Inhaltsverzeichnis
1. Allgemeines.............................. 2
2. Kodierung................................. 2
3. Inbetriebnahme ........................ 2
4. Anzeigen .................................. 3
5. Technische Daten .................... 3
6. Garantie ................................... 4
13. Anschlussschema / Connection
Diagram.................................... 8
Table of Contents
7. General Information ................. 5
8. Coding...................................... 5
9. Putting into Service .................. 5
10. Indicators.................................. 6
11. Technical Data ......................... 6
12. Guarantee ................................ 7
13. Anschlussschema / Connection
Diagram.................................... 8

2 3931181/02/05/D
Doepke
Bedienungsanleitung
Dupline 4-fach Relaisausgabe DSM 4R
1. Allgemeines
Das DSM 4R ist eine Komponente des Dupline-Installationssystems und ermöglicht das
Schalten von vier unabhängigen Verbrauchern, die auf verschiedene Phasen aufgeteilt
sein dürfen. Jeder Verbraucher darf dabei eine Stromaufnahme von bis zu 16 A aufwei-
sen.
Jeder Schaltkanal besitzt eine physikalische Rückmeldung, die eine tatsächlich vorhan-
dene Ausgangsspannung anzeigt. Diese Rückmeldung erfolgt zum einen über die LED
in der Gerätefront, zum anderen kann sie über den Dupline-Bus erfolgen.
Die in der frontseitigen Kodier- und Testbuchse angebrachte, grüne LED zeigt die ord-
nungsgemäße Arbeitsweise des Dupline-Bussignals an.
Die Schaltrelais sind remanent ausgeführt, was zu einer Zustandsspeicherung bei Aus-
fall der Versorgungsspannung führt. Ein fehlerhaftes Dupline-Signal führt wahlweise zu
einer Zwangs-Einschaltung oder Ausschaltung aller Ausgänge.
2. Kodierung
Mit dem Handkodiergerät DHK 1 kann über die Modularbuchse an der Front des
DSM 4R jedem Schaltkanal jede beliebige Adresse zwischen A1 und P8 zugeordnet
werden. Die Kanalzuordnung ist wie folgt:
Funktionen, die nicht benötigt werden, sollten unkodiert bleiben. Die Kodierung des
DSM 4R kann ohne Versorgungsspannung oder Dupline-Signal vorgenommen werden.
Sie bleibt dauerhaft erhalten, kann aber jederzeit überschrieben werden.
Die Ausgänge sind ab Werk so konfiguriert, dass sie bei Busausfall eingeschaltet wer-
den. Diese Konfiguration kann ebenfalls mit dem DHK 1 geändert werden. Bei Konfigu-
ration des Wertes „0“ werden bei Busausfall alle Ausgänge ausgeschaltet, bei „1“
eingeschaltet.
3. Inbetriebnahme
Die Installation darf nur von einer autorisierten Fachkraft vorgenommen werden. Bei der
Installation ist das Anschlussschema zu beachten. Alle anzuschließenden Leitungen
müssen spannungsfrei sein.
Um die physikalische Rückmeldung des Gerätes zu nutzen, ist zu jedem rückzumelden-
den Kanal der entsprechende N-Anschluss zu beschalten. Fehlt der N-Anschluss eines
Kanals, leuchtet die entsprechende LED des Kanals nicht und es findet keine Rückmel-
dung über den Dupline-Bus statt.
Die N-Anschlüsse dürfen nicht zum Durchschleifen der N-Leiter mehrerer Verbraucher
benutzt werden. Bei Stromkreisen, die über unterschiedliche FI-Schutzschalter geführt
werden, ist zudem auf die richtige N-Zuordnung zu achten.
Verbindungen zwischen dem Dupline-Signal und der 24 V-Versorgung oder Verbindun-
Kanal Beschreibung Kanal Beschreibung
1 Relais-Ausgangssignal 1 5 Rückmeldesignal 1
2 Relais-Ausgangssignal 2 6 Rückmeldesignal 2
3 Relais-Ausgangssignal 3 7 Rückmeldesignal 3
4 Relais-Ausgangssignal 4 8 Rückmeldesignal 4

