
f+
ARD
N
L3
L2
N
Lastseite / load-circuit
AUX
Vfour-pole, ARD (automatic reclosing device)
Testing and functional check (Selftest and Selftest restart)
After switching on the operating voltage (1) move the toggle to position I (2).
The automatic test cycle is activated as soon as the slider is moved left to posi-
tion AUTO ON, so that the toggle is completely covered (3). The green LED
illuminates (4).
Automatic operation is deactivated as soon as the slider is moved right to posi-
SET
CLACK
3
LED EIN
LED ON
4
2
5
LED AUS
LED OFF
6
1EIN
ON
SET
SET
SET
SET
Selftest/Selftest Restart EIN/ONSelftest/Selftest Restart AUS/OFF
Selftest/Selftest Restart EIN/ONSelftest/Selftest Restart AUS/OFF
Manual functional check (Selftest and Selftest restart)
When the operating voltage (1) is on and once automatic operation (2) is deacti-
vated and test button T (3) is pressed, the device must trip (4).
SET
2
4
1EIN
ON
3
SET
SET
SET
SET
Selftest/Selftest Restart EIN/ONSelftest/Selftest Restart AUS/OFF
Selftest/Selftest Restart EIN/ONSelftest/Selftest Restart AUS/OFF
Installation and operating instructions
for two/four-pole residual current circuit
breakers DRCCB 5 ST and DRCCB 5 STR
-
ists. The installation of devices of this type is not appropriate for electrical lay-
persons due to the considerable potential dangers. The installation and operat-
ing instructions must be kept so that it can be referred to at a later stage. The
operator of the electrical system must be informed about the application and
function of this protective device.
Application instructions and warnings
Devices with visible damage must not be installed or used.
Operation must only occur under normal ambient conditions free of corro-
sive gases in order to preserve the correct tripping function in the long term.
Corrosive gases include chlorine, ammonia and sulphur.
Erroneous tripping due to operation related leakage currents or atmospher-
ic interference cannot be ruled out with absolute certainty.
-
stream installation.
According to standard DIN VDE 0100-530, automatic restart is only permit-
ted in areas where only trained electricians have access.
Intended use and installation
Series DRCCB 5 protective devices are type A pulsating AC-DC sensitive resid-
ual current circuit-breakers (RCCBs) which perform a monthly selftest without
interrupting the power supply. They are used to protect electrical systems by
DRCCB 5 ST (selftest): A monthly selftest is performed without interrupting
the power supply.
DRCCB 5 STR (selftest restart): A monthly selftest is performed without inter-
rupting the power supply. The insulation resistance is also measured every two
minutes after a trip (system check). If this resistance reaches a safe value, the
system is automatically restarted.
Installation notes
The device is snapped onto a mounting rail in accordance with EN 60715. The
connection must be made in accordance with the wiring diagram. Guide all ac-
tive conductors and the neutral conductor through the circuit breaker. Supply
must come from the top.
N
Tf+
ARD
N
L
Lastseite / load-cicuit
AUX
Vtwo-pole, ARD (automatic reclosing device)
SET
AUX
Doepke
||
DE EN