBattery
SERVICENOTIFICATIONFEATURE
The panel has received a message from the cellular communicator that the cellular communicator’s standby
batteryislowormissing.TherestoralmessageisS136.
136CellCommunicatorBatteryRestored
SERVICENOTIFICATIONFEATURE
The panel has received a message from the cellular communicator that the cellular communicator’s standby
batteryhasrestored.ThismessagerestoresS135.
137WARNING:CellCommunicatorTamper
SECURITYFEATURE
Thepanelhasreceivedamessagefromthecellularcommunicatorthatthecellularcommunicator’sbuilt-in
tamper circuit was placed in an open condition while no areas of the system were armed. The restoral message is
S139.
138ALARM:CellCommunicatorTamper
SECURITYFEATURE
Thepanelhasreceivedamessagefromthecellularcommunicatorthatthecellularcommunicator’sbuilt-in
tamper circuit was placed in an open condition while one or more areas of the system were armed. The restoral
messageisS139.
139CellCommunicatorTamperRestored
SECURITYFEATURE
Thepanelhasreceivedamessagefromthecellularcommunicatorthatthecellularcommunicator’sbuilt-in
tampercircuitwasrestoredtoanormalcondition.ThismessageisarestoralforS137andS138.
AllthemessagesabovearecommunicatedbytheXR100/XR500controlpanelexceptS130andS131Cell
CommunicatorBusFailwhichissentbyboththepanelandCellCom.Forcompleteinformation,refertotheHost
CommunicationSpecication(LT-0086).