3931181/02/05/D 3
Doepke
gen zum Erdpotenzial führen zu Störungen und sind nicht zulässig.
Auf die richtige Polarität der Versorgungsspannung und des Dupline-Signals ist zu ach-
ten. Folgende Tabelle zeigt die Anschlussbelegung:
Um den Forderungen für Schutzkleinspannung zu genügen, ist bei der Installation die
VDE0100, Teil 410, zu beachten und anzuwenden.
Bitte achten Sie beim Anschluss darauf, dass das maximale Drehmoment der Klemmen
von 0,6 Nm nicht überschritten wird.
Das patentierte Schnappsystem erlaubt ein einfaches Entfernen des Gerätes von der
Hutschiene indem das Gehäuse bis zum Ausrasten hochgeschoben wird.
4. Anzeigen
5. Technische Daten
Klemme Beschreibung Klemme Beschreibung
1.1/1.5 Schaltkanal 1 (LIN/LOUT) 1.2/1.6 Rückmeldeeingang 1 (N)
2.1/2.5 Schaltkanal 2 (LIN/LOUT) 2.2/2.6 Rückmeldeeingang 2 (N)
3.1/3.5 Schaltkanal 3 (LIN/LOUT) 3.2/3.6 Rückmeldeeingang 3 (N)
4.1/4.5 Schaltkanal 4 (LIN/LOUT) 4.2/4.6 Rückmeldeeingang 4 (N)
1.3 Dupline Signalleiter - (Dupline-) 1.7 Dupline Signalleiter + (Dupline+)
1.4 0 VDC Betriebsspannung 1.8 +24 VDC Betriebsspannung
Anzeige Beschreibung
Grüne „BUS OK“-
LED
Dupline-Bus:
Aus: Busstörung / An: Bus OK
Rote LED
Schaltrelais 1..4:
Aus: Relais offen (oder N-Anschluss fehlend)
An: Relais geschlossen
Min. Typ. Max.
Dupline
Stromaufnahme 10 µA
Eingangskanäle 4 Rückmeldesignale (Kanäle 5..8)
Ausgangskanäle 4 Relaisausgänge (Kanäle 1..4)
Rückmeldung
Art über N-Bezugspotenzial
Erforderliche Ausgangsspannung 100 V AC/DC
Ausgänge
Art Schaltrelais
AC
Spannung 12 VAC 250 VAC
Nennstrom (pro Ausgang) 100 mA 16 A
DC
Spannung 12 VDC 30 VDC
Nennstrom (pro Ausgang) 100 mA 10 A

4 3931181/02/05/D
Doepke
6. Garantie
Für fachgerecht montierte, unveränderte Geräte gewähren wir ab Kauf durch den End-
verbraucher die gesetzliche Gewährleistungsfrist. Die Garantie bezieht sich nicht auf
Transportschäden sowie Schäden, die durch Kurzschluss oder Überlastung entstanden
sind. Bei Fertigungs- und Materialfehlern, die innerhalb der Gewährleistungsfrist erkannt
werden, leistet unser Werk kostenlosen Ersatz. Bei Öffnen des Gerätes erlischt der Ga-
rantieanspruch.
Lampenlastena
Glühlampen 3000 W
HV-Halogenlampen 2500 W
Leuchtstofflampen 2400 W
Leuchtstofflampen mit EVG 600 W
Gasentladungslampen max. 1000 W (70 µF), 1250 W (100 µFb)
Kondensator zur Kompensation max. 70 µF, (100 µFb)
Energiesparleuchten mit KVG 1250 W
Energiesparleuchten mit EVGc300 W
Betriebsspannung
Nennbetriebsspannung 21,5 VDC 24 VDC 26,5 VDC
Stromaufnahme 6 mA 8 mA 12 mA
Erlaubte Brummspannung 100 mVpp
Anschlüsse
Art Zugbügelklemmen
Klemmbereich 0,4 mm ∅2,5 mm²
Drehmoment 0,6 Nm
Gehäuse
Art Verteilereinbaugehäuse nach DIN43880 für Hut-
schienenmontage nach DIN EN 50022
Maße 72 x 85 x 58 (B x H x T in mm) / 4 TE
Material Polycarbonat
Allg. technische Daten
Betriebstemperatur -10°C +45°C
Luftfeuchtigkeit max. 85% (Betauung nicht zulässig)
Schutzart / Normen IEC60669, EN55022 / EN50081-1 und EN55024
/ EN50082-1
Bestellnummer, -bezeichnung 09 501 100, Vierfach-Relaisausgabe DSM 4R
a. Die Angaben beziehen sich auf eine Mindestlebensdauer von 25000 Schaltspielen und
den Anschlussbedingungen nach IEC60669.
b. mindestens 5000 Schaltspiele
c. Diese Angaben sind stark herstellerabhängig - ggf. bitte anfragen.
Min. Typ. Max.

3931181/02/05/D 5
Doepke
Operating Instructions
Dupline 4-way Relay Output DSM 4R
7. General Information
The DSM 4R is a component of the Dupline installation system. It permits the switching
of four independent loads, which may be operated on different phases. Each load can
have a current consumption of up to 16 A.
Each switching channel is provided with a physical acknowledgement feature to indicate
the output voltage which is actually present. This acknowledgement is given by the LED
on the front of the device or, on the other hand, may be given via the Dupline bus.
The green LED located in the frontal coding and test socket indicates that the Dupline
bus signal is functioning properly.
The all-or-nothing relays are designed for retentivity, which means that their status is
stored should a power failure occur. A faulty Dupline signal will result in all outputs being
automatically either switched on or switched off.
8. Coding
With the hand encoder DHK 1 each channel can be assigned any address between A1
and P8 using the modular plug at the front of the DSM 4R. The channel allocation is as
follows:
The outputs are configured at the works so that they are switched on if a bus failure oc-
curs. This configuration can also be changed with the DHK 1. If the value "0" is configu-
red, all outputs are switched off in the event of a bus failure; if "1" is set, they are switched
on.
9. Putting into Service
Commissioning may only be carried out by an authorised trained technician. Observe the
connection diagram when installing. All lines to be connected must be dead.
In order to utilize the physical acknowledgement feature of the device, each channel to
be acknowledged has to be wired to the appropriate N-terminal. If the N-connection of a
channel is missing, the relevant LED of the channel will not light up and no acknowledg-
ment will be given via the Dupline bus.
The N-connections may not be used as a feed-through for the N-conductors of several
loads. In the case of circuits involving different RCCBs, care should also be taken that N
is correctly assigned.
Connections between the Dupline signal and the 24V supply, or connections to earth po-
tential, will cause malfunctions and are not permissible.
Channel Description Channel Description
1 Relay output signal 1 5 Acknowledge signal 1
2 Relay output signal 2 6 Acknowledge signal 2
3 Relay output signal 3 7 Acknowledge signal 3
4 Relay output signal 4 8 Acknowledge signal 4

6 3931181/02/05/D
Doepke
Check that the polarity of the supply voltage and the Dupline signal are correct.
In order to meet the requirements for protective low voltage, VDE0100, Part 410, should
be observed and put into practice during installation.
When connecting please observe that the maximum torque of the terminals of 0.6 Nm
will not be exceeded.
The patented snap-on system makes it easy to remove the device from the rail by simply
pushing the housing upwards until it disengages.
10. Indicators
11. Technical Data
Terminal Description Terminal Description
1.1/1.5 Switching ch. 1 (LIN/LOUT) 1.2/1.6 Acknowledge input 1 (N)
2.1/2.5 Switching ch. 2 (LIN/LOUT) 2.2/2.6 Acknowledge input 2 (N)
3.1/3.5 Switching ch. 3 (LIN/LOUT) 3.2/3.6 Acknowledge input 3 (N)
4.1/4.5 Switching ch. 4 (LIN/LOUT) 4.2/4.6 Acknowledge input 4 (N)
1.3 Dupline signal conductor -
(Dupline-)
1.7 Dupline signal conductor +
(Dupline+)
1.4 0 VDC operating voltage 1.8 +24 VDC operating voltage
Indicator Description
Green “BUS OK”
LED
Dupline bus:
Off - bus fault / On - bus OK
4 red LED All-or-nothing relays 1..4:
Off - Relay open or no N-connection / On - Relay closed
Min. Typ. Max.
Dupline
Current input 10 µA
Input channels 4 acknowledge signals (channels 5..8)
Output channels 4 output switching signals (channels 1..4)
Acknowledgement
Type using N-Potential
Necessary output voltage 100 V AC/DC
Relay outputs
Type All-or-nothing relay
AC
Voltage 12 VAC 250 VAC
Load capacity (per output) 100 mA 16 A
DC
Voltage 12 VDC 30 VDC
Load capacity (per output) 100 mA 10 A

3931181/02/05/D 7
Doepke
12. Guarantee
All professionally installed, unaltered devices are covered by warranty during the statu-
tory guarantee period from the day of purchase by the end user. The guarantee is not
applicable to damage incurred during transport or caused by short-circuit or overloading.
In the event of defects in workmanship or material, which are discovered within the guar-
antee period, the company will provide a replacement free of charge. The guarantee will
be rendered null and void if the device is opened or tampered with.
Lamp loadsa
Incandescent lamps 3000 W
HV-halogen lamps 2500 W
Fluorescent lamps 2400 W
Fluorescent lamps with el. ballast 600 W
Gas discharge lamps max. 1000 W (70µF), 1250 W (100µFb)
Capacitor for compensation max. 70 µF (100µFb)
Energy-saving lamps, conv.
ballast
1250 W
Energy-saving lamps, el. ballastc300 W
Operating Voltage
Rated operating voltage 21.5 VDC 24 VDC 26.5 VDC
Current input 6 mA 8 mA 12 mA
Ripple voltage 100 mVpp
Terminals
Type Strain-relief clamps
Contact area 0.4 mm ∅2.5 mm²
Torque 0.6 Nm
Housing
Type Distribution installation housing to DIN 43880 for
rail-mounting to DIN EN 50022
Dimensions 72 x 85 x 58 (B x H x T in mm) / 4 modules
Material Polycarbonate
General technical data
Ambient temperature -10°C +45°C
Atm. humidity max. 85% (exposure to dew not permissible)
Encl. protection type / standards IEC60669, EN55022 / EN50081-1 and EN55024
/ EN50082-1
Order number, description 09 501 100, Four-way relay output DSM 4R
a. The data relate to a minimum service life of 25000 switching cycles and the connection
requirements as per IEC 60069.
b. Min. 5000 switching cycles
c. These data are largely dependent upon the manufacturer. In case of doubt, please refer!
Min. Typ. Max.

8 3931181/02/05/D
Doepke
13. Anschlussschema / Connection Diagram
Sollten Sie Fragen zu diesem Produkt
oder zum Dupline-System haben, wen-
den Sie sich bitte an:
In case of queries concerning this
product or the Dupline system plea-
se contact:
Doepke
Schaltgeräte GmbH & Co. KG
Stellmacherstraße 11
D-26506 Norden, Germany
Tel.: +49 (0) 4931/1806-0
Fax: +49 (0) 4931/1806-101
E-mail:
Internet:
http://www.doepke.de
3931181/02/05/D
1.1
Lin
1.3
D-
1.4
DC-
1.8
DC+
2.4 2.8 3.4 3.8 4.4 4.8
1.7
D+
2.3 2.7 3.3 3.7 4.3 4.7
1.2
N
1.6
N
2.2
N
2.6
N
3.2
N
3.6
N
4.2
N
4.6
N
1.5
Lout
2.1
Lin
2.5
Lout
3.1
Lin
3.5
Lout
4.1
Lin
4.5
Lout
Dupline -
Dupline +
0V DC
+24V DC
L3
L2
L1
N
DSM 4R
DSM 4R
EIN
BUS OK
BUS OK
EIN EIN EIN
Doepke
Dupline
3931181C
Table of contents
Languages:
Other Doepke Switch manuals
Popular Switch manuals by other brands

Weidmüller
Weidmüller Premium Line IE-SW-PL08M Series Hardware installation guide

H3C
H3C S7502 installation manual

FISCHER
FISCHER DS 11 user manual

PEHA
PEHA 405 R Installation and operating instructions

Cisco
Cisco Catalyst X6724 datasheet

TRENDnet
TRENDnet TK-204UK - DVI USB KVM Switch Quick installation guide

HMS
HMS HMS-EN2MB-R Installation sheet

Asante
Asante FriendlyNET GX4-800GBIC user manual

Guntermann & Drunck
Guntermann & Drunck DVIMUX4-USB Installation and operations

Cambium Networks
Cambium Networks cnMatrix EX1K Basic configuration guide

3One data
3One data IES7110-2GS Series user manual

Black Box
Black Box SW722A-R2 quick start guide